Main Circuit Breaker Computation And Service Entrance Conductors

Поделиться
HTML-код
  • Опубликовано: 16 окт 2024
  • Sa video na ito ituturo ko sa inyo kung paano magcompute or paano ang computation para sa main breaker at paano malalaman ang size na gagamitin para service entrace conductors
    if you enjoy watching this video don't forget to subscribe, like and hit notification bell thank you!
    Also visit my FB pages and group:
    JB Handyman Services
    ✓If you’re looking for the right person to fix the problem your facing in your home you can find it here, License Electrical Practitioner is available here, visit us
    Jun Aux TV
    ✓all about Electrical installation and Electrical devices reviews and safety awareness on Electrical
    JB Online Shop
    ✓you can buy product such as Electrical devices mostly on industrial devices
    www.facebook.c...
    Electrician For Hire
    ✓group of Electrician looking for a job and giving and taking ideas in one another
    Thanks for Watching hope you enjoy. God bless

Комментарии • 374

  • @engrjunogarte9844
    @engrjunogarte9844 5 лет назад +31

    Ganito ang pag sizing ng mga aircon.
    Single phase 1.5Hp ,230v ACU is an HVAC category equipment with compressor and hermetically sealed. May FLC itong 10A ayon sa PEC 4.30.14.2 (2017 revision) Ang branch conductor size nito ay 125% x 10A=12.5A . Base sa PEC 3.10.2.6B(16)/75°C you can use 2.0mm2 TW or Thhn. Subalit ito ay motor at may kaakibat na may in rush current at ang 2.0mm2 ay pang ilaw lamang kayat susundin mo ang next higher size na 3.5mm2. Ang OCPD nito ay gumagamit ng (175%-225% derating factor) ayon sa PEC 4.40.3.2(a).Kayat ang ocpd ng 1.5hp acu ay 2.25%xFLC (10A) =22.5A. Ang tamang sizes ng 1.5hp acu ay 3.5mm2@20a cb.
    Rule of thumb sa pag calculate at size ng ocpd value. Ayon sa code hindi ka allowed na tumaas sa 22.5A na calculated value mo. Sa halip sa next lower standard ka na 20A cb. O kaya puedi kang mag pagawa ng customized na 22.5A cb instead.
    Kung nais mong gamitin ang 175% x 10A =17.5 A ang OCPD mo ayon sa code ng PEC 4.40.3.2(a) ay 15A kung hindi ito nag nuissance tripping ang breaker mo palagi at nagiinit ang wire size sa 2.0mm2@15A cb.
    A design engineer will have his best discretion to use 20A @3.5mm2 TTHHN instead of 15A@2.0mm2 THHN for 1.5hp ACU unit for safety purpose.

    • @junauxtv
      @junauxtv  5 лет назад

      sir gawan ko to ng video sir ah shoutout to you sir...tnx..

    • @junauxtv
      @junauxtv  5 лет назад +2

      sa derating factor sir kelan ako pwd gumamit ng 1.75 at 2.25? may pinagbabasehan ba to sir?

    • @allanazotesjr5972
      @allanazotesjr5972 5 лет назад

      Nice explanation Engnr

    • @josecastillo565
      @josecastillo565 5 лет назад +1

      It is a clearly explanation engineer

    • @junauxtv
      @junauxtv  5 лет назад +1

      Tnx to engr jun ogarte....minsan need natin ng openion ng iba hindi Puro PEC lang...tnx

  • @joeymontero2730
    @joeymontero2730 5 лет назад +3

    I salute u bos.. electrician dn aq. .. marami tayung natutunan sa chanel mo.. keep up the good work...more power..

  • @michaelmalinao1303
    @michaelmalinao1303 2 года назад

    Salamat sa pag share ng kaAlaman godbless poh napakalaking bagay sa tulad qng gusto ko tlagang matoto abot electrical field

  • @marvinjimenez3738
    @marvinjimenez3738 5 лет назад +1

    .Salamat sa video mo sir may natutunan na naman ako pano magcompute ng main cb👍

    • @junauxtv
      @junauxtv  5 лет назад +1

      Welcome sir at Salamat din po

  • @romQat65
    @romQat65 5 лет назад +2

    slmt sir s mga info... mlking tulong s mga electrician n ngccmula p lng.... dagdag ko lng SAFETY FACTOR ung twag s 80% allowable for use

    • @junauxtv
      @junauxtv  5 лет назад +1

      Yes sir... sorry hindi ko na nabanggit sa video.. salamat sir.....

