Daikin VRV3 | error J2, E6 | Current Value detect by current sensor

Поделиться
HTML-код
  • Опубликовано: 26 авг 2024

Комментарии • 59

  • @g8s456
    @g8s456 Год назад +3

    If you have a J2 error & your standard compressors are pulling normal current range, you either have faulty current sensors or the connections to the control board are not correct.
    I’ve had this issue and every time it was a faulty current sensor.

  • @mymusic-tp1bh
    @mymusic-tp1bh Год назад +3

    how much control voltage from control pc board to inverter board? Measured at which clip X4A,X6A?

  • @Didik-cq8wy
    @Didik-cq8wy Год назад +1

    Trimakasih bos

  • @aureliancioroiu8178
    @aureliancioroiu8178 Год назад +2

    Hello Mr Bon.Thank you for all your video.
    Could you help me about Daikin VRV III?
    I have vrv classic inverter with 1 external unit and 5 indoor units with 3 errors:U4,J2,J7
    2 of them including master internal unit is dead.
    I want to remove 2 of them firstly and make the communication wires between the other functional ones.
    After repairing this errors, i have to do some settings from BS Button or from remote controllers like a setup master internal units and/or other settings?
    And witch settings I have to do after add indoor units?
    Thank you!

    • @BonMj
      @BonMj  Год назад +1

      On power and press reset at outdoor master cu

    • @aureliancioroiu8178
      @aureliancioroiu8178 Год назад +2

      @@BonMj ohh, thanks.Just one time or for few seconds?

    • @BonMj
      @BonMj  Год назад +1

      @@aureliancioroiu8178 wait for awhile

  • @kunanonmukdahan1745
    @kunanonmukdahan1745 Год назад +1

    Do you have a solution or VDO to check PCB inverter , PCB noise , PCB fan for VRV3 and VRV4?

  • @karimchiu7527
    @karimchiu7527 Год назад +1

    thanks sir Bon

    • @BonMj
      @BonMj  Год назад

      Welcome bro

  • @Marcoguima45
    @Marcoguima45 Год назад +1

    Good Job.

  • @RamKrishna-zb5ng
    @RamKrishna-zb5ng Год назад +2

    Nice sir

    • @BonMj
      @BonMj  Год назад +1

      Thanks 🙏

  • @airconditionermechanicsl5352
    @airconditionermechanicsl5352 Год назад +1

    What’s the best daikin app for daikin vrv tecnition use plz give me a linke

  • @abidshirhatti6815
    @abidshirhatti6815 Год назад +1

    Hi sir nice information

  • @user-qb5oi4ur1q
    @user-qb5oi4ur1q Год назад +1

    Thanks for sharing. Able to check VRV2 (2x10HP). Slave unit inverter compressor run, outdoor fan run, but standard compressor not running at all. Master unit all not running at all also. But no error code, what is the likely cause? Thanks

    • @ddre7
      @ddre7 Год назад

      The unit might be in emergency operation.

  • @IMRANKHAN-rr5ut
    @IMRANKHAN-rr5ut Год назад +1

    Please bon sir full complete this video understand practical....

  • @RamKrishna-zb5ng
    @RamKrishna-zb5ng Год назад +1

    Nice job

  • @muhdamin754
    @muhdamin754 Год назад +1

    show me how to check the current sensor if it was faulty

  • @soyevelin3896
    @soyevelin3896 Год назад +1

    Yo quiero saber si los aires vrv 3 y vrv4 y vrv5, dan el mismo error en todos

  • @VivekKumar-hp8vn
    @VivekKumar-hp8vn 7 месяцев назад +1

    Please bon sir tel me hite mode

  • @karaors8970
    @karaors8970 Год назад +1

    good job bro
    +1

    • @BonMj
      @BonMj  Год назад

      Thanks bro 🙏

  • @ahmadnasser4117
    @ahmadnasser4117 Год назад +1

    That saying j2 if it appears to us is the result of the compressor pulling high or what?😁

    • @BonMj
      @BonMj  Год назад +1

      Over 10amps will cos error E6.
      Over 40amps normally error J2

  • @RamKrishna-zb5ng
    @RamKrishna-zb5ng Год назад +1

    Good

  • @mymusic-tp1bh
    @mymusic-tp1bh Год назад +1

    `where I can measure the current sensor value in fault J2? The black and white wirings to clip X25A,X26A?

    • @BonMj
      @BonMj  Год назад

      Yes

    • @mymusic-tp1bh
      @mymusic-tp1bh Год назад +1

      @@BonMj what value can get at clip X25A,X26A?

    • @BonMj
      @BonMj  Год назад

      @@mymusic-tp1bh around 200k ohm

    • @mymusic-tp1bh
      @mymusic-tp1bh Год назад +1

      @@BonMj Thanks for your lecture, helpful.

    • @mymusic-tp1bh
      @mymusic-tp1bh Год назад +1

      Sir, where can check the current sensor value is 0 during compressor operation;
      or more than 15A during compressor stop when in abnormal case.

  • @akashshaw214
    @akashshaw214 Год назад +1

    Hlw sir
    Is there any code for normal split inverter odu pcb service light. Because I see a machine odu pcb service light blink 2 time and then 10 second off and then blink 2 times. That's why odu doesn't start but indoor running smoothly and not showing any error code.

    • @BonMj
      @BonMj  Год назад

      Check outdoor eev, pcb

    • @akashshaw214
      @akashshaw214 Год назад +1

      There is expansion valve in odu there is capillary

    • @akashshaw214
      @akashshaw214 Год назад +1

      RKY5OUV16V3 MODEL
      DAIKIN INVERTER SPLIT AC

  • @thetnainghtay4185
    @thetnainghtay4185 Год назад +1

    Hi boss daikin sky air error code is UF .what problem sir

  • @juanjuan3557
    @juanjuan3557 Год назад +1

    hai bos my vrv3 code error U2 came out what problem plez help me

    • @BonMj
      @BonMj  Год назад +1

      Check voltage

    • @juanjuan3557
      @juanjuan3557 Год назад +1

      @@BonMj voltage ok no drop stil normal

    • @BonMj
      @BonMj  Год назад

      @@juanjuan3557 try check cu fan pcb and fan motor

  • @mwdub02
    @mwdub02 Год назад +1

    Looks like it’s your compressor

  • @СергейМутин
    @СергейМутин 26 дней назад

    1:04 на русском

    • @BonMj
      @BonMj  25 дней назад

      Thanks

  • @ahmadshukrinurhilmi7575
    @ahmadshukrinurhilmi7575 Год назад +1

    sir bon how to contact u??