Double Regulating Valve | DRV | in Urdu/Hindi

Поделиться
HTML-код
  • Опубликовано: 18 апр 2021
  • This is an HVAC conceptual video about the "Double Regulating Valve - DRV" regarding the HVAC system valves which are commonly used in chilled/hot water loops at AHUs and FCUs with accessories. This video is in the Urdu/Hindi language. It is basic learning detailed information for new or fresh engineers or technical field persons. It is also important for HVAC / MEP technical staff to leaning points of view. Here sharing my experience and knowledge that will be helpful to learn & grow for Engineers & Technical staff. If you found anything which is inappropriate then convey it in the comments for my information and rectification in the future.
    I have explained the following in this video:
    1. What is a Double Regulating Valve?
    2. Types of the Double Regulating Valve.
    3. Application of the Double Regulating Valve.
    4. Function of the Double Regulating Valve.
    5. Setting of the Double Regulating Valve, etc.
    You can watch my videos through the following links:
    1. How airlock and water reduced in pipes?
    Video link: • How airlock and water ...
    2. Where PRV is required as per Pressure in Firefighting System?
    Video link: • Where PRV is required ...
    3. Difference Between Pressure Relief & Pressure Safety Valve
    Video link: • Difference Between Pre...
    4. Difference Between Pressure Reducing & Pressure Restricting Valve
    Video link: • Difference Between Pre...
    5. Converting Pump Head to Pressure or Vise Versa
    Video link: • Converting Pump Head t...
    6. Globe valve Vs Balancing valve
    Video link: • Globe valve Vs Balanci...
    7. Black Steel Pipe Detail | Standard ASTM A53 | Part-1
    Video Link: • Black Steel Pipe Detai...
    8. Black Steel Pipe Detail | Standard ASTM A53 | Part-2
    Video Link: • Black Steel Pipe Detai...
    9. Black Steel Pipe Detail | Standard ASTM A53 | Part-3
    Video Link: • Black Steel Pipe Detai...
    10. Two-way valve of HVAC
    Video Link: • Two-Way Valve of HVAC ...
    11. Three-way valve of HVAC
    Video Link: • Three Way Valve of HVA...
    #TanweerAhmed #DRV #HVAC #BalancingValve #MEP #Valves #balancing #regulatingvalve
    = YOU CAN FOLLOW ME ON SOCIAL MEDIA =
    WEBSITE: engineertanwee...
    FACEBOOK: web.facebook.c...
    INSTAGRAM: / tanweersethar
    LINKEDIN: / tanweer-ahmed-00142631
    RUclips: / tanweerahmed
    TIKTOK: vm.tiktok.com/...
    TELEGRAM GROUP: t.me/hvacmepenggg

Комментарии • 76

  • @TanweerAhmed
    @TanweerAhmed  2 года назад

    Automatic Balancing Valve link: ruclips.net/video/S370MfPwxg0/видео.html

    • @KhalidKhan-fx9ph
      @KhalidKhan-fx9ph Год назад +2

      Three way valve chiller which are youse

    • @TanweerAhmed
      @TanweerAhmed  Год назад +1

      What do you want to say?

    • @asgharahsan003
      @asgharahsan003 Год назад

      ​@@TanweerAhmed He wants to say that what is the purpose of using 3-way valve in chilled water line ?

  • @RehanKhan-fr4kg
    @RehanKhan-fr4kg Месяц назад +1

    Nice explained sir
    U are a gem I am preparing watching your video for hvac engineering

  • @kabeerabids
    @kabeerabids 2 года назад +1

    Jazakallah....Thanks for the explanation...you have strong knowledge about the subject

  • @aqeefshaikh5447
    @aqeefshaikh5447 2 года назад +3

    Jazakallahu khaira. your videos are really helpful to understand deeply.

  • @akmalakbar6881
    @akmalakbar6881 День назад +1

    Very nice sir

  • @user-id9nn4lx5e
    @user-id9nn4lx5e 7 месяцев назад +1

    Great explanation!

  • @shadabrehman709
    @shadabrehman709 3 года назад +1

    Very informative. Jazakallah

  • @mohammedwaseemahmed5946
    @mohammedwaseemahmed5946 13 дней назад +1

    Please post a video of difference between DRV and PICV.Also can we balance FCU with only DRV ?

    • @TanweerAhmed
      @TanweerAhmed  9 дней назад +1

      Watch my other videos of PICV and balancing valve for deep understanding

  • @hassanmrao1466
    @hassanmrao1466 Год назад +1

    good explanation sir

  • @Ehtesham147
    @Ehtesham147 2 года назад +1

    Thank you so much for your help.

