fire pumps installation details

Поделиться
HTML-код
  • Опубликовано: 25 сен 2016
  • fire pumps installation details
    visit for comphansive details..Thanks
    informations786.blogspot.com/2...

Комментарии • 176

  • @mohammedmakeen9132
    @mohammedmakeen9132 6 лет назад

    appreciate your hard work for us afreen Bhai...keep sharing knowledge..very helpful

  • @MrMute-md6gy
    @MrMute-md6gy 5 лет назад +1

    Thanks for priceless information you provided

  • @premvigneshappiya9583
    @premvigneshappiya9583 5 лет назад

    Hi, The video is very informative and good. Could you please explain on Electrical panel connection and Pressure details on various pump.. Thank you..

  • @paulsmith7639
    @paulsmith7639 5 лет назад +3

    Also the auto air vent valve is missing a top U bend to prevent contamination ingress.

  • @ramsiramsath
    @ramsiramsath 4 года назад +2

    Hi, If the pump room is designed as per NFPA 20 requirement, you should keep 10d of suction line. and some more i found.

  • @zealotleader5203
    @zealotleader5203 5 лет назад

    Hello
    What you say about it?
    I THINK if the source of supply is above the pump,the eccentric reducer must be placed with the flat side down.. you are correct in this

  • @TayyabKhalil
    @TayyabKhalil 7 лет назад

    Very informative. Thank you for taking out your time to make and upload this video.

  • @Praveen271
    @Praveen271 4 года назад

    Good one bro..!!

  • @Johnwick-dt9vx
    @Johnwick-dt9vx 4 года назад

    Are UL listed check valves necessary requirement or non UL listed check valves can be used?

  • @mohseenaphaniband4740
    @mohseenaphaniband4740 6 лет назад

    First of all thanks for uploading the vedio,The flexible bellow provided after the gate valve for electrical and diesel pump must before the pump connection ,must be same as shown for jockey pump
    The pressure sensing line at the discharge of pump not explain in the vedio , what about the strainer at the inlet of the pump .

  • @jagsingh8324
    @jagsingh8324 Год назад

    Very informative, good content

  • @food4u598
    @food4u598 5 лет назад

    which schedule standard pipe is used for this? what materials is used ? why they all in red color ?

  • @uzairmalik498
    @uzairmalik498 5 лет назад +1

    Good video....World is moving towards standardization. Last month I was working on a project in 62 story building in Karachi and observed the same fire suppression system.

  • @madhusudhanbt935
    @madhusudhanbt935 7 лет назад +1

    It's a nice info, may I know if it is a real fire electrical operated pump or DG operated pumps only supply water to sprinklers or hydrent system. On that time jockey pump stop working(because jockey pump is only to maintain pressure in the respected network)

    • @afreenali
      @afreenali  7 лет назад

      yes sure: real fire electrical operated pump and Digital fully Automatic Water Pump Control by BMS system..Thanks

    • @madhusudhanbt935
      @madhusudhanbt935 7 лет назад

      afreen ali Sorry I mean to ask Jockey pump is for only to maintain pressure not to supply water continuously while using hydrants for continuous firefighting

    • @afreenali
      @afreenali  7 лет назад +1

      Brother Jockey pump maintain pressure not to supply water continuously only in case of leakage because Pump only 25 GPM and main Pump 500 GPM . Jockey pump can not be pump in high grade pressure in the system. Thanks

    • @madhusudhanbt935
      @madhusudhanbt935 7 лет назад

      afreen ali thank you brother for ur clarification. Now I got my ans

    • @afreenali
      @afreenali  7 лет назад

      welcome

  • @hamedfaiz5992
    @hamedfaiz5992 6 лет назад

    Explain is good.. But I have one doubt how did working electrical to mechanical power ,so i ask you explain to electrical and panel board side..how automatically running ,used any sensor.?

  • @sudarsansahoo8449
    @sudarsansahoo8449 6 лет назад

    Afreen Bhai mujhe Khushi hui is bat ki aap fire safety ki jankari bataya magar ek chig adhura rahagai aap har fire motor Ka pressure kg aur agar Kisi motor lineme Pani Kam ho yaniki pressure Kam hojaye kya Karna padega

  • @rods1812
    @rods1812 7 лет назад +9

    Hi friend... the excentric reducer flat side must be on top and de reduction side on bottom.. this is to prevent the formation of air pockets on the suction pipe..

