Great video. Good Job and Nice Work. Thank you for sharing. May I ask, is it high pressure switch on liquid line was bad ? If it, how many pressure that switch will open ?
Yes that was pressure switch on liquid line, that should close on high pressure as ambient temperature was 75F should be close just like other pressure switch for different fan
I had the same problem with more than 20 units at the same time and I thought was normal 😅 due all motors same position were stopped ! My question is why all units with the same problem ? LPS bad in all of them or just the board know when send the 24v to this motor in particular
Well that depends what is ambient temperature is if it is too low then it takes some time to build up pressure in condensor coil and to activate fan motor relay, if it is too hot then fan starts right away just like other fan in the video was starting, board has nothing to do with it
Sorry, a newbie here. I understand that the relay was working but I don't get how you knew it wasn't the relay by moving the black wire from lower terminal to upper terminal.
@@yoyoman3386 ok I check step by step, condensor fan motor was not working I checked motor, it was ok then supply motor voltage by bypassing relay which was by moving black wire, motor started next step was why relay wasn't working so Traced relay through wire diagram, and found pressure switch was faulty
Thanks my AMIGO that was one of the best step by step troubleshooting
Thanks
Very informative and educational thanking you for sharing your knowledge.
Thanks
Nice video, watching from Norway, hope for more videos!
Thanks please share it to your friends
Very good job
@@maheradous9257 thanks
I appreciate LENNOX equipment, nd this was a very good video on rtu’s .
Gonna subscribe thank you for the editing, content , and posts
Thanks
Thank you for the video very well explained and to the point! New subscriber here, keep up the good work and thanks again for inspiring the newcomers
Thanks
Excellent video Bro👏👏
Thank you so much!!!
Thanks
Great informative video bro! Thanks
@@influenz1490 thanks watch my other videos and share
Nice video new follower
@@frankmesias1949 thanks
Good experience bro
@@salmannawaz5392 thanks
Great video. Good Job and Nice Work. Thank you for sharing. May I ask, is it high pressure switch on liquid line was bad ? If it, how many pressure that switch will open ?
Yes that was pressure switch on liquid line, that should close on high pressure as ambient temperature was 75F should be close just like other pressure switch for different fan
thanks for sharing.
Thanks
👏🏼
Thanks
I had the same problem with more than 20 units at the same time and I thought was normal 😅 due all motors same position were stopped ! My question is why all units with the same problem ? LPS bad in all of them or just the board know when send the 24v to this motor in particular
Well that depends what is ambient temperature is if it is too low then it takes some time to build up pressure in condensor coil and to activate fan motor relay, if it is too hot then fan starts right away just like other fan in the video was starting, board has nothing to do with it
Please send to me more videos.
@@maheradous9257 thanks please subscribe my channel you will find more videos
Perblam E2 model termsta SERVICE FIRST SENO 1577 Trane Rooftop
@@benahmedahmed831 sorry didn't get you
@@Learnhvac. ؟
I’m confused why the problem couldn’t have been the relay itself? Because it was bypassed and the motor started
That was not relay it was pressure switch actually, and I start from the component which is not working, and Traced it backward for root cause
The relay was working properly but not receiving 24v to activate it for that reason the motor not working. 24v was controlled by LPS in this case.
@@joseantoniopadronhidalgo8016 yes
Sorry, a newbie here. I understand that the relay was working but I don't get how you knew it wasn't the relay by moving the black wire from lower terminal to upper terminal.
@@yoyoman3386 ok I check step by step, condensor fan motor was not working I checked motor, it was ok then supply motor voltage by bypassing relay which was by moving black wire, motor started next step was why relay wasn't working so Traced relay through wire diagram, and found pressure switch was faulty