24 - Field Zone Modules - Introduction to Fire Alarms

Поделиться
HTML-код
  • Опубликовано: 2 фев 2025

Комментарии • 26

  • @JoeKlochan
    @JoeKlochan  11 лет назад +5

    If you're asking what I think you're asking, the answer is yes. The addressable FZM has 1 address only. Every conventional device that's connected to it would show up at the panel as the same address. So if you have smokes, pulls, and heats all tied to that circuit, you'd have to label that modules something like "3rd floor detection", just as you would a zone on a conventional panel.

    • @pipegarilao2927
      @pipegarilao2927 4 года назад

      How many wires install from smoke detector to module

  • @calebmorand4604
    @calebmorand4604 2 года назад

    Great explanation! Does this kind of module supervise the 24 volt resettable power? Or is a power supervision relay needed? If the module loses the resettable power, would it send a trouble signal to the SLC? Thanks!

    • @JoeKlochan
      @JoeKlochan  2 года назад +1

      Depends on the panel. Notifier panels supervise the power if the module is programmed correctly. Gamewell FCI modules do not. Other manufacturers I'm not sure off-hand

  • @jms7620
    @jms7620 21 день назад

    I'm confused we install intelligent panels for schools and all we need is slc to each device no power we only use mini mods for co detectors I only have a year as an apprentice so I don't know a bunch... is it the panels or type of heats/smokes we are using perhaps

  • @joshualuna6082
    @joshualuna6082 2 года назад

    @Joe Klochan how many two wire smoke detectors can connect per ZMF-1 module?

  • @Arnoldjoakhim30
    @Arnoldjoakhim30 Год назад

    Can you connect addressable smoke to a conventional fire lite Ms 4 ?

  • @yeoj8358
    @yeoj8358 Год назад

    Hi Sir, what is the value I can put for end of line resistor in a 24 volts circuit? Thank you Sir

  • @magdifahmi6229
    @magdifahmi6229 Год назад

    Great work ,Can youdo a video on how to read Fire alarm drawings for installers

  • @Vipul-57
    @Vipul-57 4 года назад

    Hi Joe how r you doing...
    How to commissioned Honeywell fire panel

  • @rao54
    @rao54 Год назад

    Hi sir how many smoke detector to connect in one notifier

  • @Frankspliff2
    @Frankspliff2 4 года назад

    What is the simplex model number of module that would work with 4008?

    • @jepps1021
      @jepps1021 3 года назад

      I believe it's called a ZAM module.

  • @mava5634
    @mava5634 5 лет назад

    the manufacture of these modules sets the battery feeding terminalsT4 and T5, here battery is feeding T11 and T 10, I am confused

    • @JoeKlochan
      @JoeKlochan  5 лет назад

      Mava, no battery should be connected to these. Make sure you're comparing the same type of module. I think some terminals chanced when the modules switch from the V type to the H type, but always following the install sheet.

    • @mava5634
      @mava5634 5 лет назад

      @@JoeKlochan thanks a lot

  • @kamaldas2430
    @kamaldas2430 4 года назад

    Can you please share a video on Fault isolator module?

  • @justinallen9014
    @justinallen9014 4 года назад

    How do you test to tell if a SK Monitor module went bad

    • @JoeKlochan
      @JoeKlochan  4 года назад

      Depends on the problem you think it's causing. If the panel is not communicating with the module, you can connect it directly to the panel. If it's showing an activation, you can temporarily resistor it out. There are even more basic steps, but a lot of the troubleshooting is basic common sense.

  • @mitchgorman6876
    @mitchgorman6876 11 лет назад

    Could you do a segment on fault isolation modules?

  • @001marselle
    @001marselle 8 лет назад

    I am following these videos , but what i see you jump to explain part from brand , please correct me if i am wrong .

  • @anirudhmanoj9639
    @anirudhmanoj9639 5 лет назад

    What is Fire alarm zone can explain it

  • @muhammadnaeem5480
    @muhammadnaeem5480 7 лет назад +1

    what is slc

    • @futurealarms121
      @futurealarms121 7 лет назад +2

      It stands for Signaling Line Circuit. It's the addressable equivalent of a zone on a conventional panel. Except that it's far more powerful because it can connect to multiple devices, each of which can have its own individual device name and programming. Other companies, such as EST, call them loops. Simplex, Notifier, Fire-Lite, and the rest call them SLCs though. Exact same thing though.

    • @carlosyelamo7594
      @carlosyelamo7594 5 лет назад +1

      signal loop control