Morley IAS DXC Panel Commissioning | Fully Practical | Autolearn | DX CONNEXION | By Ansari29

Поделиться
HTML-код
  • Опубликовано: 21 авг 2024
  • In this video, you can learn how to do commissioning of Morley IAS DXC panel.This video is important for project & service engineer who is working in fire & safety industry. This video is also useful for those person who are working in facility & operation industry.
    If you are first time watch my channel so I request you to please first visit my channel videos & if you like my videos then only subscribe to my channel & also write comments if you want such valuable information.
    __________________________________________________________________________
    You can also join us on our facebook page, link available below.
    / ansari2991
    __________________________________________________________________________
    Must watch my previous video for more knowledge
    ---Interview Question & Answer On Fire Suppression System | Part-3 | FM200 | NOVEC | By Ansari29
    • Interview Question & A...
    ---Interview Question & Answer in Fire Alarm System | Part-2 | By Ansari29
    • Interview Question & A...
    ---Interview Question & Answer in Fire Alarm System | Part-1 | By Ansari29
    • Interview Question & A...
    ---Faults & Troubleshooting in Addressable Fire Alarm System | Types of Faults | In Hindi | By Ansari29
    • Faults & Troubleshooti...
    ---Ground Fault in Addressable Fire Alarm System | Causes & Troubleshooting | Easy to identify | Hindi
    • Ground Fault in Addres...
    ---Addressable Fire Alarm System | How its Work | Type of Addressing | Module Integration | In Hindi
    • Addressable Fire Alarm...
    ---Builder Integration In Addressable Fire Alarm System By Using Control & Monitor Module | Ansari29
    • Builder Integration In...
    ---Monitor Module & How its Work | Fire Alarm Integration | Flow Switch, WLD, EDR, VESDA Integration
    • Monitor Module & How i...
    ---Control / Relay Module in Addressable Fire Alarm System | Module Integration | CRF300,ULMCOM,MI-DCMO
    • Control Module in Addr...
    -----------------------------------------------------------------------------------------------------------------------Morley IAS DXC-1, Morley IAS DXC-2, Morley IAS DXC-3, Morley IAS DXC-4,
    Honeywell fire alarm commissioning,fire alarm system commissioning,fire alarm testing and commissioning,commissioning in hindi,fire alarm testing,testing and commissioning of fire alarm system,fire alarm,fire alarm installation,fire alarm system testing,fire alarm system working principle,fire alarm system in hindi,how fire alarm system works,fire alarm system,fire alarm system installation,how to program a fire alartm panel,how to do fire alarm system installation
    fire alarm panel,conventional fire alarm system,designing of fire alarm system in hindi,conventional fire alarm system in hindi,fault & troubleshooting in fire alarm system,फायर अलार्म सिस्टम में दोष और समस्या निवारण,open circuit fault in fire alarm system,battery fault in fire alarm system,AC supply fault in fire alarm system,fire,smoke detector,MCP,heat detector,troubleshooting,fault,addressable fire alarm system wiring,addressable fire alarm system installation,addressable fire alarm system installation in hindi,addressable fire alarm system tutorial,addressable fire alarm advantages,addressable fire alarm system cabling,addressable fire alarm system diagram,fire alarm addressable system wiring diagram,addressable fire alarm system explained,how addressable fire alarm system works,addressable fire alarm system loop,fire alarm system addressable type,addressable fire alarm system wiring,
    addressable fire alarm system installation,
    addressable fire alarm system installation in hindi,
    addressable fire alarm system manufacturers in india,
    bosch addressable fire alarm system,
    addressable fire alarm system communication protocol,
    addressable fire alarm system components,
    addressable fire alarm system cabling,
    conventional and addressable fire alarm system,
    conventional vs addressable fire alarm system,
    addressable fire alarm system diagram,
    addressable fire alarm system design,
    fire alarm addressable system wiring diagram,
    addressable fire alarm panel,
    addressable fire alarm system explained,
    addressable fire alarm system honeywell,
    how addressable fire alarm system works,
    honeywell addressable fire alarm system wiring diagram,
    addressable fire alarm system india,
    addressable fire alarm system installation guide,
    addressable fire alarm system loop,
    addressable fire alarm system manufacturers,
    wiring of addressable fire alarm system,
    addressable fire alarm system ppt,
    addressable fire alarm system protocol,
    addressable panel fire alarm system,
    ravel addressable fire alarm system installation,
    addressable fire alarm system specification,
    addressable fire alarm system siemens,
    addressable fire alarm system,
    addressable fire alarm system working principle,
    addressable fire alarm system wiring diagram,
    -----------------------------------------------------------------------------------------------------------------------
    #Commissioning
    #MorleyIASDXCautolearn
    #Firepanelcommissioning