    • @nestorjrcalinog8721
      @nestorjrcalinog8721 4 года назад

      @@junauxtv sir verification lng..sa topic bout Total load computation, ginamit mo sa ACU 10A rating ampacity multiply by 230v =2300va.
      Summimg up 3000+1218+2300
      =6518va ni label mo ng Total net computed load. Sa computation mo nmn nang Main circuit breaker and service entrance conductor same sa part ng ACU ginamit mo ang 250% full load current ng single phase motor. TANONG?ano ang connection sa pag compute ng net computed load 6518va kung Hindi nsma sa computation ng Main circuit breaker at service entrance conductor saan napunta un 6518va?Note pde n pla mag compute ng Main breaker ampacity at conductor size ng HINDI mag compute nang Total Net computed load.
      Pls check salamat!

  • @Jerome-ot4eg
    @Jerome-ot4eg 4 года назад +1

    hello po kuys! I'm an Architecture Student po, and I find your videos so helpful! sana more videos to release pa po!

  • @jelmarcastrudes555
    @jelmarcastrudes555 4 года назад +1

    salamat sa video mo sir laking tulong to sa aming mga electrician babago palang,,,

    • @junauxtv
      @junauxtv  4 года назад

      Salamat din po sir...

  • @HouseDr
    @HouseDr 5 лет назад

    Nice po sir ok po lagi video nyo lagi q po watch... Dmi nyo po ksi knowledge... Salute you sir pa advice nman po kun anu comment nyo s video q para ma improve maraming salamat po and godbless

    • @aizacancino8750
      @aizacancino8750 4 года назад

      Sir anu pu b dapat gamitin n size ng wire mula s meralco meter papunta ng main breaker.ang distanciya ay 100mtr mula metro hanggang bahay.

  • @berniecana8830
    @berniecana8830 5 лет назад +1

    salamat sa pag share mo bro may natutunan ako mabuhay ka god bless,,,,,,

    • @junauxtv
      @junauxtv  5 лет назад

      Salamat din po sir

  • @ningdeloy6342
    @ningdeloy6342 5 лет назад +1

    subscribed ako sayo sir ...nice idea mga video mo humble always ka god bless sir

    • @junauxtv
      @junauxtv  5 лет назад

      Laking tulong po yan sir.... maraming salamat po sir

  • @datupobrejakeminiicemaker1435
    @datupobrejakeminiicemaker1435 5 лет назад +2

    Bos salamat sa mga upload mo dami akng natutunan shoutout dto sa davao city

    • @junauxtv
      @junauxtv  5 лет назад

      Salamat din po sir....

  • @johannaleiosita4725
    @johannaleiosita4725 5 лет назад

    Nice sir....galing...salamat sa info..shut out sa klasmate ko sa EIM..davao.

  • @MilVien
    @MilVien 3 года назад

    Nakakautay ako sa turo boss. Salamat ulit

  • @elmapiedra3964
    @elmapiedra3964 4 года назад +1

    Idol salamat sa mga tinutoro mo, marami kami natutunan sana kung meron kman groupchat pasali nman.

    • @junauxtv
      @junauxtv  4 года назад

      Fbpage lang mam Jun Aux TV din po name

  • @samsodenmelicano5187
    @samsodenmelicano5187 5 лет назад +1

    Congrats sir Jun Aux TV, Good jub. po, at salamat sa video mo..

    • @junauxtv
      @junauxtv  5 лет назад

      Salamat din po sir.....

  • @HouseDr
    @HouseDr 5 лет назад

    Nice tutorial po ulit boss

  • @cindypip100
    @cindypip100 3 года назад

    Hello boss..merry Christmas syo. Isa ako sa mga subscribers mo. Ask ko lang boss kung pwede ka gumana ng video paano mag wiring sa outlet..ilaw..at circuit breaker kung Ang Libya ng kuryente gaya sa aming at line to neutral..mdyo nalilito ako boss sa line to line at line to neutral. Gusto ko sana line to neutral kung paano Ang wiring..salamat at mabuhay ka boss..abangan ko yan video mo.

  • @johnpaulotaopa5207
    @johnpaulotaopa5207 5 лет назад +1

    sana sir pwede po ba na I post niyo po sa fb yung mga example na computation at yung iba mga diagram din na ginagawa niyo po godbless and more power marami po ako natutunan sa channel niyo sir

    • @junauxtv
      @junauxtv  5 лет назад

      May balak po ako sir for that...magagawa ko lng yan if we reach 30k subs...

  • @christophermata563
    @christophermata563 5 лет назад

    ayus sir may bago nanaman natutunan..

  • @dentoyvlogz6259
    @dentoyvlogz6259 5 лет назад

    Salamat s impormasyon sir...may natutunan n nmn aq....pashot out nxt blog sir..dto po aq K.S.A

  • @emmanthenomad
    @emmanthenomad 4 года назад

    Good job bro , perfect explanation,God Bless You .