    • @afreenali
      @afreenali  7 лет назад

      Thanks for You are right

    • @afreenali
      @afreenali  7 лет назад

      ruclips.net/video/iIDspuse0Jc/видео.html

    • @afreenali
      @afreenali  7 лет назад

      ruclips.net/video/90T7pGKk1mc/видео.html

    • @haleemfp
      @haleemfp 6 лет назад

      I was about to say this.... in this case if installation, air trapped and goes to impeller. Thereby the effect of cavitation increase and will heat and damage the pump.
      What I said is as per nfpa 20.

    • @gettingintoaction1
      @gettingintoaction1 5 лет назад +1

      Flat side of Eccentric reducer should be down , when source of supply is above pump and vice versa.

  • @simpledesign5305
    @simpledesign5305 3 года назад

    Great.. Thanks for this

  • @shafiqrehman7436
    @shafiqrehman7436 5 лет назад

    Respected sir,
    have you any inspection layout OF ELECTRIC FIRE PUMP ? Reply

  • @SuperRancell
    @SuperRancell 4 года назад

    FOR HVAC PUMPING DESING
    Hi thanks a lot for you videos
    I have a question...
    For calculate the Head at the secondary circuit:
    1.- Evalute the pipings circuit from the decoupler???
    2.-How estimate the energy flow at Primary Circuit (inposted by the primary pumps) for evaluate the HEAD at the secadary circuit ???

  • @nadimakhtar711
    @nadimakhtar711 6 лет назад +2

    Useful for me.

  • @laphilong2860
    @laphilong2860 5 лет назад

    Hi Friend, Please Show me, I think the center line plant off Tee and horizontal split-case Pump shaft should not be parallel. is it right??

  • @sruthijeril8026
    @sruthijeril8026 4 года назад

    Can you make on video on
    1) fire diesel parts and it function
    2) fire pump inside parts and functio

  • @nayeemhussain8121
    @nayeemhussain8121 3 года назад +1

    Hi sir, my name is nayeem, and just want to know any design vacancy in fire protection system,
    I have 4 years of experience in fire fighting and fire alarm system...
    Thank you

  • @vinaygoel859
    @vinaygoel859 5 лет назад

    HELLO SIR
    good morning sir
    what is the minimum pressure in pipe according to chart please explain it

  • @SAFETYMGMTSTUDY
    @SAFETYMGMTSTUDY 6 лет назад

    Nice video sir

  • @ambaisi
    @ambaisi 4 года назад +2

    Is 1/2 inch pipe sufficient for the supply of diesel from the tank to pump?

    • @afreenali
      @afreenali  4 года назад +1

      Yes sure good

    • @ambaisi
      @ambaisi 4 года назад

      @@afreenali Thanks a lot.

  • @silent9566
    @silent9566 6 лет назад

    what is the black thing in the diesel pump?

  • @paulsmith7639
    @paulsmith7639 5 лет назад +1

    The suction reducer is installed incorrectly. The float of the reducer should be on the top to prevent air traps. It’s upside down!

  • @yunuspervez4702
    @yunuspervez4702 3 года назад +2

    Eccentric reducer in pump suction should have flat top.

  • @Ansari29
    @Ansari29 3 года назад

    Nice Video 👍

  • @danish2zia
    @danish2zia 6 лет назад

    Can you please share electrical termination details of diesel pump and electric pump

  • @karemasamuel1330
    @karemasamuel1330 7 лет назад +1

    very good

  • @stalinmarmatas7428
    @stalinmarmatas7428 7 лет назад +1

    With out a tamper switch for each gate valve for monitoring?

  • @kunalkamble3540
    @kunalkamble3540 2 года назад

    Sir,
    Why in Dubai indian experience is not considerared.

  • @ahammadhusen9932
    @ahammadhusen9932 6 лет назад

    Sir please upload video of cooling tower and its pipe layout with valve.

    • @afreenali
      @afreenali  6 лет назад

      shortest time in this week thats why i cannot make video in this week hope i will make soon i noted for you Thanks

  • @akilinayat9595
    @akilinayat9595 2 года назад

    Glycerol filled pressure gauges to be used with syphon arrangment.
    Manhole door is not provided for diesel tank for yearly cleaning tank.
    Level gauge is also not provided to diesel tank for diesel level checking
    Batteries terminal, plastic protection caps are not provided.

  • @saadkadu3835
    @saadkadu3835 6 лет назад

    Plz upload video on working of Deluge valve

    • @afreenali
      @afreenali  6 лет назад

      Deluge Valve is known as a system control valve in a deluge system, used for fast application of water in a spray system. Deluge valve protects areas such as power transformer installation, storage tank, conveyor protection and other industrial application etc

  • @ShoebKhan-mb9tc
    @ShoebKhan-mb9tc 6 лет назад

    Why there is no strainer before pump inlet?

