DOL starter switchgear rating selection in details .

Поделиться
HTML-код
  • Опубликовано: 13 окт 2024
  • Direct online starter #DOL #switchgear# rating # selection learn in details .
    click on below link for estimation sheet preparation.
    • How to make estimation... .
    Thanks Thanks Thanks for watching this video.

Комментарии • 101

  • @marcheck3400
    @marcheck3400 11 месяцев назад

    Thank you, this is a good one. A lot of tutorials forgot to include consideration of MCB trip curve characteristic in their calculation. In practice I prefer to be a bit more detailed with the trip curve calculation, but for learning this is good enough.

  • @VijaySharma-hj9kg
    @VijaySharma-hj9kg Год назад +1

    You have Given This Information Very Well

  • @durgavenkata6891
    @durgavenkata6891 2 года назад +1

    Excellent madam. Amps keliye mera formula Hp*1.34, example 10hp ka motar 10*1.34=13.4Amps isa calculate karta

  • @mubeengujjar1152
    @mubeengujjar1152 11 месяцев назад

    Thanks for this co-operation

  • @ankitpatel9429
    @ankitpatel9429 Год назад

    Madam ji your video very useful
    Please continue electrical technician or Eng. Work video uploaded

  • @jayeshprajapati3607
    @jayeshprajapati3607 2 года назад

    Medam aap ye vali video continue karte huve SFU SELECTION OR MPCB KA SELECTION KESE KARNA HE VO BATAYE

  • @iie4237
    @iie4237 Год назад +1

    informative ❤

  • @rajeshsaket910
    @rajeshsaket910 Год назад +1

    Thanks sister for waching video

  • @annurchoudhary786
    @annurchoudhary786 Год назад

    Very good video mam🎉🎉

  • @chiragchaudhari5031
    @chiragchaudhari5031 Год назад

    very helpful for interview

  • @YogeshKumar-vg5jz
    @YogeshKumar-vg5jz 2 года назад

    Madam, your channel is right on point what electrician, engineers, and technician need

  • @gitanjaliatugade8600
    @gitanjaliatugade8600 2 года назад

    Nice..info for beginners..ty mam🙏💐☺️

  • @waqar1ist
    @waqar1ist 2 года назад

    Amazing explaination Mam

  • @amitensingh
    @amitensingh 4 месяца назад

    55 kw motor k liye agar 2 se multiply karnge to 110 amp aayega but flc-96 amp hai fir kaise calculate kare

  • @sandippatil776
    @sandippatil776 Год назад +1

    for MCB rating selection why we divide by 5 to starting FLC?

  • @iamre-volve
    @iamre-volve Год назад

    Very nice

  • @mithunsarker5090
    @mithunsarker5090 7 месяцев назад

    Good information... Thanks....

  • @vaghadiyaraj23699
    @vaghadiyaraj23699 Год назад

    Type 2 coordination chart according kiya ji hai na

  • @muhammadshehbazaslam4549
    @muhammadshehbazaslam4549 3 года назад +4

    Dear Madam,
    You have selected MCB 26A, OLR around 16A...that's fine...
    But you said in DOL, motor always draws higher current at start, (130A according to video). So that point is that how motor will continue to run even starting current is higher than MCB, OLR rating? There will be no tripping? Why? Because at start current will be higher than OLR, as well as MCB rating...
    Please clear this point, thanks

    • @emmittdariel4613
      @emmittdariel4613 3 года назад

      instaBlaster...

    • @imransaifilaathi8759
      @imransaifilaathi8759 3 года назад +3

      In short!
      Motor ka starting current initially high hota kuch mili seconds k liye(nearly 2 3 cycles me). Uske baad motor apni steady condition me a jaati h. Us initial time me high current bear krne k liye hi hum c Type mcb lete hain.
      For further detail
      Ap ek baar b,c and d curve MCB k characteristics study ke lo.