  • @meganotutor6135
    @meganotutor6135 5 лет назад +1

    ok pre nadagdagan na naman ang natutunan ko hehehe baka kukuha na ako ng NCll nito kaso problema ko kung bibigyan ako ng certipacate of employment ng amo

    • @junauxtv
      @junauxtv  5 лет назад +1

      Try lng sir mas maganda kung may pinanghahawakan kang katibayan na Electrician ka

  • @reynaldaclan7952
    @reynaldaclan7952 5 лет назад +1

    Salamat sa Idea Sir 👍👍👍

    • @junauxtv
      @junauxtv  5 лет назад

      Salamat din po sir

    • @reynaldaclan7952
      @reynaldaclan7952 5 лет назад +1

      Jun Aux TV Sir naaalala ka pa daw ni PROF. LAMANILAO Sir .. nangangamusta siya sayo .. sabi nya ipagpatuloy mu lang daw yung channel mu Sir .. Actually Sir, sabi niya sakin na mg.download dw ako ng videos mu pra makita ka daw niya .. more power Sir Jun Aux .. God bless po, paki shout out hehhe😃😎😎😂👍

    • @junauxtv
      @junauxtv  5 лет назад

      Na shout out na po kita sir...pati si sir lamanilao

  • @christopherbatonghinog2028
    @christopherbatonghinog2028 5 лет назад

    Salamat sa pag share ng knowledge mo...ito gusto kung matotonan ..pero suggest ko lang po bro..na sana may auto focus camera mo para malinaw...pero thumbs up..salamat

    • @junauxtv
      @junauxtv  5 лет назад +1

      Tnx sir...noted po yan sir...tnx

  • @yiealcala
    @yiealcala 4 года назад +1

    Salamat sa learning Sir.

    • @junauxtv
      @junauxtv  4 года назад

      Maraming salamat din po sir

  • @j-mantrip2110
    @j-mantrip2110 5 лет назад

    Gusto ko lang mag thank you sayo sir nang dahil sayo kahit wala ako ni kunting knowledge sa electrical pero mahilig ako mag tap tap sa bahay ko hehehe pero ng dahil sa video mo sir nagkakarun ako ng idea slmat po bossing mlking tulong yung video mo sa tulad ko na zero knowledge sa electrical. Mabuhay kayo

    • @junauxtv
      @junauxtv  5 лет назад

      Maraming salamat po sir.....abang abang ka lng ng bagong upload sir marami pa kayong dapat matutunan

  • @jaysoncid8151
    @jaysoncid8151 3 года назад

    Boss pa topic nmn yung computation ng multiple meter tnx.. More powr

  • @engrjunogarte9844
    @engrjunogarte9844 5 лет назад +10

    Sa presentation when you are sizing your wires and breaker always use PEC 3.10.2.6(b)(16)
    Since ang total computed load current mo ay 43A. Tumama ka naman dahil ang rated current sa table ay 55A at 14mm2.
    Rule of thumb ng pag gamit ng PEC 3.10.2.6(b)16 ay
    1. Kung 100A or less ang rated current mo default ka sa 60°C column.
    2. Kung 100A and above default ka sa 75°C column. Ang mga motor dito ay may exception. Kung ang motor mo ay less than 100A at hindi type BDC at may naka saad sa terminal temp na 60°C default ka sa 60°C column otherwise 75°C ang mga motor mo.
    3. Ang 90°C ay exclusively use for derating purposes only.
    Share ko lang sayo yan

    • @troynezybanez9969
      @troynezybanez9969 5 лет назад +1

      Sir, may matanung lng po ako. Bakit po sa mga industrial company sir ang electrical distribution panel or electrical power panel po nila, ang nka design nila na main breaker sa panel ay 80A at may more or less 15 branches breaker na may tig 20A na rating kada isa, ang tanung ko lng po sir ay hindi ba masyadung mababa yung 80A na main para sa 15 branches na may tig 20A na rating? gusto ko lng po maliwanagan panu po nila na compute yun o design na po talaga nila yan o may mga standard ba???

    • @junauxtv
      @junauxtv  5 лет назад

      Ang main kasi sir hindi nakadepende sa daming branches kundi sa total load po sir...

    • @troynezybanez9969
      @troynezybanez9969 5 лет назад

      @@junauxtv ah ganun po ba sir, salamat po

    • @engrjunogarte9844
      @engrjunogarte9844 5 лет назад +2

      Sir ang mga industrial company ay may malalaking 3 phase power load at mga single phase load Ang 80A mo sa main breaker ay mallit po yan para sa industrial power load. Mukhang sa commercial load po ata ang input data nyo. May mga standard equivalent ang sizing ng breaker at wires base sa PEC.Thanks po.

  • @raymartsomintac7284
    @raymartsomintac7284 5 лет назад

    Sir slamat sa mga dagdag kaalaman,tanung ko lng po sir pno po pg halimbawang 100amp ung nlagay na main CB my masamang epekto po ba un sakali?KC kadalasan ganon po ung mga nkikita ko dto sa province

  • @alyssacanovas4407
    @alyssacanovas4407 3 года назад

    Thank you po!