  • @shaikkareem1142
    @shaikkareem1142 5 лет назад

    Hi, sir u r vdos is good but in hind tips ok u have mor vdos please give me ok and thanks

  • @khadeershaikh1418
    @khadeershaikh1418 7 лет назад +4

    please tell me pressure maintained at jockey and electric pump

    • @afreenali
      @afreenali  7 лет назад +2

      ruclips.net/video/90T7pGKk1mc/видео.html

  • @ramalingeswararaobhavaraju5813
    @ramalingeswararaobhavaraju5813 3 года назад

    Thank sir.

  • @msajjadalimsajjadali6742
    @msajjadalimsajjadali6742 6 лет назад

    good job

  • @shaikgm8084
    @shaikgm8084 5 лет назад

    sir... i want connections from diesel tank to diesel pump
    please tell me how to connect this one,how many inch pump using in this connection....please give me replay

    • @allangascon8242
      @allangascon8242 5 лет назад

      In diesel pump you can see the two black hose pipe with a tag for the supply and return connection.never to use a gate valve in the return piping line.

  • @TheNetcubus
    @TheNetcubus 7 лет назад +1

    nice work my friend , it would be nice if u provided some tech details . thank you

    • @afreenali
      @afreenali  7 лет назад +1

      thanks soon i am working in detail drawing i will upload soon Thanks☺

    • @afreenali
      @afreenali  7 лет назад

      ruclips.net/video/iIDspuse0Jc/видео.html

    • @afreenali
      @afreenali  7 лет назад

      ruclips.net/video/90T7pGKk1mc/видео.html

  • @dsmehndi5813
    @dsmehndi5813 4 года назад

    Will u plz tell me in a single fire room. How many types of pumps are needed to assemble process

  • @AliRaza-cn7qw
    @AliRaza-cn7qw 5 лет назад

    Salam
    Bhai ap ki video thyk but agr English main explain ni ho rhi to Kia zarorat ha English main smjhany ki Hindi main smjha dety achi smjh a jati

  • @beltranfloresflores2408
    @beltranfloresflores2408 4 года назад

    Mejorar la toma, la succión en desorden

  • @fahadelambilacheri6120
    @fahadelambilacheri6120 7 лет назад +1

    I AM 5 YEAR EXPERIENCE I FIRE FIGHTING ENGINEER ANY GOOD OPRTUNITY

    • @nahidhassan8500
      @nahidhassan8500 6 лет назад

      Fahad Elambilacheri add me in what's app - +8801811900607

  • @YaseenKhan-pe3qj
    @YaseenKhan-pe3qj 6 лет назад +1

    suction pipe minimum length from pump flange to fitting shall 0 times of pipe dia

  • @mohammadshojib2927
    @mohammadshojib2927 5 лет назад

    No Supervised system found for gate valve.

  • @jaipur3808
    @jaipur3808 4 года назад

    Why bypass is provided after Discharge Point in Diesel Tank ?..and that also went back to main storage tank why??

  • @balansvanas4605
    @balansvanas4605 7 лет назад +7

    ECCENTRIC REDUCTION ASSEMBLY INCORRECT

    • @GrimThe21
      @GrimThe21 5 лет назад

      NO IT IS NOT.. You have to realise that water soarce is supplied from above the suction centreline so it must be flat down... Supply from below suction centre line flat ontop.

    • @ChristianGuco
      @ChristianGuco 4 года назад

      @@GrimThe21 Yup its a positive suction, but installing eccentric like that is bad practice

    • @leonardlim4838
      @leonardlim4838 3 года назад

      @@ChristianGuco sir what is the correct position of escentric reducer?thank you

  • @allankusumah2794
    @allankusumah2794 6 лет назад

    the flexible is useless if you install far form pump and between the fix support what for is useless. and the excentric reducer installation is reverse that can use air trap is suction pipe and can cause cavitation at pump. the maintenance space for both engine and fire pump is not good. the battery position in front of fire pump control panel how come.

  • @rajibnandi7989
    @rajibnandi7989 7 лет назад +1

    can u help about fire fighting technicians. we have company here in dubai?

    • @afreenali
      @afreenali  7 лет назад

      ruclips.net/video/iIDspuse0Jc/видео.html

    • @afreenali
      @afreenali  7 лет назад

      ruclips.net/video/90T7pGKk1mc/видео.html

    • @oluyemiakande5626
      @oluyemiakande5626 7 лет назад +2

      am a good technician,
      i know fire works and domestic plumbing

    • @naveend1373
      @naveend1373 7 лет назад

      Oluyemi Akande .msg me 9963792657 Naveen India

    • @rajibnandi7989
      @rajibnandi7989 7 лет назад

      just text me by whatsapp +971566279462

  • @muhammadnouman519
    @muhammadnouman519 2 года назад

    Where is Y strainer to every pump in suction line?

