Zone Module | Conventional Devices to Addressable Panel Communication | Complete Wiring | MI-DCZRM

Поделиться
HTML-код
  • Опубликовано: 11 сен 2024
  • Zone Module | Conventional Devices to Addressable Panel Communication | Complete Wiring | MI-DCZRM
    In this video, you can learn how to connect conventional devices to Addresable fire alarm panel.This video is important for project & service engineer who is working in fire & safety industry. This video is also useful for those person who are working in facility & operation industry.
    If you are first time watch my channel so I request you to please first visit my channel videos & if you like my videos then only subscribe to my channel & also write comments if you want such valuable information.
    --Playlist for Question & Answer
    / playlistlist=pl1hai91e...
    --Playlist for Fire Alarm System
    ruclips.net/user/pl...
    --Playlist for FM200 System
    • FM200 System
    __________________________________________________________________________
    addressable fire alarm system wiring,
    addressable fire alarm system installation,
    addressable fire alarm system installation in hindi,
    addressable fire alarm system programming,
    addressable fire alarm system in tamil,
    addressable fire alarm system tutorial,
    addressable fire alarm system vs conventional,
    addressable fire alarm system manufacturers in india,
    addressable fire alarm system advantages,
    addressable fire alarm system boq,
    bosch addressable fire alarm system,
    addressable fire alarm system communication protocol,
    addressable fire alarm system components,
    addressable fire alarm system cabling,
    conventional and addressable fire alarm system,
    conventional vs addressable fire alarm system,
    addressable fire alarm system diagram,
    addressable fire alarm system design,
    fire alarm addressable system wiring diagram,
    addressable fire alarm panel,
    addressable fire alarm system explained,
    addressable fire alarm system honeywell,
    how addressable fire alarm system works,
    honeywell addressable fire alarm system wiring diagram,
    addressable fire alarm system india,
    addressable fire alarm system installation guide,
    addressable fire alarm system loop,
    addressable fire alarm system manufacturers,
    wiring of addressable fire alarm system,
    addressable fire alarm system ppt,
    addressable fire alarm system protocol,
    addressable panel fire alarm system,
    ravel addressable fire alarm system installation,
    addressable fire alarm system specification,
    addressable fire alarm system siemens,
    semi addressable fire alarm system,
    fire alarm system addressable type,
    addressable fire alarm system working principle,
    addressable fire alarm system wiring diagram,
    addressable fire alarm system zones,
    zeta addressable fire alarm system
    fire relay module,
    fire relay module notifier,
    fire relay module connection,
    fire relay wiring,
    fire relay for access control,
    fire alarm relay for access control
    fire alarm relay wiring diagram,
    relay pumping fire engine,
    water relay fire fighting,
    fire alarm relay module,
    relay module in fire alarm system,
    water relay fire service,
    fire alarm relay module wiring,
    fire alarm module connection,
    fire alarm module wiring,
    interface module fire alarm system,
    fire alarm input output module,
    fire alarm monitor module,
    fire alarm isolator module,
    fire alarm relay module,
    control module fire alarm system,
    fire alarm control module wiring diagram,
    module fire alarm system,
    fire alarm relay module wiring,
    zone module fire alarm
    bosch addressable fire alarm system,
    addressable fire alarm system communication protocol,
    addressable fire alarm system components,
    addressable fire alarm system cabling,
    conventional and addressable fire alarm system,
    conventional vs addressable fire alarm system,
    addressable fire alarm system diagram,
    addressable fire alarm system design,
    fire alarm addressable system wiring diagram,
    addressable fire alarm panel,
    addressable fire alarm system explained,
    addressable fire alarm system honeywell,
    how addressable fire alarm system works,
    honeywell addressable fire alarm system wiring diagram,
    addressable fire alarm system india,
    addressable fire alarm system installation guide,
    addressable fire alarm system loop,
    addressable fire alarm system manufacturers,
    wiring of addressable fire alarm system,
    addressable fire alarm system ppt,
    addressable fire alarm system protocol,
    addressable panel fire alarm system,
    ravel addressable fire alarm system installation,
    addressable fire alarm system specification,
    addressable fire alarm system siemens,
    zeta addressable fire alarm system
    __________________________________________________________________________
    #zonemodule
    #Firealarmintegration
    #MI-DCZRM

Комментарии • 79

  • @Ansari29
    @Ansari29  Год назад +1

    Friends, ek chota sa correction hai, terminal number 6(-) & 7(+) for power supply hai aur terminal number 9(-) & 10(+) Conventional detector hai, sorry for inconvenience. Pls make it correct in your notes.

    • @tusharimran8117
      @tusharimran8117 Год назад

      where is sounder out put line

    • @riksonali7487
      @riksonali7487 8 месяцев назад

      sir zon module me Sath kea peralal canect hoga

  • @sajjadkhan7768
    @sajjadkhan7768 Год назад +2

    Zone modol 5 or 8 kiske liye use krega bhai or ho sake tu practical karke dikhayega bhai jaan or aap ki video bohot achi rahti h samjh me aata h.