  • @arieldizon6638
    @arieldizon6638 5 лет назад +1

    Thank u boss watching her in palo leyte..

    • @junauxtv
      @junauxtv  5 лет назад

      Daghang salamat sir....

  • @charrydecano8701
    @charrydecano8701 5 лет назад +2

    hi sir jun..Goodmorning nice video sir👍

    • @junauxtv
      @junauxtv  5 лет назад +1

      Salamat din po...

  • @strongpride73
    @strongpride73 Год назад

    Thanks for this informative things. By the way, could you let me know of any regulation of the percentage of full load current? Any specific codes/s standards? IEC or NEC?

  • @kingkwinpelsontv
    @kingkwinpelsontv 5 лет назад +1

    I'll used this for my instruction

  • @jugelbam8433
    @jugelbam8433 4 года назад +2

    Sir what if dalawa ACU ko na 1.5hp
    So dalawang 2,300va ba yung isolve sa 250%?
    Meaning 4,600vs x 250%? Ganan po ba?

  • @obetliquit5204
    @obetliquit5204 4 года назад +2

    Pwd po bang magtanung? Anu po ibig sabihin nung single phase motor @ inverse time breaker?? At tsaka bkit po yun yung ginamit nyu?? ( For project purposes hehe ) P.S. thank you po pala sa vid nato hehe

    • @junauxtv
      @junauxtv  4 года назад

      Single-phase Motors
      Single phase motors are the electrical devices with output power around 1HP (Horse power). These are mostly single phase induction motors. It plays a vital role in domestic applications. Most of these domestic applications are fans, electric toys, blowers, centrifugal pumps, washing machines and so on.
      When supplying a single phase voltage to the stator of these machines, the stator will produce flux. This flux rotates and cuts the rotor conductors. Due to this an EMF is induced. As the rotor circuit is closed the current flows through the rotor conductor. This rotor current will cause rotor flux. These rotor fluxes also rotate in opposite direction as the stator flux. The interaction of these two fluxes leads to a resultant torque which rotates the motor. But, the two fluxes (stator and rotor fluxes) are equal in magnitude but opposite in direction. Due to this the resultant torque cancels with each other. Therefore, the motor will not rotate. It is the reason the single phase motors do not self-start.
      To start these single phase motors auxiliary winding or starting winding is used additionally with normal running field winding. The auxiliary winding is placed with a phase shift of 90° to the running winding and physically connected in parallel to the running winding. There are various methods to start these machines. Based on the methods these are classified as split phase motors, shaded pole motors, and reluctance motors. The split phase motors are again classified as capacitor start motors, capacitor run motors, and capacitor start capacitor run motors.

    • @junauxtv
      @junauxtv  4 года назад

      Sir mas maganda po search nyo nlng po sa google para complete don lang din kasi ako kukuha..hehe

  • @edralinbacalso3255
    @edralinbacalso3255 4 года назад

    Sir, maraming salamat sa knowledge nyo po, tanong kolang sir kailan po ba gagamit ng 8 branches pataas?

  • @jimreylid-ayan8462
    @jimreylid-ayan8462 2 года назад

    Sir... good evening..galing po ba sa PEC ung table na ginamit nyo? kung saan makikita po ung load allowed, ung tapat nya Kung ilang breaker capacity, awg, mm^2 etc.

  • @danielnicolasamar2860
    @danielnicolasamar2860 4 года назад

    Hi sir Jun, good day. First of all , I’m just learning PEC and Hindi po ako REE or electrician, ask ok po Saan galing Ang table Ng sizing Ng breaker capacity at load allowed, etc. Gusto ok Po kasi I value engineering Yung electrical wiring sa pinapagawa king Bahay. Salamat

  • @monmon-sx5cj
    @monmon-sx5cj 4 года назад

    sir. for confirmation lng hehe. hnd na kailangan magbase sa mga branch circuit breaker?? diritso na sa mga loads kagaya ng ginawa mo?mm

  • @soroanjonnel9484
    @soroanjonnel9484 7 месяцев назад

    Good day po master,. tanong kulang pa Kong pede pobang gumamit Ng 30amp,sa dalawang 1.5hp,.sana po ma pasin

  • @crisremata4708
    @crisremata4708 2 года назад

    Ask ko lang po sir, if may branches ako na (15A) sa Ilaw, (20A) sa CO, 3 (20A) sa acu at ref, nasa 1hp lang naman ang aircon sir, nacompute ko na base din sa video mo about ACU's, at lastly water pump na (20A).
    So total is 95Ax80%=76A (safety factor)
    So ang gagamitin ko na Main is 80A, tama sir diba?