  • @hlamoe935
    @hlamoe935 6 лет назад +3

    Installation shown here are not up to NFPA 20 Standard, suction distance not proper, eccentric reducer mounting wrong and OS & Y GATE Valve has no temper switch.

    • @Highlights_football_cricket
      @Highlights_football_cricket 5 лет назад

      Can you please tell me about distance and the detaila which we need to take while installing a pump

    • @allangascon8242
      @allangascon8242 5 лет назад

      Correction,tamper switch sir not temper switch

  • @forexlearnpro2264
    @forexlearnpro2264 6 лет назад +1

    Mery pyary bahi pls ap hindi ya urdu me video banao pls

    • @afreenali
      @afreenali  6 лет назад

      bhai Hindi mai b video hai ..check in my channel

    • @namiramariamhayath6858
      @namiramariamhayath6858 6 лет назад

      Boss, where's the strainer in the inlet, no identification or tagging, not told about working of different pumps, where is pressure switch? Sensing line? Only gate valve????

  • @angelosalinas4057
    @angelosalinas4057 2 года назад

    What is that?

  • @Hvacian
    @Hvacian 6 лет назад +2

    horrible voice ..not cleared ..your video is good ..but what are you saying ..?

    • @Fakhrealammm
      @Fakhrealammm 6 лет назад

      have you payed him for the video?

  • @asgarfarooque6802
    @asgarfarooque6802 Год назад

    Achcha after installing all the recommendation given by the fire brigade and achieving their certificate and just after achieving the certificate in a month or 2 fire happens in that building who is responsible

  • @br01engineeronwheels
    @br01engineeronwheels 2 года назад

    What's the responsibility of Pump technician ?

  • @jiromartinez3301
    @jiromartinez3301 5 лет назад

    Eccentric will be on the suction side and concentric will be on The discharge side

  • @LatheWar
    @LatheWar 5 лет назад +1

    Sir hindi me batao ye

  • @erwincallao9018
    @erwincallao9018 6 лет назад

    Your flexible is not listed.

  • @rajeshgummula3479
    @rajeshgummula3479 7 лет назад

    nice bro i like

  • @user-lh7iv5gs2c
    @user-lh7iv5gs2c 3 года назад

    انا فني تركيب مضخات في طرق اسهل من كده بكتير

  •  7 лет назад +1

    Chuyên g/c và Lắp đặt: INOX- CẤU KIỆN THÉP- HỢP KIM NHÔM CN:" BỒN CN- BỒN ÁP LỰC- BỒN GIA NHIỆT- BỒN CHỨA THỰC PHẨM- SILO- ỐNG CN- ỐNG VI SINH- ỐNG THỰC PHẨM- BỒN &ỐNG GAS CN- BỒN KHUẤY CN": 0974060068( Mr Hoàn)

  • @shahzadkhan-bs7vb
    @shahzadkhan-bs7vb 7 лет назад

    Please tell me in urdu or hindi.

  • @nasrinaktar7298
    @nasrinaktar7298 3 года назад

    i no this work

  • @gowthamansairam5841
    @gowthamansairam5841 2 года назад

    Where is the main raiser.......

  • @mohammedsafeer2725
    @mohammedsafeer2725 6 лет назад

    your installation of reducer at pump suction flange is wrong

    • @zealotleader5203
      @zealotleader5203 5 лет назад

      I think , if the source of water supply is above the pump , the flat side of eccentric reducer should be down.. what you say ?

  • @MDKHAN-nh5vg
    @MDKHAN-nh5vg 3 года назад

    Not installed as per NFPA

  • @advantureindia951
    @advantureindia951 4 года назад

    Khana khake boliye sir kuch sunai nahin deta...😜😜😜😀😀😀😃😀

  • @mdramjanali44
    @mdramjanali44 5 лет назад

    please translate in bangla/hindi

  • @metropcsspringvalley2102
    @metropcsspringvalley2102 5 лет назад

    The small pump isn't chipping out i think it's the check valve but it was recently changed

  • @chetan1972
    @chetan1972 7 лет назад +1

    Why sprinkler pump was not installed in the pump room?

  • @muhammaduzairmukhtar
    @muhammaduzairmukhtar 7 лет назад +1

    Dear Afreen are you work in KSA?