    • @Ansari29
      @Ansari29  Год назад

      Shukriya bhai, 5 & 8 itna use nhi hota hai. As per my experience. Pls share my video in your company group.

  • @firezoneindia2077
    @firezoneindia2077 Год назад +1

    Nice Ansari ji

  • @farrukhmahmood4099
    @farrukhmahmood4099 Год назад +2

    MashAllah. Bhai jan kya bat ha.

    • @Ansari29
      @Ansari29  Год назад

      Thanks. Pls share my videos in your company group.

  • @saleemhusain2941
    @saleemhusain2941 Год назад +1

    Thank you for the such a informative video.

    • @Ansari29
      @Ansari29  Год назад

      Glad it was helpful!

  • @ubaidubaid7090
    @ubaidubaid7090 Год назад +1

    Good job very informative

    • @Ansari29
      @Ansari29  Год назад

      Glad it was helpful!

  • @jahangirtechnical1952
    @jahangirtechnical1952 5 месяцев назад +1

    Thank sir

    • @Ansari29
      @Ansari29  4 месяца назад

      Most welcome, pls share my videos in your company groups

  • @naseeryahya2034
    @naseeryahya2034 8 дней назад

    Hybrid model.
    Thanks

  • @nasirhusain6489
    @nasirhusain6489 Год назад +1

    Well-done bro

    • @Ansari29
      @Ansari29  Год назад

      Thanks, pls share my video in your company group

  • @KUMARJAIVINDER
    @KUMARJAIVINDER Год назад +1

    Very useful information

    • @Ansari29
      @Ansari29  Год назад

      Thanks a lot

    • @Ansari29
      @Ansari29  Год назад

      Pls share my video in your company group. & subscribe for more such videos

  • @aliaquib7
    @aliaquib7 Год назад

    Asalamualaikum sir it's clear how to use zone converted into addressable panel with zone module but i have one Question in conventional panel NAC how we connect with module coz zone and NAC are separate wiring na

  • @AnwarKhan-of6zy
    @AnwarKhan-of6zy Год назад +1

    I have installed new Loop Card also then also same issue and same problem Card I have installed in other panel it’s working fine

    • @Ansari29
      @Ansari29  Год назад

      It's may be connector issue at panel side

  • @irfansiddique3292
    @irfansiddique3292 Месяц назад

    zone 1 tu apne teminal 9&10 pe connect kr dia hy Zone2 ksy connect hoga or 11 & 12 terminal kis liye use hoty hain

  • @midhunlal4367
    @midhunlal4367 Год назад +1

    nice video

    • @Ansari29
      @Ansari29  Год назад

      Thanks, please share my videos in your company group

  • @rays8091
    @rays8091 Год назад +1

    Good info.. can you give any adeas in what do when add morley ias isync error problem in panel. Voltage is present but the device not work. Thanks for reply

    • @Ansari29
      @Ansari29  Год назад

      Check loop voltage & device connectivity from Fire panel to 1st detector

  • @srinishvlogs
    @srinishvlogs Год назад

    Hi sir
    Monitor module use karsakthe hai Kya conventional mcp ko,

  • @ashishindulkar5366
    @ashishindulkar5366 4 месяца назад

    Sir hmne ek building me 1 se 8 floor ka ek loop banaya hai
    Lekin ye loop aur zone me kya difference hai?

  • @kishanpatel-en2cu
    @kishanpatel-en2cu 6 месяцев назад

    Exter power supply nahi dega to chalega all ready loop cabel to aaya hai sir in aur out ka

  • @AliAhmad-iy2uc
    @AliAhmad-iy2uc Год назад +1

    Hochiki panel ke bare me bataiye

  • @manauwarhussain2721
    @manauwarhussain2721 Месяц назад

    Right sir mai bhi Lagaya hon Bankar me HZM Module

    • @Ansari29
      @Ansari29  Месяц назад

      Thanks for your comments

  • @mkstudio3241
    @mkstudio3241 8 месяцев назад

    module ko FACP se kis jangha se suppy dein btaye 24 VDC btye

  • @mdshayan7220
    @mdshayan7220 Год назад +1

    Conventional panel ko loop se nikal kar waha addressable lagana he Kiya?

  • @kanzakhurum6558
    @kanzakhurum6558 Год назад

    I want to do thesis on "fire alarm system" can you suggest me plz any problem on which I can work in my research??