  • @ardelynversoza6651
    @ardelynversoza6651 4 года назад

    Ser jun c ardelyn ako. Gusto ko malaman kng pwede kunan ng amperahe ung panel board. Para malaman ko kng ilan ang load tinatakbo nya. Pwede ba sa main breaker ako kumuha para malaman ung load ng lahat ng applaiance

  • @gddraftsman5617
    @gddraftsman5617 3 года назад

    bago ang alhat i link mo naman sa description yung naunang video heheh

  • @raymondbarba2719
    @raymondbarba2719 3 года назад

    Master good pm po, tanong kulang master, may load ako sa bahay na 9746 watts ilang amperes ba dapat na main breaker ko at pwedi bayan sa residential building....

  • @HollyMolly8982
    @HollyMolly8982 Год назад

    sir ask ko lang what if lima aircon .. yung total VA ng limang acu ba ang imumultiply sa 250%?? ty

  • @alvinjakecator2327
    @alvinjakecator2327 2 года назад

    gandang gabi po
    ask ko lng po sana
    pwede po kaya ung main breaker ko sa panel board(10 branches) is 100A tas ung cb ko po sa service entrance is 100A din po lang po tas #8 po na wire?
    residentian lng po.
    tia po😌

  • @alfredodabatos408
    @alfredodabatos408 5 лет назад

    Good morning. Sir jun.hindi ko naintindihan ang v.a ano nayan saan ba mabahagi at sino yan saan makita sa divice .from cebu .electrecal maintenace po ako..ngayon..thanks.sir jun aux.love yuo.

    • @junauxtv
      @junauxtv  5 лет назад

      Voltage x current = Volt-ampere or VA

    • @junauxtv
      @junauxtv  5 лет назад

      Daghang salamat sir... love you too..

  • @jhomariegabionza1926
    @jhomariegabionza1926 4 года назад

    Shout out po😊

  • @comidadenoypi460
    @comidadenoypi460 4 года назад

    Sir pakiliwanagan po ako sa bakit po may inverse time yung computation mo sa ACU breaker..mcb is up to 63 amp na wala pong inverse time..pede ba yung 175 to 225 percent

  • @inoidfluke2316
    @inoidfluke2316 3 года назад

    Bro paano pag multiple panel board.. I mean halimbawa commercial buildimg with 4 units and different panel board tapos isa lang ang ang pagkukunan na entrada pano ang computation nun? Total ko lang ba lahat ng load ng panel boards ko?

  • @sannylozada2114
    @sannylozada2114 5 лет назад +1

    Sir Good morning. Advice lang nakabili q ng breakers main switch 100 ampere ang circuit breaker ay 30 ampere tapos nakabili din q ng wire NH ang size 12 and 14 pwede b s aircon ang size 12 at iba p.ang size 14 s ilaw gamitin.thanks.

  • @jarissinking4191
    @jarissinking4191 3 года назад

    Hello po sir si Louis po ito ng Basilan, ilang ampere po ng main breaker ang kailangan ng bahay ko na may 18 bulbs 6 con. Outlets, 2 aircons, 1 washing machine at 1 ref

  • @johnbautista7819
    @johnbautista7819 4 года назад

    Yung 14 mm wire po ba ay for service entrance na po ba yun sa may papuntang electric meter?

  • @zaldyroxas2062
    @zaldyroxas2062 3 года назад

    Sir pano mag compute halimbawa..my 10 unit or tag 60 amp.per unit ang main..ilang size n wire sa service entrance at main circuit breaker cut off..ilang amp.salamat s reply.

  • @lulu3954
    @lulu3954 5 лет назад

    Pag sa condo po ba diba may breaker na sa unit. Tapos san po takbo nun? Breaker na per floor or main na ng building?

  • @ricardomecate9210
    @ricardomecate9210 3 года назад

    Sir ito ang tanong ko pwedeba ang#8awg sa100ampere na main circuit breaker,dahil ang aming entrance wire galing sa poste ay #8awg

  • @jesusmesa2673
    @jesusmesa2673 3 года назад

    Pwede ba mka-hingi ng table ng wire sizes convertion ? AWG -mm2...

  • @margamarcos8986
    @margamarcos8986 5 лет назад +1

    Sir ask ko LNG halimbawa may motor ako 220 v 2,hp fla 13.5 paano ang computation para malaman ang amp rating ng magnetic contactor at olp na gagamitin sir at paano ang pag adjust sa setting ng olp para sa inrush current ng motor at ilang percent ho ba ang itinataas sir tnx sa reply mo

    • @junauxtv
      @junauxtv  5 лет назад

      Multiply mo sa 125% sir..

  • @micahabrahammontemayor2226
    @micahabrahammontemayor2226 4 года назад +1

    Sir..paano po naging 2300VA yung aircon na 1.5hp..?thanks

  • @lolotv2867
    @lolotv2867 3 года назад

    Sir kung wye connected load ang supply,paano ang computation? Lalo Kung meron ang halong 3phase motor na load?