    • @marcheck3400
      @marcheck3400 11 месяцев назад

      Understand that this is an old question, but commenting anyway in case somebody else needs this info.
      In general application, there are 2 types of overcurrent detection: Thermal, and magnetic. Thermal tripping uses a bimetalic strip that, during current overload, heats up and bends. The bending triggers the trip mechanism. The heating process takes time, and this introduces a time delay into the tripping action. The higher the overload current, the shorter the tripping time, which is why this is sometimes called a "inverse time" type circuit breaker.
      Magnetic tripping depends on the magnetic field strength generated by the current flowing through the circuit breaker. During overload the magnetic field is much stronger than usual, and this immediately triggers the trip mechanism. There is no time delay because change in magnetic field is immediate. This is also sometimes called "instantanous tripping".
      Overload Relay (low to medium spec models) exclusively uses thermal tripping system. This is why, in certain countries like mine, overload relays are more commonly called Thermal Relay.
      MCB uses both thermal and magnetic tripping system. The faceplate rating is usually the thermal tripping threshold, while the magnetic tripping threshold is set much higher, 3x, 5x, 10x the faceplace value depending on the MCB trip curve spec (B, C, D etc).
      During motor starting, when the current draw is very high, Overload Relay does't trip (yet) because the motor starting process is usually shorter than the bimetallic strip heat up time. However if the motor seizes up during starting and the high current draw is sustained, the Overload Relay bimetallic strip will heat up substaintially and trips. The downside to this is, if there is a short circuit, it will take some time to trip, so your wires can get heated up quite substaintially and there can be a risk of fire.
      The case with MCB is a bit compilcated because it uses both thermal and magnetic tripping. The delayed thermal tripping characteristic you see in Overload Relay is also present in MCB, so during normal motor starting it will not trip (yet), and if the motor siezes it will also eventually trip. But, once the magnetic tripping threshold is reached, the MCB will no longer use thermal tripping (which is slow) and uses magnetic tripping instead (fast). This eliminats the problem you see in Overload Relay during short circuit situation, but, as I am sure you had experience at least once in your life, MCB can be annoyingly sensitive. Proper MCB sizing therefore is a more involved process.

    • @indrak1463
      @indrak1463 9 месяцев назад

      Nice ​@@marcheck3400

  • @prahladrajak240
    @prahladrajak240 3 месяца назад

    Very nice thank you

  • @prathapmv2777
    @prathapmv2777 3 года назад

    Nice sister 👍, from Kerala.

  • @dineshpadmane8112
    @dineshpadmane8112 3 года назад

    Very well explained ma'am

  • @mahidarling8602
    @mahidarling8602 3 года назад

    Nicely explained madam...these concepts are very useful to me ...why bcz i started electrical panel board manufacturing company ...so i request u to share ur full knowledge to me madam...tq....

  • @neetuyadav6253
    @neetuyadav6253 Год назад

    Aap MPCB or MCCB se selection batao

  • @iie4237
    @iie4237 3 года назад

    very nixe video

  • @rajuakkineni5966
    @rajuakkineni5966 Год назад

    madam industrial equipment vfd's transformers's vcb sf6 breakers oprating system to explaned

  • @pathakbrakeskumar7227
    @pathakbrakeskumar7227 Год назад +1

    Tq👌👌👌👌👏👏👏

  • @ramprakashkushwaha5661
    @ramprakashkushwaha5661 3 года назад

    Thanku ma'am and switchgears control panel study in ee and eee .

  • @snehachandran5947
    @snehachandran5947 2 года назад

    Thankyou..... Very usefull

  • @ranjithp6087
    @ranjithp6087 3 года назад +1

    Mam,when motor starting time the inrush high current directly passing through the mcb and contactor.so mcb is selected higher rating,why contactor is selected same to the FLC.what is the reason?