  • @devkantyadav-ju2cn
    @devkantyadav-ju2cn 5 месяцев назад +1

    Sir zone madul ke sath mcp and hooter kaise connect kare

    • @Ansari29
      @Ansari29  5 месяцев назад

      Ispar m jald hi video banany wala hoo

  • @abdulrahimkhan2029
    @abdulrahimkhan2029 Год назад +1

    Addressable detector to RI concoction ma kia koi panel programming hay ?
    Morly Honeywell panel ma device level faults dekhata hay .
    Please solution

    • @Ansari29
      @Ansari29  Год назад

      No programming for RI connection, & Device level fault means detector sensing capacity reduced, need to replace the detector

  • @madhanscott8694
    @madhanscott8694 Год назад +1

    Dear sir,
    Please repeater panel connection ok but how to programming repeater panel make honeywellRS485
    I install one site but mainpanel to repeater not linking
    Only shown version only shown

    • @Ansari29
      @Ansari29  Год назад

      I will try to make video on this topic

  • @firealarmalarmsystem43
    @firealarmalarmsystem43 Год назад

    Conventional MCP ko Honeywell addressebal panel ke sath kis module se connect kre

  • @zubairhusain9524
    @zubairhusain9524 Год назад +1

    Sir interface unit orr module ma kia different hota ha ?

    • @Ansari29
      @Ansari29  Год назад

      It's called zone interface module to connect conventional to addressable system

    • @zubairhusain9524
      @zubairhusain9524 Год назад

      @@Ansari29 it's mean both are same

  • @madhanscott8694
    @madhanscott8694 Год назад +1

    Sir one doubt Ravel panel please same type how to cable routing please explain sir

    • @Ansari29
      @Ansari29  Год назад

      Your answer is in my video, pls check my video properly

    • @madhanscott8694
      @madhanscott8694 Год назад

      @@Ansari29 sir u posted Honeywell sir I ask Ravel avni panel sir please one video separate Ravel panel please sir

    • @madhanscott8694
      @madhanscott8694 Год назад +1

      @@Ansari29 same raval panel conventional to address please one separate video need I totally watch your video please

    • @Ansari29
      @Ansari29  Год назад

      Ok, so u mean Ravel conventional to Ravel addressable panel...????

    • @madhanscott8694
      @madhanscott8694 Год назад +1

      @@Ansari29 yes sir , i have installed in Ravel addressable panel in my site already customer so many long days installed conventional panel rav el
      My question is conventional panel convert to addressable so please clarify zone interface module u posted in honey well video I ask Ravel make zone interface module Ravel

  • @imranmahmood3003
    @imranmahmood3003 Год назад +1

    One module for one loop?

  • @Tourism2003
    @Tourism2003 Год назад +1

    How to connect repetal to main panel connection

  • @R.K.bharat6399
    @R.K.bharat6399 2 месяца назад

    0:32

  • @mohammadakram3434
    @mohammadakram3434 Год назад +1

    Bhai novec system pr kaam kar raha hu Ek problem solve nhi ho raha h jab main novec cylinder ka maintenance switch disable karta hu to panel par abnormal ka trouble baar baar Q aata hain

    • @Ansari29
      @Ansari29  Год назад +1

      If possible remove the cable & don't reset the panel until your work complete. Actually it's is integrated with fire panel, that's why trouble showing in panel, this is ok. You just remove the cable & reconnect ones job done.

    • @mohammadakram3434
      @mohammadakram3434 Год назад

      @@Ansari29 i will try

  • @maakram7712
    @maakram7712 Год назад +1

    How many zones we can connect with one zone module,
    One more thing , most of the brands has this zone module or not

    • @Ansari29
      @Ansari29  Год назад

      Only 1 zone. Need to check from OEM

  • @mrgladiatorss
    @mrgladiatorss Год назад +1

    could you please make subtitle for all videos

  • @AnwarKhan-of6zy
    @AnwarKhan-of6zy Год назад

    ZX Loop Panel having problem of Loop Card blinking and not detecting any devices after commissioning its show 0 device

  • @lakshman9229
    @lakshman9229 Год назад

    After fire activation, into zkne interface modules it's showing inputs wiring faults

  • @nirajnirala5605
    @nirajnirala5605 Год назад

    Bhai hame bim dadcar ke video bhej

  • @lakshman9229
    @lakshman9229 Год назад

    Pls suggest me solutions

  • @lakshman9229
    @lakshman9229 Год назад

    Model no MI-DCZRM

  • @tusharimran8117
    @tusharimran8117 Год назад

    power supply connection 6 and 7 but where is sounder line connation

  • @lakshman9229
    @lakshman9229 Год назад

    After for action, its showing input wiring fault

  • @lakshman9229
    @lakshman9229 Год назад +1

    We are facing 1 issues with panel

    • @Ansari29
      @Ansari29  Год назад

      Please share pic to ansari2991@gmail.com

  • @swarupdas1323
    @swarupdas1323 Год назад

    Conventional panel ka hooter bajega Nehi kya....hooter ka connection kaha karu