  • @marjunborabo4702
    @marjunborabo4702 4 года назад +1

    Bagong tuklas ko sa vlog mo ano Po ung fb page or fb account mo tnx

    • @junauxtv
      @junauxtv  4 года назад

      Nasa description below sir ang link..tnx po sir

  • @roberttatualla5930
    @roberttatualla5930 3 года назад

    sir gusto ko po kabitan ng generator ang nabili ng tiyahin kong bahay sa cavite e meron siyang 4 1hp na aircon at 1 3 tonner,ilang KVA po kaya or papaano ang computation,salamat po

  • @norieltamayo9636
    @norieltamayo9636 5 лет назад +1

    Dito sa aming lugar residential area. Ang mga electrical meters nasa labas na ng bahay may sariling poste na nakakabit ang mga metro na mayroon circuit breaker na 30 Amperes lang bawat metro. Bale wala rin kung tataasan ko Main Breaker ko sa bahay kc 30A lang nkalagay sa metro

    • @junauxtv
      @junauxtv  5 лет назад

      Tama po sir...if higher po ang load you should notify power provider na need nyo po mas mataas na cb rating

  • @marjunborabo4702
    @marjunborabo4702 4 года назад

    Sige subscribe na kita

  • @blackycute123
    @blackycute123 5 лет назад

    Gud day sir .. Nagtataka lang po ako kung bakit 250% ang ginamit, kasi alam ko po ginagamit lang yun kapag hahanapin ang breaker para lang sa ACU. 25% ang alam ko po multiplier nya kasi po total connected load + (25% of largest motor).. D ko lang din po sure baguhan lang din ako sa electrical :D opinion ko lang po to ;D

    • @junauxtv
      @junauxtv  5 лет назад

      Multimotor po ata yan sir...

    • @charlesaugust9219
      @charlesaugust9219 5 лет назад

      250% is used as a multiplier for the biggest motor load. Sa computation kasi ng main, kinakailangan sufficient ang allowance mo para i sustain nya ang kuryente o boltahe na kinakailangan, especially kapag sabay sabay na ginamit ang mga appliances at iba pang kagamitan.

    • @charlesaugust9219
      @charlesaugust9219 5 лет назад

      25% is used for the main feeder.

    • @marianitoerispe4347
      @marianitoerispe4347 5 лет назад

      Pagkaalam ko po tama po yung 250 percent para po yan sa gagamitin main breaker ng motor 125 percent nmn para sa wire n gagamitin. 250×(FLC) , 125×(FLA).

  • @Lokaismaet
    @Lokaismaet 4 года назад +1

    Sir ilang amp ba ilagay sa laudry na breaker nya? Yan small appliance load ba mag kasama naba jan ang ref,rice cooker,tv, radio, electric range cooker?tnx sir

    • @junauxtv
      @junauxtv  4 года назад

      sa small appliance sir..20 amps...
      ranges sir need may separate cb depende sa range mo sir..

    • @Lokaismaet
      @Lokaismaet 4 года назад

      Ok sir salamat

  • @nestorgulle4443
    @nestorgulle4443 3 года назад

    Sir magandang umaga po tanong kolang po ilang ampers at anong size ng wire para s electric oven n electrolux 60CM, 4HP, 54L. main breaker kopo ay 60ampers maraming salamat po.

  • @jovenmalate4215
    @jovenmalate4215 4 года назад

    Alam na nmin yan

    • @junauxtv
      @junauxtv  4 года назад

      For those who don't know yet

  • @kittsantos-ocampo6432
    @kittsantos-ocampo6432 3 года назад

    Sir, what if 3 ACU gagamitin...3 ung kuwarto? so mumultiply ung 2300 VA to 250% lahat? so bali total non is 17250VA..lalabas ang main circuit breaker is 125A..tama ba?

  • @luvinaalivio2266
    @luvinaalivio2266 4 года назад +1

    Gud eve sir, baka pwedeng maturuan mo aq ng sample design ngctransformer and calculation... Tnx

    • @junauxtv
      @junauxtv  4 года назад

      Soon sir...hehe

    • @luvinaalivio2266
      @luvinaalivio2266 4 года назад +1

      @@junauxtv o kya my recomend kang training center sir, kelangan q po kc nextyr.. Tnx

    • @junauxtv
      @junauxtv  4 года назад

      @@luvinaalivio2266 negative sir wala din kasi sa tesda yan sir.... try mo sir sa PEC alam ko may topic don for transformer

    • @luvinaalivio2266
      @luvinaalivio2266 4 года назад

      @@junauxtv tnx sir

  • @emmanuelaban9397
    @emmanuelaban9397 4 года назад

    Sir need guidance lang po. From electric main to circuit breaker ko na 30amp going to branches breaker main is 60amp okay lang po ba?

