Repairing Daikin E3 Error

Поделиться
HTML-код
  • Опубликовано: 15 ноя 2021
  • E3 Fault - High Pressure Switch Activation
    This is stating that there has been a high pressure error on this system. This could be due to fan motor or air flow problems but it could also be an issue with the actual high pressure switch.
    In this video I diagnose the High Pressure Switch to be faulty and I show you the steps I take to make that diagnosis. I also show you how I replace the actual switch and the steps involved.
    Thanks for watching.
  • ХоббиХобби

Комментарии • 25

  • @chocman77
    @chocman77 2 года назад +1

    Good job man, nice and tight in that condenser lol, keep the videos coming 👏👏

    • @maracservices
      @maracservices  2 года назад

      Thanks mate. Yeah they’re so tight aye, so much stuff to burn lol.

  • @hamdani5502
    @hamdani5502 Год назад +2

    Thanks Mr ....

  • @suldaancooling4207
    @suldaancooling4207 2 года назад

    Thanks you so much bro👍👍♥️♥️

  • @eastcoast186
    @eastcoast186 Год назад +2

    Hey mate we’re the nitrogen purge to braze and micron gauge for vacuum

  • @shamimdhaka4424
    @shamimdhaka4424 Год назад +2

    Good video very tanks

  • @rdenir
    @rdenir Год назад +1

    Thanks for pointing out just how stupid the HP switch is on the Daikin units,, I have replaced so many and every time I just shake my head in disbelief as to why they designed it that way where it requires a gas removal process..Yet the HP sensor switch can be removed in minutes by screwing off and screwing back on..

    • @maracservices
      @maracservices  Год назад +1

      It makes no sense to me either. So stupid!

    • @rdenir
      @rdenir Год назад +1

      @@maracservices what’s even more unbelievable is that this has just happened to me again today on a VRV unit!!

    • @maracservices
      @maracservices  Год назад

      @@rdenir oh wow.. I’ve come across this twice now. They definitely fail. Once again, why it is soldered in is beyond me..

  • @vladimirnik7260
    @vladimirnik7260 2 года назад +1

    Hi, soldering was without nitrogen?

  • @deepastephenson6422
    @deepastephenson6422 Год назад

    Nice and great way to understand and find the daily and solve it

  • @johnhenderson4335
    @johnhenderson4335 Год назад +1

    How did u manage to get the last of the gas in? I though the last would go in the suction when on?... I'm trying to learn ac, just incase iv missing something..

    • @johnhenderson4335
      @johnhenderson4335 Год назад +1

      This comment was for previous video mate.. Same HP video /fault

    • @maracservices
      @maracservices  Год назад +1

      So after evacuating the system, I weigh in the refrigerant. In the perfect case, there is enough pressure in the bottle to add all the gas in. If not, then I run the system and add it slowly through the suction line.
      I hope that helps mate.

  • @ushant29
    @ushant29 8 месяцев назад +1

    Hi Mitch,
    DAIKIN AIR WATER HIGH TEMPERATURE 16K installed in 2019
    I have an error code that remains displayed:
    Unit 0
    E3 12
    160 L32
    006 F5E
    Do you have any information regarding this recurring error code?
    Unit 0 concerns the outer group?
    Best Regards ;)

    • @maracservices
      @maracservices  8 месяцев назад

      Sorry mate I don’t really understand what your talking about. Daikin E3 is a high pressure switch. Something is causing the system to have high head pressure OR the pressure switch is faulty.

  • @sotirigouna8195
    @sotirigouna8195 2 года назад +1

    Hey bud
    I have the same error coming up but mine stays on for about 40mins and the top fan doesn’t kick in either

    • @maracservices
      @maracservices  2 года назад

      It’s a high pressure switch so unfortunately the only way to diagnose this is to reset the system, and run it with some gauges on the unit. If the pressure is indeed getting to high then it could be caused by the top fan not running (if on cooling mode). However if it is coming up with this error when the pressures are fine then I’d put my money on the HPS being faulty.

  • @richardmalewski953
    @richardmalewski953 Год назад +1

    No Schrader core on switch? Crazy

    • @maracservices
      @maracservices  Год назад

      No Schrader. You have to reclaim all the refrigerant to change it over. Crazy is correct haha.

  • @bmiadmin5784
    @bmiadmin5784 6 месяцев назад

    The worst brand ever come across. So many faculties and problems!!!