Комментарии • 227

  • @Arbab_vlog88
    @Arbab_vlog88 Год назад +1

    Aapka video bahut helpful hota hai bhai

    • @Ansari29
      @Ansari29  Год назад +1

      Thank you, pls share my videos in your company group

  • @tahirshaikh3989
    @tahirshaikh3989 2 года назад +1

    Thank u sir
    Most Awaited for this Vedio
    Jzk

    • @Ansari29
      @Ansari29  2 года назад

      Your most welcome Tahir

  • @techopinion7639
    @techopinion7639 2 года назад +1

    You are doing good work. Professional work 👌
    Thanks from Lahore, Pakistan

    • @Ansari29
      @Ansari29  2 года назад

      Thanks for your comments 🙂

    • @Ansari29
      @Ansari29  2 года назад

      Pls share my videos in your company group

  • @rohansuresh455
    @rohansuresh455 Месяц назад +1

    Hi Ansari we have Morley DXC panel. we have one fault with this (LOOP OPEN CIRCUIT L1) Before one heart detector damage. we change this detector, to the same address.

    • @Ansari29
      @Ansari29  Месяц назад

      Aapky doubt ka video upload hogaya h please check. Pls subscribe to my channel & press the bell icon for notifications

    • @subratsahoo3657
      @subratsahoo3657 Месяц назад

      Can you send me the video link for open loop ?​@@Ansari29

  • @z.m.chainal6736
    @z.m.chainal6736 2 месяца назад

    ❤❤❤

  • @jayantkumarmangaraj8689
    @jayantkumarmangaraj8689 2 года назад +1

    Informative Vedio,
    Can you please make a Vedio on addressable FA system with a laptop or desktop commssing.

  • @asgarrkl
    @asgarrkl Год назад +1

    Please reply for the following
    1. What is the loop card concept in a addressable fire alarm system?
    2. Is there any cost difference between 2 loop panel and 4 loop panel of honeywell? or technically as we have total 300 devices in our G+5 floor. Do we need 4 loop panel?

    • @Ansari29
      @Ansari29  Год назад

      1. Loop card means 1 loop circuit
      2. Yes 2 & 4 loop panel have different cost.
      3. More than 198 you have to install 4 loop panel

  • @gopikumarmishra8544
    @gopikumarmishra8544 2 года назад +1

    Honywell ka frenhight series IFP2100ECS ka manual programming ka video banaeye

  • @MDKHAN-nh5vg
    @MDKHAN-nh5vg 2 года назад +1

    super 👍

    • @Ansari29
      @Ansari29  2 года назад

      Thanks Mr.Khan

    • @Ansari29
      @Ansari29  2 года назад

      Pls share my videos in your company group

  • @sayedmohdazim254
    @sayedmohdazim254 2 года назад +1

    Bhai mujhe batao apollo x95 panel mein addressing kaise edit karte hai. 1 vlog apollo x95 mein bhi banao Programming & Commissioning per.

    • @Ansari29
      @Ansari29  2 года назад

      Check karna padyga ....

  • @rabbualam8568
    @rabbualam8568 2 года назад +1

    Sir plz aage ka video bana kar daliye mai aap ka video ka wait karta hu ane ka

    • @Ansari29
      @Ansari29  2 года назад

      Sure Alam, thoda busy ho ek project m, jald hi new topics par video aana shru hojayega....