  • @asifsajjad6085
    @asifsajjad6085 Год назад +1

    Good very helpful

  • @nomibhatti2400
    @nomibhatti2400 2 года назад +1

    Very very nice sir g

  • @farhatalisethar9097
    @farhatalisethar9097 3 года назад +1

    Great Ada

  • @ziyamasad2709
    @ziyamasad2709 3 года назад +1

    Jazakaallah bhai... please provide us the details of standard valve package connections in AHU & FCU including btu meter, inlet which valves are used & outlet which valves are used for constant & vfd type flow...

  • @subhashillikode8484
    @subhashillikode8484 3 года назад +2

    Good explanation, expecting more and let me known which is the good book to learn

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      Thanks, these are taken from catalogue of equipment

  • @asifjutt8824
    @asifjutt8824 3 года назад +1

    v good sir

  • @exploreskillswithdawoodmasih
    @exploreskillswithdawoodmasih 3 года назад +1

    Helpful.

  • @mohammadabdulaleem1101
    @mohammadabdulaleem1101 3 года назад +2

    Sir why we fix drv in return line please answer

    • @TanweerAhmed
      @TanweerAhmed  3 года назад +1

      Normally it is installed on the return line because of following reasons.
      1. ASHRAE Recommendations.
      2. The coil of the unit should be flooded in case the valve is closed.
      3. With a control valve on the return side, the water is at a higher pressure through the coil, reducing off gas, thereby lowering dissolved oxygen content. Lower dissolved oxygen extends equipment life by minimizing the air entrapment.
      4. If it is a hot system, some manufacturers have temperature limitations on the actuators. If there is a180°F limit on the actuator (common to some actuators), the return side is preferred as it will operate at a cooler temperature.
      5. If it is a cold system, it is always better to have less thermal breaks on the colder side (e.g.42°F water) than on the warmer return side (e.g.,56°F water). The return side installation reduces sweating on the electronic actuator, which is more prone to failure when wet.

    • @mohammadabdulaleem1101
      @mohammadabdulaleem1101 3 года назад +1

      @@TanweerAhmed thanks sir.. quick response. Jazakallah

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      Welcome

  • @AhmedAhmed-kp6ms
    @AhmedAhmed-kp6ms 3 года назад +1

    Tanveer pa g, plz guide me about fcu fresh air supply control & location of it & also control fcu air throw control.

  • @gangavaramimran
    @gangavaramimran Год назад +1

    Purpose installing Drv in Chilled water return main line

    • @TanweerAhmed
      @TanweerAhmed  Год назад

      Watch this video, I hope that you will understand

  • @ranadastgir3690
    @ranadastgir3690 2 года назад +1

    DRV FCU K IN LINE PAR LAGTY HAN YA OUT PAR. ???

  • @abdul10375
    @abdul10375 2 года назад +1

    Chilled line k ooper red color kyun liya jata he

  • @qumartanweer6589
    @qumartanweer6589 Год назад +1

    Aw sir aik drafting video banae small villa ka hvac ka.

    • @TanweerAhmed
      @TanweerAhmed  Год назад

      I don't understand. What you want to say

    • @qumartanweer6589
      @qumartanweer6589 Год назад

      @@TanweerAhmed hvac drafting video for G+1 2 floor like how to draw duct, fcu ahu Or other components related to hvac like eccentric reducer concentric reducer elbow

    • @TanweerAhmed
      @TanweerAhmed  Год назад

      @@qumartanweer6589 Sorry, I don't know drafting work. AutoCAD draftman know this work.

    • @qumartanweer6589
      @qumartanweer6589 Год назад +1

      @@TanweerAhmed ok Sir thanku, aapki videos se bahut help hote hai Thank a lot

    • @TanweerAhmed
      @TanweerAhmed  Год назад +1

      Welcome

  • @gufran548
    @gufran548 3 года назад +1

    Assalamualaikum sir
    If u have CCU unit(PAC) unit vedio please send link

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      Watch in HVAC playlist i.e. package FAHU unit

  • @tajkhan-jm9fe
    @tajkhan-jm9fe 2 года назад +1

    How to balance chilled water with metter

  • @ijazahamed1749
    @ijazahamed1749 2 года назад +1

    What is the function of double regulating valve. Can u explain in English

  • @PawanKumar-mw5uv
    @PawanKumar-mw5uv 3 года назад +1

    I need your help for some license query for global trading

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      I don't know about globel trading

  • @merajmoqueem5828
    @merajmoqueem5828 2 года назад +1

    Types of balancing

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      What do you want to say?

    • @merajmoqueem5828
      @merajmoqueem5828 2 года назад +1

      I want to know how many types of balancing valve?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      I have explained in this video and also will make more videos

  • @PawanKumar-mw5uv
    @PawanKumar-mw5uv 3 года назад +1

    Messenger I'd or anything by which I can contact you it is big project pls discuss with me

  • @imamimam994
    @imamimam994 2 года назад +1

    Assalamu aleikum bhai jaan aapka mo no Chahiye

    • @TanweerAhmed
      @TanweerAhmed  2 года назад +1

      Join my Telegram group and its link is given in each video's description and also community tab