    • @afreenali
      @afreenali  7 лет назад

      Yes Dear

    • @muhammaduzairmukhtar
      @muhammaduzairmukhtar 7 лет назад

      AfreenAli
      In which city, Can you please give me your mobile no

    • @afreenali
      @afreenali  7 лет назад

      I m on vacation in will back after one month

  • @iqbalkhan1640
    @iqbalkhan1640 5 лет назад

    Awesome sir bt voice problem

  • @Pelusacollective
    @Pelusacollective 6 лет назад +1

    mumble mumble jumble ok ok .... let me guess he works in Dubai

  • @syedzubairali5269
    @syedzubairali5269 7 лет назад +1

    hi bro

  • @joshfreak0007
    @joshfreak0007 7 лет назад +2

    Speak louder dude

    • @afreenali
      @afreenali  7 лет назад +1

      next time i have to try my level best .Thanks

    • @afreenali
      @afreenali  7 лет назад

      ruclips.net/video/iIDspuse0Jc/видео.html

    • @afreenali
      @afreenali  7 лет назад +1

      ruclips.net/video/90T7pGKk1mc/видео.html

  • @TheCrustyFry
    @TheCrustyFry 5 лет назад +1

    You need to flip the eccentric reducer upside down.

  • @KMA835
    @KMA835 6 лет назад +1

    i can't hear you bro

  • @usmannomi4626
    @usmannomi4626 4 месяца назад

    Prv Khan ha

  • @ibrahiminayat505
    @ibrahiminayat505 4 года назад

    jab enghlis nahe aaty tu q bat karta ha

  • @leventkuzay5983
    @leventkuzay5983 5 лет назад

    min. 10XDia. straight pipe should be installed in order to avoid turblent flow in suction side of the pump.

  • @muratakay3499
    @muratakay3499 7 лет назад +1

    there are unnecesary equipments. Suction side have extra unnecessary valve and rubber compensator::::)))))

    • @afreenali
      @afreenali  7 лет назад

      this is as per NFPA installation..thanks

    • @afreenali
      @afreenali  7 лет назад

      ruclips.net/video/iIDspuse0Jc/видео.html

    • @afreenali
      @afreenali  7 лет назад

      ruclips.net/video/90T7pGKk1mc/видео.html

    • @mohammedkirmanisyed7960
      @mohammedkirmanisyed7960 6 лет назад +1

      Not at all NFPA 20 installation's followed....suction side reducer is eccentric....but installed incorrectly. ..the taper side should be bottom not on top side...and many more...

  • @Sanjayjhaofficial962
    @Sanjayjhaofficial962 5 лет назад

    G

  • @farrukhmehmood679
    @farrukhmehmood679 5 лет назад

    Sir hindi urdu main b btya krin please

  • @debashisdas3598
    @debashisdas3598 6 лет назад +1

    Improve your voice and you are only showing the parts without explaining their functions and how do they work. Don't just post any video randomly without any preparation. I don't mean to hurt you, but please check these points so as to improve yourself

    • @afreenali
      @afreenali  6 лет назад

      OK------group link chat.whatsapp.com/InDSuQrqStPED1lVYlhQ7k

  • @paradoxlearningpoint4296
    @paradoxlearningpoint4296 3 года назад

    apni english bolte somossa hole banglai bolen, kotha sposto hoini apnar

  • @jitbiswajit7336
    @jitbiswajit7336 3 года назад

    Very poor presentation.Must start from pump foundation and then proceed from there.

  • @mohammedsamimukarram2270
    @mohammedsamimukarram2270 7 лет назад

    wtf dude

    • @afreenali
      @afreenali  7 лет назад

      ruclips.net/video/iIDspuse0Jc/видео.html

    • @afreenali
      @afreenali  7 лет назад

      ruclips.net/video/90T7pGKk1mc/видео.html

  • @husseinbindhafer3840
    @husseinbindhafer3840 5 лет назад

    i cant hear you clearly what the explanation is

  • @niazafridi3651
    @niazafridi3651 9 месяцев назад

    Rubbish sound volume

  • @Antindev
    @Antindev 5 лет назад

    Speak to good voice.. Not good u r voice.
    I can't able to understand...

  • @jiromartinez3301
    @jiromartinez3301 5 лет назад

    Eccentric reducer position is wrong

  • @ivanivanov7671
    @ivanivanov7671 5 лет назад

    Totally wrong assembly. This won’t be accepted by any assurance company.

  • @food4u598
    @food4u598 5 лет назад

    which schedule standard pipe is used for this? what materials is used ? why they all in red color ?

    • @rubengajol6006
      @rubengajol6006 5 лет назад

      red color is a sign of fire protection line,,