    • @Ansari29
      @Ansari29  2 года назад

      Thanks for your comment dear 🙂

  • @rabbualam8568
    @rabbualam8568 2 года назад +1

    Sir aap se ek request h ki addressbal system pe ek video banaye jis me kya kya device lagta h connection or

  • @rabbualam8568
    @rabbualam8568 2 года назад +1

    Sir kab video bana kar daliyega jo hum bole the video bana ke dalne ke liye daliye n sir plz plz jaldi se

    • @Ansari29
      @Ansari29  2 года назад

      Hi Alam, mai ny addressable system ka ek video banaya h jismai almost sub explain kiya hoo
      Pls find below link
      ruclips.net/video/_6_xiGmG4CE/видео.html

  • @sportswouldcup
    @sportswouldcup 2 года назад +1

    Sir drowning se xplane kar ke btaiye Honeywell Morley panel pe please

  • @rk6786
    @rk6786 2 года назад +1

    Hi bro your doing great job. I have dxc 2morlay panel fault showing device added. Once we lean the loop still same issue .. kindly give suggestions

    • @Ansari29
      @Ansari29  2 года назад

      Try to do autolearn

  • @vinayreddy.h5906
    @vinayreddy.h5906 Год назад +1

    Please do SMX 4 loop panel video

  • @zabirshah3472
    @zabirshah3472 Год назад +1

    Assalamualaikum Bhai .aap ne zone ke bare men nahi btaya zone se hi hooter bajta hai kis detector se hooter bajana hai

    • @Ansari29
      @Ansari29  Год назад

      Detector k activate hony par NAC circuit activate hojati hai or hooter ko supply milta hai

  • @amolwankhade8433
    @amolwankhade8433 Год назад

    Dear .sir ...
    Monitor module. Control relay module
    And REPETOR Pnel ka ..commissioning kaise kare...
    Or isko addressing kaise kare ....
    Please bataiye

  • @ak_double_one
    @ak_double_one Год назад +1

    What output is generated by the smoke detector which helps panel to recognise particular address of the detector.

  • @akashpandav9601
    @akashpandav9601 2 года назад +1

    Sir comishning ke pehle detector blink nahi karte kya?

  • @mobitech7268
    @mobitech7268 2 года назад +1

    Sir, how much distance should be there between two smoke detector as per standard? And for above false ceiling detector spacing will be same or different?

    • @Ansari29
      @Ansari29  2 года назад

      Pls check my detector spacing video..

  • @vijilprajapati3756
    @vijilprajapati3756 Год назад +1

    98 smoke detector connect in 1 loop now
    I m extend one more loop and now we are 50 device divided to 2 loop now 1 loop 46 and other loop 52
    But problem is before loop break and device divided so device missing error are occurs or not in 1 loop?

    • @Ansari29
      @Ansari29  Год назад

      Auto learn again, your issue will resolved

  • @vijilprajapati3756
    @vijilprajapati3756 2 года назад +1

    We make communicate two morlay dxc4 panel each other. Fire occurs in one loop of one panel how to result of second panel and loop sounder are are coonect all system

    • @Ansari29
      @Ansari29  2 года назад +1

      There is one TX RX connection terminal for connecting 1 panel to other, you can simply connect & check. Meanwhile I will try to make video on said topic

  • @rishikumar9788
    @rishikumar9788 2 года назад

    Mera or ek sawal hai Morley me beem detector ko kaise install karte hai control module - ya monitor modul me /

