Problems kept coming with chiller

Поделиться
HTML-код
  • Опубликовано: 9 ноя 2024

Комментарии • 28

  • @HVACTIME
    @HVACTIME  Год назад

    I have produced a 6 page Technical Reference Guide. hvactime.shop/products/yk-tech-sheet

  • @HVACChillin
    @HVACChillin 2 года назад

    I have a plant with 3 YT’s. Just replaced 1 potentiometer, 2 weeks later the next chiller is showing the same alarm. I like these videos gives a better understanding of Yorks. Don’t get to really work on them much.

    • @Sprinttrackfan1
      @Sprinttrackfan1 2 года назад

      Mmm old YT’s. Dinosaurs at this point. This plant should look into York’s YZ chiller if they want a low pressure and low GWP refrigerant option.

  • @LeSpank1012
    @LeSpank1012 2 года назад +1

    great explaination, personally i work with people that are filled with memorized info. So they could never explain why and that really prohibited my learning. Wish i found this channel sooner.
    Keep up the amazing work

  • @kylemcelya5589
    @kylemcelya5589 2 года назад

    Another great video. Thank you so much for the amount of depth you go in. I am just starting my journey into chillers and need all the information you can provide.

    • @HVACTIME
      @HVACTIME  2 года назад +1

      Awesome welcome to the chiller side. If you ever want tech support or training then checkout my website.

  • @richardbartlett6932
    @richardbartlett6932 2 года назад +1

    brilliant stuff. you handle the pressure of these bad boys well 👍

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 2 года назад

    Very well thought out explanation of operations. I understand what you explained and it makes sense. That poor chiller was fighting a high load and was giving it all it had.....thought it was cool that you basically put a "governor" on it....so it wouldn't "red line" the chiller.

  • @thesilentonevictor
    @thesilentonevictor 2 года назад

    Great work hvac time

  • @sterlingarcher46
    @sterlingarcher46 2 года назад

    Great info thank you ! So is there a way for the unit to monitor itself and prevent going into overload ? otherwise everytime they go into a hot pull-down they have to call a service tech ...

  • @bennguyen3180
    @bennguyen3180 2 года назад

    Hello Master HVAC! The York chiller, between cool chiller and air chiller. I know cool chiller have water in supply or return line because water come from cooling tower but air chiller why have water in supply or return line. Where the water come from?

  • @lorenbartling7921
    @lorenbartling7921 Год назад +1

    Vane motor switch would be in the PRV Actuator sir…

  • @mpamsinc
    @mpamsinc Год назад +2

    doing a vane re-calibration has 0% to do with vane closed switch or control of vanes. Vane motor does not stop when closing because the feed back position indicates 0. it is internal limits in motor or physical stalling before internal closed switch is made. Important if sharing info that it is accurate. i don't want to be that negative guy but it is important to be correct.

  • @Countsploogula
    @Countsploogula Год назад

    You’re the man 👌🏻👌🏻

  • @bennguyen3180
    @bennguyen3180 2 года назад

    Hello Master HVAC, for air chiller has housing strainer on water supply line or not.

  • @mikebrattole
    @mikebrattole 2 года назад

    Actuator more then likely on its way out. I’d clear out the surge map shows over 13k surges Maps probably full and machine will run better. 80% for 10 minutes is more then enough for your pull down. Just my two cents.
    Next time you are working on a York pull the VM cover. Vane Motor Switch Operation (VMS)
    The auxiliary contacts are internal Normally - Open (NO) contacts on terminal 1 to 6 on the actuator terminal block. Notice that terminal 1 has a jumper wire 1A to L1. L1 is supplying 120 vac to terminal 1. When the vane motor actuator shaft is within 11° of being fully closed (CCW), the auxiliary contacts 1 to 6 close, supplying a 120 vac signal to terminal 6, which would then be routed to the respective control panel to indicate that the vane motor/pre- rotation vanes are in the closed position.

    • @jeffreyrex8232
      @jeffreyrex8232 Год назад +2

      Takes a brave man to clear a surge map out without knowing what else is going with site conditions.

  • @Kimbosdk1qc
    @Kimbosdk1qc 2 года назад

    Hi , I have a problem with chiller york YCIV0280 sometime run very well but sometime run but the temperature not low of 58°F and not show alarms the suction 50 discharge 229.

  • @jojoanthony9899
    @jojoanthony9899 2 года назад

    Whats the best books on chillers or school to be a technician?

    • @HVACTIME
      @HVACTIME  2 года назад

      I recommend starting with IOM's

  • @RREngr
    @RREngr Год назад

    hlo sir my YK series chiller solid state starter, Vane motor calibration problem when i calibrate on lower motor calibrate and moving up and down but upper side motor dont work, i have started it manually, pls suggest how to solve it

  • @karaors8970
    @karaors8970 2 года назад

    🤳🧿🛠️👍🇹🇷✋ nice work

  • @dazzykhan786
    @dazzykhan786 2 года назад

    What is the password to do calibration PRV and IGV ?