LENNOX Package RTU Not cooling, step by step troubleshooting

Поделиться
HTML-код
  • Опубликовано: 4 май 2024
  • LENNOX Package RTU Not cooling, step by step troubleshooting.

Комментарии • 23

  • @roqueherrera8471
    @roqueherrera8471 18 дней назад +2

    Thanks my AMIGO that was one of the best step by step troubleshooting

  • @Kaapee
    @Kaapee 8 дней назад +2

    Nice video, watching from Norway, hope for more videos!

    • @Learnhvac.
      @Learnhvac.  8 дней назад

      Thanks please share it to your friends

  • @jenniferm5375
    @jenniferm5375 23 дня назад +1

    Thank you for the video very well explained and to the point! New subscriber here, keep up the good work and thanks again for inspiring the newcomers

  • @jrh86
    @jrh86 26 дней назад +3

    Very informative and educational thanking you for sharing your knowledge.

  • @jamesortolano3983
    @jamesortolano3983 23 дня назад +1

    I appreciate LENNOX equipment, nd this was a very good video on rtu’s .
    Gonna subscribe thank you for the editing, content , and posts

  • @harbbains5718
    @harbbains5718 20 дней назад +1

    Excellent video Bro👏👏
    Thank you so much!!!

  • @MariosACandRefrigeration
    @MariosACandRefrigeration 25 дней назад +2

    thanks for sharing.

  • @roqueherrera8471
    @roqueherrera8471 18 дней назад +1

    👏🏼

  • @zekenzy6486
    @zekenzy6486 6 дней назад

    Great video. Good Job and Nice Work. Thank you for sharing. May I ask, is it high pressure switch on liquid line was bad ? If it, how many pressure that switch will open ?

    • @Learnhvac.
      @Learnhvac.  5 дней назад

      Yes that was pressure switch on liquid line, that should close on high pressure as ambient temperature was 75F should be close just like other pressure switch for different fan

  • @joseantoniopadronhidalgo8016
    @joseantoniopadronhidalgo8016 3 дня назад

    I had the same problem with more than 20 units at the same time and I thought was normal 😅 due all motors same position were stopped ! My question is why all units with the same problem ? LPS bad in all of them or just the board know when send the 24v to this motor in particular

    • @Learnhvac.
      @Learnhvac.  3 дня назад

      Well that depends what is ambient temperature is if it is too low then it takes some time to build up pressure in condensor coil and to activate fan motor relay, if it is too hot then fan starts right away just like other fan in the video was starting, board has nothing to do with it

  • @tyleramorin89
    @tyleramorin89 6 дней назад +1

    I’m confused why the problem couldn’t have been the relay itself? Because it was bypassed and the motor started

    • @Learnhvac.
      @Learnhvac.  6 дней назад

      That was not relay it was pressure switch actually, and I start from the component which is not working, and Traced it backward for root cause

    • @joseantoniopadronhidalgo8016
      @joseantoniopadronhidalgo8016 3 дня назад +1

      The relay was working properly but not receiving 24v to activate it for that reason the motor not working. 24v was controlled by LPS in this case.

    • @Learnhvac.
      @Learnhvac.  3 дня назад

      @@joseantoniopadronhidalgo8016 yes