  • @dhirendrashah2031
    @dhirendrashah2031 Месяц назад +1

    If we want to add new device in exsting system so what we have to do

    • @Ansari29
      @Ansari29  Месяц назад

      Just connect that device in loop circuit & do Auto learn & then do addressing

  • @atharali8314
    @atharali8314 2 года назад +1

    very useful and knowledgeable video ansari bhai... how to contact to for queries

    • @Ansari29
      @Ansari29  2 года назад

      Thanks, pls send your queries to ansari2991@gmail.com

  • @superknowledge3135
    @superknowledge3135 Год назад

    Sir mere dxc4 panel ka LOOP CARD response nahi le raha h .sab card remove karne ke baad bhi har loop ka niche wala LED hi kam kar raha b

  • @mawazahmed3560
    @mawazahmed3560 2 года назад +1

    Sir Siemens Fire Alarm panel K baare me Kuch Details Bataye sir please

    • @Ansari29
      @Ansari29  2 года назад

      Ok I will try to make video on said topic...

    • @Ansari29
      @Ansari29  2 года назад

      Pls share my videos in your company group

  • @syedzafar2068
    @syedzafar2068 2 года назад +1

    MCP agar detector k bich me lagana padta hai to mcp me bhi addressing karna padega kya?

    • @Ansari29
      @Ansari29  2 года назад +1

      Yes, Addressable system m mcp m bhi addressing hoti hai ...

    • @syedzafar2068
      @syedzafar2068 2 года назад

      @@Ansari29 thanks

  • @prashantprabhune461
    @prashantprabhune461 2 года назад +1

    Hello.,
    can you explain difference between Dx 4c & Zx 5e.
    why I should promote zx5 e then Dx

    • @Ansari29
      @Ansari29  2 года назад

      I need to check...

  • @SantoshJadhav-su3bw
    @SantoshJadhav-su3bw 7 месяцев назад

    Dxc2 connection diagram with iclock990

  • @ajaysingh1921
    @ajaysingh1921 2 года назад +1

    Hooters kawn sa lagega sir kya Morley ka Loop hooter lagega

    • @Ansari29
      @Ansari29  2 года назад

      Loop hooter.... Ya fir CM k through bhi hooter ko activate kar sakty hai but best loop hooter sahi rehta hai

  • @rabbualam8568
    @rabbualam8568 2 года назад +1

    Assalamu alaikum sir video bahut din ho gaya h nhi lad rahe h kab daliye ga

    • @Ansari29
      @Ansari29  2 года назад

      Ha alam bhai thoda busy chal raha hoo Isiliye video record karny ka time nhi milra

  • @ShadabKhan-ks4hf
    @ShadabKhan-ks4hf 2 года назад +1

    Sir 1 loop m kitne detecter add kar sakte hain maximum

    • @Ansari29
      @Ansari29  2 года назад

      Morley m 99 detector add kar sakty h but har panel ka alag alag hota hai

  • @nexttime2871
    @nexttime2871 Год назад +1

    Haw to connect addressable sounder in panel dxc 2 loop

    • @Ansari29
      @Ansari29  Год назад

      Hooter option provided

  • @prajapatipragnesh3504
    @prajapatipragnesh3504 2 года назад

    Dxc panel main loop add kaise kare?
    Or comissioning me program kaise kare

  • @rishikumar9788
    @rishikumar9788 2 года назад

    Sir commission karne ke liye main menu me konsa ki pahle press karte hai

  • @21rajmangade51
    @21rajmangade51 2 года назад +1

    Fire damper per video bano na

  • @ligeeshk7268
    @ligeeshk7268 Год назад

    Sir in this, automatically detect the panel, which sensors are conected or not?
    And any brand of facp detect automatically the sensors?
    We have the duty to edit or adress the names

  • @devchauhan8814
    @devchauhan8814 Год назад +1

    Dear Ansari ji,
    Plz tell me for logic and pattern create

  • @hamidsayyad2727
    @hamidsayyad2727 2 года назад +1

    Bhia fire alaram.. K point ka kya charges h. Mtlb labour charhe

  • @Satsangkamargjaigurudev
    @Satsangkamargjaigurudev Месяц назад +1

    Hi i am getting fault - No Reply from device R001. i am not able to find the device R001. please reply on the same

    • @Ansari29
      @Ansari29  Месяц назад

      Check panel programming. R001 kisko assign Kiya hai....wo faulty ya fir disconnect hua h

  • @sarfraj9317
    @sarfraj9317 Год назад

    Honeywell notifier Id 3000 evacuate program. How to know plzz 🙏 one video for this .

