Episode 2 - What is a ACB, Air Circuit Breaker, Trip Units, draw-out explained by a M&E engineer!

Поделиться
HTML-код
  • Опубликовано: 6 сен 2024

Комментарии • 51

  • @bikolano1982
    @bikolano1982 Месяц назад

    thanks for this video.

  • @sheriffdeen175
    @sheriffdeen175 2 месяца назад

    It is really helpful thanks

  • @Kannan_RL
    @Kannan_RL 11 месяцев назад +1

    Very informative videos

  • @ashutoshmahajan823
    @ashutoshmahajan823 5 месяцев назад

    Need Videos on Contactors and Its accessories

  • @jerrytan3588
    @jerrytan3588 3 года назад +2

    What is the useful life for the ACB? In terms of maintenance, in what interval ACB shall be maintained (monthly? Half yearly? yearly?) and what are the scopes involved?

    • @themeengineers1671
      @themeengineers1671  3 года назад

      Hi Jerry thank you for your comment. ACB's useful life tags with the Switchboard of 20 years if it is well maintained.
      In terms of maintenance, a yearly Basic end-user maintenance program and
      Standard end-user maintenance program every 2 years is required.
      As for OEM maintenance, depending on the current loading, criticality and environment it is recommended to have maintenance every 2years for bad conditions, and 5 years for better conditions.
      Hope that answers your questions!

    • @jerrytan3588
      @jerrytan3588 3 года назад

      @@themeengineers1671 Thanks for the response. Clear!

    • @gharamkhallouf7591
      @gharamkhallouf7591 Год назад

      ​@@themeengineers1671 we need more video why stoped.😢

  • @bobbyearayil
    @bobbyearayil 7 месяцев назад +1

    Excellent

  • @eheh7829
    @eheh7829 3 года назад +1

    Outstanding job

  • @edwinferguson8337
    @edwinferguson8337 2 года назад +2

    Great job.

  • @ELECTRICIANSatWORK
    @ELECTRICIANSatWORK 6 месяцев назад

    Thank you so much

  • @thurazawwisewish1843
    @thurazawwisewish1843 10 месяцев назад +1

    Thanks

  • @barunakumarpradhan4644
    @barunakumarpradhan4644 8 месяцев назад +1

    Very useful video

  • @sheriffdeen175
    @sheriffdeen175 2 месяца назад

    Thanks sir

  • @ansharafi5398
    @ansharafi5398 3 года назад +1

    good work,
    need much deep inormation

  • @andyding673
    @andyding673 Год назад +1

    Thank you,very useful

  • @techcat7318
    @techcat7318 2 года назад +1

    Whoa just discovered your.Very informative 👍🏻👍🏻

  • @steveokinevo
    @steveokinevo 3 года назад +2

    Good video friend I have question I watched engineers test acb mechanisms on regular basis, they would shut off acb and then rack it out not fully??? Then rack back in, pump and energize again. Why did they rack it out????

    • @themeengineers1671
      @themeengineers1671  3 года назад

      Hi steve, the pumping action is to charge the coil, after the coil is charged the acb is ready to close the circuit again.
      The reason we rack it out not fully i assume is to move the breaker to a test mode/ maintainence mode, where main contacts are isolated(open) and control circuits remain connected. In this position we will be able to still test the function of the breaker without closing the circuit at all(we dont want to open and close the circuit so many times during test as it cause disruptions to the loads). Therefore racking to test position ensures one time power off and give you ability to test various features of the breaker many times before racking in again for operation.
      Hope this explains

    • @steveokinevo
      @steveokinevo 3 года назад +1

      @@themeengineers1671 you sir are a legend thanks so much for the response that clears it up nicely, I always wondered why now I know. Hope to see more videos from you soon, its excellent content.

  • @MarkKalani
    @MarkKalani 3 месяца назад

    Does the Trip Unit have input from Current Transformer?

  • @thurazawwisewish1843
    @thurazawwisewish1843 10 месяцев назад +1

    Ok

  • @thurazawwisewish1843
    @thurazawwisewish1843 10 месяцев назад +1

    Great

  • @naakiemeshach7873
    @naakiemeshach7873 6 месяцев назад

    Thank you for the class, but I would like to watch episode 1.

  • @graham5649
    @graham5649 2 года назад +1

    Great video, really helpful, thanks

  • @ahmedfarid737
    @ahmedfarid737 3 года назад +1

    Very good
    I appreciate your efforts

  • @MuhammadIrfan-gs2eb
    @MuhammadIrfan-gs2eb 2 года назад +1

    Very nice thank you

  • @BariawAbera
    @BariawAbera 2 месяца назад

    It is really helpful

  • @themeengineers1671
    @themeengineers1671  3 года назад

    feel free to drop any questions here and I will answer them!

  • @alsiyabi9590
    @alsiyabi9590 3 года назад +1

    good video, thanks for the effort

  • @user-ts3yj9fn5d
    @user-ts3yj9fn5d 5 месяцев назад

    What words does AMPS stand for?

  • @jeorgenalugon5208
    @jeorgenalugon5208 2 года назад

    kindly discuss about Frame Sizes of ACB.

    • @themeengineers1671
      @themeengineers1671  2 года назад

      Hi they are usually described as AF, amp frame, it comes in 800, 1250, 1600, 2000,2500, 3200,4000,5000,6300.

  • @Laurock93
    @Laurock93 Год назад

    Nice video, thanks for the info!

  • @jongabrielmgster8648
    @jongabrielmgster8648 2 года назад +1

    If the the trip unite gets tripped, does the current stop flowing thourh the entier acb and is it onlt the trip unit that can break the current if there is somthing wrong?

    • @themeengineers1671
      @themeengineers1671  2 года назад

      The entire acb is opened once the trip unit detects a fault. A good trip unit shows the fault type for the engineer to rectify. Once fault is rectified the acb can be reset and re closed. Hope i answered your question

  • @TRQ24
    @TRQ24 2 года назад +1

    Good....

  • @niyongiraemmanuel1496
    @niyongiraemmanuel1496 Год назад

    Hello. I have sace emax. But the display is not starting on. Once Db is powered. What could be the cause ?? What should I do?

    • @themeengineers1671
      @themeengineers1671  Год назад

      Hi, do ensure that the dc supply is in. Or acb itself is powered on. Otherwise it might be a faulty trip unit.

  • @katuraysalad
    @katuraysalad Год назад +1

    Thank you for this video

  • @thurazawwisewish1843
    @thurazawwisewish1843 10 месяцев назад +1

    Thanks

  • @abdessamedghettas7167
    @abdessamedghettas7167 2 года назад +1

    Thanks