  • @vipinthampy4669
    @vipinthampy4669 2 года назад +1

    Please explain cable sizealso taking7.5 kw as example

  • @baskaravenkatesh4444
    @baskaravenkatesh4444 2 года назад

    Excellent 👌👌👌

  • @juhisharma444
    @juhisharma444 4 года назад +2

    What a beautiful explanation.... waiting for your next vedio regarding single line diagram

  • @37prakhar
    @37prakhar 2 года назад

    Cut to cut clear

  • @ankitpatel9429
    @ankitpatel9429 Год назад

    MCB Selection me 130/5
    5 kya hai

  • @motivationmeditationrelaxa6675
    @motivationmeditationrelaxa6675 3 года назад

    Thank you sister good explanation 🙂☺️

  • @Ramjan-ali735
    @Ramjan-ali735 8 месяцев назад

    From dubai see

  • @MrSai27
    @MrSai27 3 года назад +1

    Make more videos for mcc panels🙏

  • @MukeshSingh-zw5qx
    @MukeshSingh-zw5qx 3 года назад

    Very nice explanation..thanks

  • @aishap2286
    @aishap2286 2 года назад

    Thank mam

  • @farhanshaikh6103
    @farhanshaikh6103 3 года назад

    Nice ma'am

  • @venubonthu8839
    @venubonthu8839 3 года назад

    Thank you. explanation is good

  • @ranjithp6087
    @ranjithp6087 3 года назад

    Very nice explanation thanks

  • @HariHari-jr5pg
    @HariHari-jr5pg 3 года назад

    THANK YOU. PLEASE GIVE DETAIL FOR SIZING OF SPARES TO AUTO TRANSFORMER STARTER & SIZING OF IN& OUT CABLES FOR ALL CONTROL PANELS

  • @rahulingale4386
    @rahulingale4386 3 года назад

    Good knowledge sharing for interview

  • @dulalhossain5127
    @dulalhossain5127 3 года назад +1

    Nice video

  • @Hemaldas2024
    @Hemaldas2024 6 месяцев назад

    √3 keya hai plz batao

  • @r.d.245
    @r.d.245 3 года назад

    💐👍👌

  • @stalinsubbiah3238
    @stalinsubbiah3238 10 месяцев назад

    Why we have to multiply by ten then divide by five

  • @HariHari-jr5pg
    @HariHari-jr5pg 3 года назад

    PLEASE MENTION THE SIZING OF CONTACT OR IN TRMS OF FLC*MULTIPLIER
    SUPPLY CABLE IN/OUT TO STARTE =FLC*MULTIPLIER
    MAIN CIRCUIT WIRES IN STARTER=FLC*MULTIPLIER.

  • @MukeshKumar-ed9gg
    @MukeshKumar-ed9gg Год назад

    ❤❤❤tq mam

  • @sefatullah441
    @sefatullah441 3 года назад

    please upload more videos

  • @anoop22march
    @anoop22march 3 года назад

    Thank you mam, waiting for more video

  • @engjamalhussain823
    @engjamalhussain823 3 года назад +1

    kw * 1.73 =Ifl
    now upto 50 hp motors we take 2 times the ifl I.. e I*2 =starting current
    above 50 hp we take 1.5 time
    I * 1.5 = starting current
    and select the mcb or Mccb according to the starting current
    sharjah regulation ..

  • @udaygurav6113
    @udaygurav6113 3 года назад

    👍💐

  • @vasavanileshr4674
    @vasavanileshr4674 Месяц назад

    1.732

  • @patelkaushik2996
    @patelkaushik2996 2 года назад

    13.05×10 esme 10 value kiski he

  • @uzzalchakma9783
    @uzzalchakma9783 3 года назад +1

    ♥♥♥♥♥

  • @HariHari-jr5pg
    @HariHari-jr5pg 3 года назад

    I WANT TO KNOW THE SIZING OF SPARES, CONRACTORS, OLR MAIN& CONTROL CIRCUIT WIRES TO ALL DOL, STAR&DELTA,ATS,RRS,VFD&VFD ETC.