  • @rabbualam8568
    @rabbualam8568 2 года назад +1

    Hello sir new video kab dal rahe ho bahut din se intezar kar raha hu video ana ka daliye sir plz

    • @Ansari29
      @Ansari29  2 года назад

      Hi Alam, yes bohot din sy video nhi upload kiya because kuch personal reasons sy time nhi mil pa raha hai... But jald hi videos upload hogy.... Apko kon sy topic par video chahiye... Mujhe bataye m try karta hoo...

    • @rabbualam8568
      @rabbualam8568 2 года назад +1

      Thik h sir

  • @rk6786
    @rk6786 2 года назад

    Next same Morley dxc2 address not set asper cabling it means as per cabling from panel 1,then 2 3,4 but detector address placed like from panel 2 address,1,4,3 if we install it's give any issue

  • @rabbualam8568
    @rabbualam8568 2 года назад +1

    Sir video nhi bana rahe h video bana kar daliye sir

    • @Ansari29
      @Ansari29  2 года назад +1

      Thanks Alam
      Thoda busy hoon ek project m. Next month sy regular videos aayegy. Each topic p.

  • @activesystems4668
    @activesystems4668 Год назад +1

    if any demo with dxc-2 panel communication with usb lead cable

  • @midhunsankar9974
    @midhunsankar9974 2 года назад

    Bro..we have simplex 4100 semi addressble pane.zone ways connection not adress type..we have 8 lift connected befor..now one lift NC wire is missing from fire panel..so wt we do for ne NC wire for lift?

  • @amitkumarjha6174
    @amitkumarjha6174 28 дней назад +1

    I have faults in my device and it is not erasing. Device not resetting. Plz help

    • @Ansari29
      @Ansari29  26 дней назад

      Check that fault, may be Detectors faulty

  • @deepaksarthi5786
    @deepaksarthi5786 11 месяцев назад

    Sir mujhe smoke detector se bina connection nikale smoke detector ko kaise bypass kar sakte hai

  • @amolwankhade8433
    @amolwankhade8433 Год назад +1

    Sir ji..
    Monitor module ,control module
    Isolator module ..ka commissioning kaise kare......
    Panel me nhi aarha hai...

    • @Ansari29
      @Ansari29  Год назад

      Auto learn karo

    • @amolwankhade8433
      @amolwankhade8433 Год назад

      MCP KE NAM SE ATA HAI..
      USKO CHENGE KRKE MONITOR MODULE ...MON KRNA PDA SIR JI..

    • @amolwankhade8433
      @amolwankhade8433 Год назад

      @@Ansari29
      Sir ji .
      Monitor module.
      Jo Flow switch ke liye use Kiya hai
      Usme input open circuit aa rha hai..
      Iskya kya solution hai..
      Please help me..🙏

  • @uttamchaudhari7794
    @uttamchaudhari7794 Год назад

    New detector add karne ke liye programing kaise kare

  • @ShivPujan-iq5dw
    @ShivPujan-iq5dw Месяц назад

    How to make cause and effect and delay time..

  • @tukunabehera7342
    @tukunabehera7342 2 года назад +1

    LED CARD ADDED fault shootout kese kare

  • @swapnilsalvi4707
    @swapnilsalvi4707 Год назад +1

    How to configuration morely fire panel to panel

    • @Ansari29
      @Ansari29  Год назад

      Isi video m configuration h

  • @mohamedkamil4224
    @mohamedkamil4224 2 года назад +1

    Assalammu alaikkum, In facp where should i take the loop connection to repeater panel.form which terminal of the facp.

    • @Ansari29
      @Ansari29  2 года назад

      Use RS485 connection available in panel from point A & B to next panel point A & B. Use 2 core cable for it..I hope you have understood....

