York YMC2 Service Needed || That Doesn’t Sound Good

Поделиться
HTML-код
  • Опубликовано: 10 фев 2025
  • Met up with JCI tech to service our YMC2 chillers that have been surging and Loss of Subcooler Liquid Seal warning resolved #york #chiller #hvac

Комментарии • 18

  • @springws14lbss
    @springws14lbss 8 месяцев назад +7

    Sounded like the Titanic engine room at the start!

  • @zekenzy6486
    @zekenzy6486 8 месяцев назад +1

    Great video. Thank you for sharing. Those are big chiller

    • @subcoolHVAC
      @subcoolHVAC  8 месяцев назад +1

      Thanks for watching!

  • @jeffreyrex8232
    @jeffreyrex8232 5 месяцев назад

    That poor MOD A 😢 NRV is doing its job in the discharge. 👌🏻

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 8 месяцев назад +1

    Cool video. Glad to see they raised the liquid level....60% seems a tad high, but i get it. During start up, it seems like they always set it to 35%-37%. We do the maintenance and repairs on our customers YK's. Did they clean the heat exchanger for the VSD coolant. That can get pretty nasty over time. A lot of people wait till they get high temp alarms before doing it though. Enjoyed the video...thanks for sharing

    • @subcoolHVAC
      @subcoolHVAC  8 месяцев назад +2

      Yeah, it ran better at 42% but JCI tech settled on 50% , they backwashed the exchanger, I did see some high motor baseplate alarms in the history after they left… probably from air. The old coolant was dark . Thanks Jason! 👊

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC 8 месяцев назад +1

      @@subcoolHVAC 42% seems to be the sweet spot here.

  • @TBJK07Jeep
    @TBJK07Jeep 8 месяцев назад +2

    Loss of subcooler seal is when your drop leg temp gets lower than your condenser temp. It basically is calculating that there is flash gas instead of a full liquid seal. Also on your drive heat exchanger, pull both heads when brushing it. One side may look ok, but when you pull the other, it will look like shit. It’s more work, but in the end its better.

  • @martywatson7764
    @martywatson7764 3 месяца назад

    Is there a video out there how to replace coolant in drive cooler? Just got PM for YMC2 with HYP drive that will need coolant replaced in Spring. Thanks for video.

    • @subcoolHVAC
      @subcoolHVAC  3 месяца назад

      I don have a video on that yet, we power down, drain coolant, flush with distilled water, refill with York 013-04129-000 coolant (light blue color) . Recheck levels after restart

  • @thesilentonevictor
    @thesilentonevictor 8 месяцев назад +4

    That sound at the start had wondering what the issue i was saying must be surging lol

    • @subcoolHVAC
      @subcoolHVAC  8 месяцев назад +1

      Yep, with high pitch tap from check valve.

  • @Ericbakereb1
    @Ericbakereb1 8 месяцев назад +1

    Thought you were in a factory or so.ething at first lol.

    • @subcoolHVAC
      @subcoolHVAC  8 месяцев назад +1

      🤣 yep, it was definitely an unexpected kind of surge

  • @dragonstorm9968
    @dragonstorm9968 8 месяцев назад +1

    Sounds like that there is the EMERGENCY STOP BUTTON FOR to immediately stop a machine.

    • @subcoolHVAC
      @subcoolHVAC  8 месяцев назад +2

      That’s the last button to push