  • @josephjamesverano8058
    @josephjamesverano8058 4 года назад +1

    good day po! 😊 ask ko lang po yung table 2.20.3.3 which is lighting load demand factors ang nakalagay sa pec. bakit po kasali sa demand factor yung small appliance load tsaka laundry circuit?

    • @junauxtv
      @junauxtv  4 года назад +1

      Sir check mo sa examples ng PEC don mo yan sir makikita

    • @josephjamesverano8058
      @josephjamesverano8058 4 года назад

      @@junauxtv yes po. i just checked pec at ang 2.20.3.3 is for lighting demand factors only. eh bakit nasama sa calculation yung ibang circuits for calculating feeder?

  • @jobortyadao
    @jobortyadao 5 лет назад +1

    Tanong ko lang boz, kung ilang c.o.? at lights na pwedeng pagsabayin sa 30 ampere na circuit?

    • @junauxtv
      @junauxtv  5 лет назад

      Anong wire po gagamitin mo sir?

  • @mjlesly5702
    @mjlesly5702 5 лет назад

    Astig to..

  • @hatchiretchistudio5148
    @hatchiretchistudio5148 4 года назад

    tanong ko lang po idol pwede po ba yun ' yung load service entrance sa meter na 5.5 mm dudugtungan ko ng #6 na wire papuntang main circuit breaker? Kasi yun po idol ang nkalagay sa load service entrance eh 5.5mm 🙏 ty po

  • @alcruz1996
    @alcruz1996 3 года назад

    sir anu ba dapat na ilagay sa main na breaker 5 na aircon na split type ,10 na outlet at 10 na ilaw ..salamat

  • @marxisotorio7229
    @marxisotorio7229 4 года назад

    Kaya na po ba ng 60 amp na main breaker kung dalawa ang aircon sir?dalawang 3/4 hp yung aircon sir

  • @levikeithflores367
    @levikeithflores367 5 лет назад +1

    di po ba dapat mas mataas ang ampacity ng wire natin kesa sa breaker. example is 60mm2 THHN ampacity neto eh 170 amps, dapat ang breaker neto is about 150. kasi bago pa mareach ng wire ang peak load neto at bago pa ito malusaw o masunog eh mag tritrip na ating breaker? kasi ung sa graph na binigay niyo is ung 60mm na wire ang breaker na nakalagay is 175? lusaw na ang wire mo pero di pa nag tritrip breaker mo. Ask ko lang po. Ty Ty

    • @junauxtv
      @junauxtv  5 лет назад

      May naupload na po akong tamang table for that sir...nasa Facebook page natin..

  • @carljimbayot1348
    @carljimbayot1348 4 года назад

    Idol naka line to line ba yung meralco?

  • @roderickrecimo5069
    @roderickrecimo5069 4 года назад

    boss parang may mali dun sa computation ng demand factors. di po ba ang sub total ay 6480VA. base sa table 2.20.3.3 , yung first 3,000 or less and DF ay 100%. Then yung 3,001 - 120,000 and DF ay 35%. Yung sub-total na 6480 ay nasa 3,001-120,000 na range. so di po ba ang DF na gagamitin ay 35% lang?

  • @kaliwalitv2406
    @kaliwalitv2406 5 лет назад

    Boss pwede bang gamitan ng 80amp na breaker ung main? Kc may sobra dito na 80 amp n breaker sayang kung itatapon k lng...

  • @engrjunogarte9844
    @engrjunogarte9844 5 лет назад +1

    Dito mo pala i base ang pag size up ng ocpd mo.
    PEC 2.40.1.6
    (a) Fuses and Fixed-Trip Circuit Breakers. The standard ampere ratings for fuses and inverse time circuit breakers shall be considered 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, and 6000 amperes.

    • @giemello220
      @giemello220 5 лет назад +1

      sir tnung ko lng po kung pnu computation ng main breaker?
      my 2 unit 3hp at 4 unit na 5hp aircon...? restaurant po my 3 exhaust fan.

    • @junauxtv
      @junauxtv  5 лет назад

      apply mo sir ung nasa video natin...

  • @yomarsasutil3848
    @yomarsasutil3848 5 лет назад +1

    Gud day sir.. Paano poba makoha ang volt amper cumputation basi ng load.. Slmat

    • @yomarsasutil3848
      @yomarsasutil3848 5 лет назад +1

      Sir pwde mkahingi ng amper rating chart ng gauge ng wire breaker

    • @junauxtv
      @junauxtv  5 лет назад

      Need mo itotal lahat ng load sir in VA
      VA=volt x ampre

    • @junauxtv
      @junauxtv  5 лет назад

      Fbpage sir Jun Aux TV din po nakapost na yan sir

  • @rhobelvilla4947
    @rhobelvilla4947 3 года назад

    boss jun pede ba akong gumamit ng 50amp.na main breaker kc isang aircon at apat na ilaw lang ang load at apat na outlet lang boss

  • @anthonymendoza1734
    @anthonymendoza1734 4 года назад

    Yung 0.8 is yung power factor dba sir?