    • @mohamedkamil4224
      @mohamedkamil4224 2 года назад

      @@Ansari29 Thank you, in notifier panel the supervisory terminal is there.from that terminal i have to give loop between facp and repeater or any other terminal ports are there?

  • @guruprasad-bq9fz
    @guruprasad-bq9fz 8 месяцев назад +1

    Can I use all Sounders in loop.....

    • @Ansari29
      @Ansari29  8 месяцев назад

      If loop sounder then connect but before check load.

  • @nirmalone3026
    @nirmalone3026 Год назад

    Ji i have one doubt?
    In Est3 Panel Ct1, Ct2, Cc1 what?

  • @faisalsaleem6046
    @faisalsaleem6046 2 года назад +1

    MCP mei data not available Jo fault hota ha wo kis waja say ata ha

    • @Ansari29
      @Ansari29  2 года назад

      Exactly nhi samaj aaraha hai....? What's ur panel fault

  • @akashpandav9601
    @akashpandav9601 Год назад +1

    Sir . What is device level fault???

    • @Ansari29
      @Ansari29  Год назад +1

      Device level means detector sensitivity gets low. You have to replace it

  • @21rajmangade51
    @21rajmangade51 2 года назад +1

    Sir MSFD per ek video banau na

    • @Ansari29
      @Ansari29  2 года назад

      Ok Check karta hooo

  • @prashantsharma7828
    @prashantsharma7828 2 года назад

    Agar Morley fire panel me auto Learn krenge to Jo usme address h vo delt ho jyegi please btaiye

  • @Rdl495
    @Rdl495 2 года назад +1

    Beam detector alignment video

    • @Ansari29
      @Ansari29  2 года назад

      Yes Sure

    • @Rdl495
      @Rdl495 2 года назад

      Thanks sir

    • @Rdl495
      @Rdl495 2 года назад

      Sir your contact plz

  • @tukaidutta5806
    @tukaidutta5806 2 года назад

    Shudhu ok marlei hobe naki panal khule lock korte hobe

  • @awadhrajpal2121
    @awadhrajpal2121 2 года назад +1

    Dear Sir Please I hope ki aap mujhe address pattern programming zone detail me explain kigiye

    • @Ansari29
      @Ansari29  2 года назад

      I will try, I need system so that I can make a video on itm

  • @arunasarthi2334
    @arunasarthi2334 2 года назад +1

    Sir two loop ka panel hai 1 loop sahi bta rha hai dusara loop me double address or divice fult batata hai cable ka continuity bhi check kar liya hu sab sahi hai ab kya karu jisase mera problem solve ho jaye

    • @Ansari29
      @Ansari29  2 года назад

      Device faulty m aap device change kardo or double address k liye m aapko solution dyta hoo thoda w8 kijiye....

    • @arunasarthi2334
      @arunasarthi2334 2 года назад

      @@Ansari29 divice change karne par bhi double address btata hai

  • @rishikumar9788
    @rishikumar9788 2 года назад

    Pls sir reply jarur kariye mujhe kal panel commissioning karna hai

  • @dubeyshyam7570
    @dubeyshyam7570 7 месяцев назад

    Connfiguration fault kaise thik hota hai

  • @abdulrahimkhan2029
    @abdulrahimkhan2029 Год назад +1

    Sir, device level fault how this problem rectify

    • @Ansari29
      @Ansari29  Год назад

      Detector Sensing level gets low, replace the device

  • @islamiyakhan9533
    @islamiyakhan9533 5 месяцев назад

    Sir is Honeywell Dxc 1 Morley IAS Mai conventional hoter chal skta h

  • @rabbualam8568
    @rabbualam8568 2 года назад +1

    Sir aap se request ek video banai cctv camera ka installation ke bare plz

    • @Ansari29
      @Ansari29  2 года назад

      Yes Sure, I will try to make video on said topic.