  • @patelkaushik2996
    @patelkaushik2996 2 года назад

    13.05/5 esme 5 value kiski he

  • @rashidmomin8429
    @rashidmomin8429 Год назад

    Why you decide by 5

  • @dheeranstudiotamil4777
    @dheeranstudiotamil4777 3 года назад

    I love u.pls reply

  • @kuldeepraghuwanshi60
    @kuldeepraghuwanshi60 3 года назад +1

    Like🥀🥀👌👌

  • @krusnendusahu6096
    @krusnendusahu6096 3 года назад

    Medam cable ka load calculation bataye

  • @hanif1508
    @hanif1508 3 года назад

    735.5

  • @swapnilshiyaniya5306
    @swapnilshiyaniya5306 3 года назад +2

    madam ... 1 HP = 0.746 kW

    • @prasadshigwan
      @prasadshigwan Год назад

      Her formulas also same if u check carefully sir
      For eg
      1hp motor means 0.746kw
      Put in her formula ie
      HP* 0.746=kw
      So
      1*0.746=0.746kw
      If 5hp motor then
      5*0.746=3.73kw
      And if u use kw to hp then
      Kw/0.746=hp
      3.73/0.746=5hp

  • @feresticquilorkalaivanan3383
    @feresticquilorkalaivanan3383 3 года назад

    Thank u madam thanks

  • @aslamalikhan1124
    @aslamalikhan1124 3 года назад

    Mam 1phase and 3phase load calculation for domestic and commercial ke liye NIKALNA bataiyega mam nice video

  • @jitendrakamble4446
    @jitendrakamble4446 4 месяца назад

    1 HP = 0.746 KW

  • @ranjithp6087
    @ranjithp6087 3 года назад

    How to select mccb for starters

  • @leeladharjaiswal5258
    @leeladharjaiswal5258 3 года назад

    Madam j aur k curve v hote h

  • @druganahak9130
    @druganahak9130 4 года назад

    Good

  • @Kmlsngh98
    @Kmlsngh98 3 года назад

    pls, Ma'M make more video, Please..

  • @naveenbe123
    @naveenbe123 3 года назад

    No protection for contactor when Shor circuit.....

  • @mirzasaqib4220
    @mirzasaqib4220 3 года назад

    Why you devided by 5

  • @Bindukirasoiandvlogs
    @Bindukirasoiandvlogs 4 года назад

    wow

  • @ayyoobkhan6642
    @ayyoobkhan6642 4 года назад +2

    130/5 for MCB rating clcultion , where u got 5?

    • @akhtar2830
      @akhtar2830 3 года назад

      I have also same doubt

    • @akhtar2830
      @akhtar2830 3 года назад

      Pls reply mam

    • @siddharthsorathia5449
      @siddharthsorathia5449 3 года назад +1

      Bcoz C class mcb 5-10 times higher current carry kar sakta he.matlab 26amp ka mcb lagaya to at starting 5 times higher current carry karlega..kuch micro-sec ke liye hi 5-10 times current flow hoga

    • @harishdsouza7082
      @harishdsouza7082 3 года назад

      @@siddharthsorathia5449 right

  • @aamirsuhail2512
    @aamirsuhail2512 7 месяцев назад

    Never rely FLC on twice of kW, you r giving wrong information

  • @nikhilchavhan2441
    @nikhilchavhan2441 9 месяцев назад

    KW To HP ?
    KW × 1.341
    HP To KW ?
    HP ÷ 1.341

  • @mirzasaqib4220
    @mirzasaqib4220 4 года назад

    Why 130 dividing by 5

  • @subodhsawant7144
    @subodhsawant7144 3 года назад

    Your surge current calculation is wrong ..... It's not 10 times .... FLC...

  • @G-O-P-I
    @G-O-P-I 3 года назад

    Could you speak in English???
    Mam.. I know only English

  • @snkkhan2000
    @snkkhan2000 3 года назад

    why volt is 415. what about phase.if volt is 415. insufficient information,

  • @sandipkushwaha303
    @sandipkushwaha303 11 месяцев назад

    Whatsapp grup hai ji

  • @sandippatil776
    @sandippatil776 Год назад +1

    for MCB rating selection why we divide by 5 to starting FLC?

    • @Ayansh-vv9ug
      @Ayansh-vv9ug Год назад

      Because min will be 5 times so we will devide by 5

  • @pradiptotkar2181
    @pradiptotkar2181 3 года назад

    very Nice