  • @jelmarcastrudes555
    @jelmarcastrudes555 4 года назад +1

    hello sir tanung lang poh paano poh ba ang proper computation formula ng load para malaman yung size ng cable na gagamitin at breaker sir,, katulad po ng 35mmsquare paano poh malaman kung anung size ng breaker sir

    • @junauxtv
      @junauxtv  4 года назад

      Unang una sir.... halimbawa ilaw...alamin mo lahat kung ilan ang total wattage ng ilaw mo sir

  • @ramchelperlas-ke1fe
    @ramchelperlas-ke1fe 8 месяцев назад

    sir pano po b mkapasok sa tesda? kc maalam npo aq mag electrical at electrician npo aq ngaun for 4 years kc po gsto qpo magka nc2

  • @lynardrocero4352
    @lynardrocero4352 3 года назад +1

    Boss ano size ng wire
    4 aircon
    1 electric stove
    15 lights
    8 outlet

  • @ronaldflores8931
    @ronaldflores8931 4 года назад +1

    Sir Jun.. ask po ako ok lang ba main ko 30amp
    Tapos mag outlet ako ng 20amp
    15amp sa ilaw. Ok Lang po ba?...

    • @junauxtv
      @junauxtv  4 года назад

      Ok lang po sir...dapat angkop ang wire size sa cb rating mo sir ah...

    • @ronaldflores8931
      @ronaldflores8931 4 года назад

      @@junauxtv salamat sir Jun.. marami nakong natutunan sa iyu.. God bless po...

  • @chrismelo1395
    @chrismelo1395 3 года назад

    Applicable load sa single dwelling
    Circuit #1 dapat general lightning k muna
    Circuit #2 small appliances
    Circuit #3 laundry
    Circuit #4 electric range
    Circuit #5 aircon
    Eto yung tama para hindi k mahirapan mag explain.

  • @junevalenzuela9938
    @junevalenzuela9938 4 года назад

    Hello po sir..ask po sana ng computation at ampere rating ng circuit breaker as manual transfer switch na gagamitin sa 5kva na generator. Thank u po

  • @Vieandres
    @Vieandres 5 лет назад +1

    ok lang po ba limang 20 ampere tapos main 60a wala po ba effect yan kc lampas na mga branches sa main 60 amp.?

    • @junauxtv
      @junauxtv  5 лет назад

      Wala po sir..nagbase po tayo sa total load hindi po total ng mga amps ng cb sir...tnx po...

  • @mapagsamantala6465
    @mapagsamantala6465 5 лет назад +1

    Sir pwd mgrequest sau bk pwd ka gumawa ng video na hot wir3e neutral at ground ganito kasi ang wire ring Nila dto sa Kuwait Yong isang ilaw tatlo ang switch

    • @junauxtv
      @junauxtv  5 лет назад

      Dagdag natin yan sir

  • @TheMegatot
    @TheMegatot 4 года назад

    Paps, pano of 4 ang ACU and 3 Water heater? total VA ko is 43,180.

  • @norielangeloduran322
    @norielangeloduran322 3 года назад

    sir paano po naging volt ampere ang wats?
    ano po ang formula or right computation ?

  • @MarkjunAgape
    @MarkjunAgape 4 года назад

    Sir medyo nagugulohan lang po ako. sa 1.5HP A.C.U. po. bakit 2300VA po yung 1.5hp diba po 1HP = 746 W or 746VA
    parang yung 2,300 VA parang 3HP po ata yun?

  • @ardelynversoza6651
    @ardelynversoza6651 4 года назад

    Ser Pano mo nakuha ung 2.300 sa ac 1.5 hp.

  • @jhuncabasaljr.8871
    @jhuncabasaljr.8871 5 лет назад

    Giod job sir

  • @vochemindagnal9829
    @vochemindagnal9829 5 лет назад +1

    3480 va, yan na ba ung table computation ng lighting tska convenience outlet?o depende p rin sa measure ng bahay?

    • @junauxtv
      @junauxtv  5 лет назад

      Computed load lang yan sir hindi yan fix value of any circuit or standard value

    • @vochemindagnal9829
      @vochemindagnal9829 5 лет назад +1

      ah ok ,thanks sir.di cya katulad ng small apliances n merun 1500va.

    • @junauxtv
      @junauxtv  5 лет назад +1

      @@vochemindagnal9829 opo sir...dba po subtotal ng load is 6480-3000=3480
      Ung 300*100%=3000
      3480*35%=1218