    • @Ansari29
      @Ansari29  2 года назад

      Pls share my videos in your company group

    • @rabbualam8568
      @rabbualam8568 2 года назад +1

      Plz sir video dalo cctv camera installation ka plz

    • @Ansari29
      @Ansari29  2 года назад

      Yes Sure, thoda wait kijiye, jaisy time milyga bana k upload karuga ..

    • @rabbualam8568
      @rabbualam8568 2 года назад +1

      Sir full setup ke sath video bana ke daliyega installation ka video bada v jayega to koi dikkat nahi thik h sir

  • @MohitKumar-hn2yx
    @MohitKumar-hn2yx 5 месяцев назад +1

    How to divice put in test mode.

    • @Ansari29
      @Ansari29  5 месяцев назад +1

      Go to programming mode.check test option will be there...

  • @mrigankapal828
    @mrigankapal828 2 года назад +2

    KISIKE PASS FIRE ALARM KA KAM HAI TO PLS BATAIYE, MUJHE KAM SIKHNA HAI PLS ANYONE, ANSARI VAI MAINE KNOWLEDGE TO LIYA LEKIN KAM KAYSE KARE, KAM HAI TO DIJIYE PLS

  • @vijilprajapati3756
    @vijilprajapati3756 2 года назад +1

    how to create master panel in fire alarm system in multiple panel

    • @Ansari29
      @Ansari29  2 года назад

      There is no need to create master panel, as company already provide different model for master & slave. We just connect in terminal

  • @udaisinghbhati8590
    @udaisinghbhati8590 Месяц назад

    Sir loop open circuit q dika rah h please solutions

  • @ArifudinArif-in6tt
    @ArifudinArif-in6tt Год назад

    Sir output open circuit pls tell how to fix it

  • @omprakashj3446
    @omprakashj3446 2 года назад +1

    How many control modules can be installed in a single loop?

    • @Ansari29
      @Ansari29  2 года назад

      In Morley 99

    • @omprakashj3446
      @omprakashj3446 2 года назад +1

      Whether number of modules which can be installed depends on manufacturer

    • @Ansari29
      @Ansari29  2 года назад

      Yesss... But module is sufficient to give integration...

  • @raswini9078
    @raswini9078 8 месяцев назад

    Signal corrupt fault showing, how to solve it

  • @premchand7173
    @premchand7173 2 года назад +1

    How to smoke detector delete in panel

    • @Ansari29
      @Ansari29  2 года назад

      Which panel...???

  • @Daisy-hy2qp
    @Daisy-hy2qp 2 года назад

    Sir pls tell us about how to provide power supply for FAS panel and hooters

    • @Ansari29
      @Ansari29  2 года назад

      External 24 VDV power supply

  • @ShahbazHussain-iw6ol
    @ShahbazHussain-iw6ol 7 месяцев назад

    Reset
    Restart kaise kare sir

  • @mahendrasinhravalji3858
    @mahendrasinhravalji3858 2 года назад +1

    Fire foults kese sol kar sakte hai

    • @Ansari29
      @Ansari29  2 года назад

      Pls check my fault & troubleshooting video

  • @shankulkush658
    @shankulkush658 2 года назад +1

    How to creat multiple zones in dxc panel

    • @Ansari29
      @Ansari29  2 года назад +1

      Level 3 m jaky aap loop select karky device ko zone number k hisab sy add karsakty..

  • @NNK99
    @NNK99 Год назад

    Iss panel mein history log delete kaise karte hain please sir ??

  • @DharmendraSharma-xn3lf
    @DharmendraSharma-xn3lf 8 месяцев назад

    Dxc4 mi zone divide kaise karen

  • @yashonathkoli7442
    @yashonathkoli7442 2 года назад +1

    Sir how to clear double address fualt.

    • @Ansari29
      @Ansari29  2 года назад +1

      Try auto learn 1st & then check which detector showing double address

    • @yashonathkoli7442
      @yashonathkoli7442 2 года назад

      @@Ansari29 sir Even after turning auto learning, the device is showing double address.

  • @sanarehman7342
    @sanarehman7342 Год назад +1

    How to rectify Duplicate address trouble

    • @Ansari29
      @Ansari29  Год назад

      Jo bhi duplicate aaraha hai pehly usko delete karo or for new device k option m jaky add karo solve hojayega

    • @sanarehman7342
      @sanarehman7342 Год назад +1

      @@Ansari29 loop Partial short, panel bhi change kar diya still same issue araa hai , double address ka bhi fault ara hai, delete ka koi option nahi hai edit hi kar sakte text wagera me, please suggest

    • @Ansari29
      @Ansari29  Год назад

      @@sanarehman7342 make of the panel...? Pls share pic to me ansari2991@gmail.com

  • @manojkambli1647
    @manojkambli1647 Год назад

    How to program Patten in dxc panel

  • @user-ko8cy7ew7i
    @user-ko8cy7ew7i 8 месяцев назад

    Is there any Institute from where i can get training&programming licesence?

  • @usmanali-xx3qe
    @usmanali-xx3qe 2 года назад +1

    Bhai fire alarm ki cv kase bane kiya ap mujey cv bana kar de saktey hai

    • @Ansari29
      @Ansari29  2 года назад

      Aapka jo bhi knowledge hai wo usmai daal dijiye..apny jis bhi fire panel p kaam kiya hai wo likh di jiye that's it

    • @usmanali-xx3qe
      @usmanali-xx3qe 2 года назад

      @@Ansari29 mere pass 6 saal ka experience hai notifier ka agar ap bana de tu ap ka thanks

  • @amitkashyap2429
    @amitkashyap2429 2 года назад +1

    M facing Mon input 2 - input open circuit
    Mon input 1- input open circuit ...pls tell how fix this

    • @Ansari29
      @Ansari29  2 года назад

      Please check loop circuit, it may be open. Remove all the cable from the panel & take countinity test. You will get the idea.

    • @amitkashyap2429
      @amitkashyap2429 2 года назад

      @@Ansari29 i ihave checked my loop is okay ...but still its showing it

    • @ArifudinArif-in6tt
      @ArifudinArif-in6tt Год назад

      Output open circuit pls tell how fix this

  • @RohitKumar-ur5wn
    @RohitKumar-ur5wn Месяц назад

    75 alaram point hor device kasa aad kra

  • @hanumanaika4321
    @hanumanaika4321 9 месяцев назад

    I need for hooter connection video

  • @HoseinSheykh
    @HoseinSheykh 3 месяца назад +1

    Hello, how are you? I have an urgent question about morley dx 2 is it possible for you to help me?

    • @Ansari29
      @Ansari29  3 месяца назад

      Tell me your doubt..??

    • @HoseinSheykh
      @HoseinSheykh 3 месяца назад

      johan it means dear

    • @HoseinSheykh
      @HoseinSheykh 3 месяца назад

      The output voltage of each 2 loops is 11 volts, is this correct?

  • @pathanmajidkhan1688
    @pathanmajidkhan1688 2 года назад +1

    Level fault kese hatay

    • @Ansari29
      @Ansari29  2 года назад

      Detector ka sensing level kam hogaya hai, pls replace asap

  • @saurabhkumars.k688
    @saurabhkumars.k688 2 месяца назад

    Sir I m new uesr fire panal cheek of fire

  • @vivekkumarsingh8942
    @vivekkumarsingh8942 Месяц назад

    Laptop se nahi hota hai kya

  • @omkardattsharma6336
    @omkardattsharma6336 Год назад

    Sir floor by floor hooter kse kre

  • @instrumentation4u531
    @instrumentation4u531 2 года назад

    Please help me with Honeywell HM-PSE-S2 wiring diagram , plzzz

  • @imbsr2221
    @imbsr2221 Год назад

    Hii sir this side bhaigirah mujhe morley ias addressble panel ko power device se Jodna tha jisse ki fire incident hone par light of ho Jaye uske liye mujhe panel me ek no to NC point chahiye tha please help me