If you have a J2 error & your standard compressors are pulling normal current range, you either have faulty current sensors or the connections to the control board are not correct. I’ve had this issue and every time it was a faulty current sensor.
Hello Mr Bon.Thank you for all your video. Could you help me about Daikin VRV III? I have vrv classic inverter with 1 external unit and 5 indoor units with 3 errors:U4,J2,J7 2 of them including master internal unit is dead. I want to remove 2 of them firstly and make the communication wires between the other functional ones. After repairing this errors, i have to do some settings from BS Button or from remote controllers like a setup master internal units and/or other settings? And witch settings I have to do after add indoor units? Thank you!
Thanks for sharing. Able to check VRV2 (2x10HP). Slave unit inverter compressor run, outdoor fan run, but standard compressor not running at all. Master unit all not running at all also. But no error code, what is the likely cause? Thanks
Hlw sir Is there any code for normal split inverter odu pcb service light. Because I see a machine odu pcb service light blink 2 time and then 10 second off and then blink 2 times. That's why odu doesn't start but indoor running smoothly and not showing any error code.
If you have a J2 error & your standard compressors are pulling normal current range, you either have faulty current sensors or the connections to the control board are not correct.
I’ve had this issue and every time it was a faulty current sensor.
👍
how much control voltage from control pc board to inverter board? Measured at which clip X4A,X6A?
Trimakasih bos
👍
Hello Mr Bon.Thank you for all your video.
Could you help me about Daikin VRV III?
I have vrv classic inverter with 1 external unit and 5 indoor units with 3 errors:U4,J2,J7
2 of them including master internal unit is dead.
I want to remove 2 of them firstly and make the communication wires between the other functional ones.
After repairing this errors, i have to do some settings from BS Button or from remote controllers like a setup master internal units and/or other settings?
And witch settings I have to do after add indoor units?
Thank you!
On power and press reset at outdoor master cu
@@BonMj ohh, thanks.Just one time or for few seconds?
@@aureliancioroiu8178 wait for awhile
Do you have a solution or VDO to check PCB inverter , PCB noise , PCB fan for VRV3 and VRV4?
thanks sir Bon
Welcome bro
Good Job.
Thanks
Nice sir
Thanks 🙏
What’s the best daikin app for daikin vrv tecnition use plz give me a linke
Hi sir nice information
Thanks
Thanks for sharing. Able to check VRV2 (2x10HP). Slave unit inverter compressor run, outdoor fan run, but standard compressor not running at all. Master unit all not running at all also. But no error code, what is the likely cause? Thanks
The unit might be in emergency operation.
Please bon sir full complete this video understand practical....
Nice job
Thanks
show me how to check the current sensor if it was faulty
Yo quiero saber si los aires vrv 3 y vrv4 y vrv5, dan el mismo error en todos
Most
Please bon sir tel me hite mode
good job bro
+1
Thanks bro 🙏
That saying j2 if it appears to us is the result of the compressor pulling high or what?😁
Over 10amps will cos error E6.
Over 40amps normally error J2
Good
👍
`where I can measure the current sensor value in fault J2? The black and white wirings to clip X25A,X26A?
Yes
@@BonMj what value can get at clip X25A,X26A?
@@mymusic-tp1bh around 200k ohm
@@BonMj Thanks for your lecture, helpful.
Sir, where can check the current sensor value is 0 during compressor operation;
or more than 15A during compressor stop when in abnormal case.
Hlw sir
Is there any code for normal split inverter odu pcb service light. Because I see a machine odu pcb service light blink 2 time and then 10 second off and then blink 2 times. That's why odu doesn't start but indoor running smoothly and not showing any error code.
Check outdoor eev, pcb
There is expansion valve in odu there is capillary
RKY5OUV16V3 MODEL
DAIKIN INVERTER SPLIT AC
Hi boss daikin sky air error code is UF .what problem sir
Check indoor thermistor
@@BonMj thanks sir
hai bos my vrv3 code error U2 came out what problem plez help me
Check voltage
@@BonMj voltage ok no drop stil normal
@@juanjuan3557 try check cu fan pcb and fan motor
Looks like it’s your compressor
1:04 на русском
Thanks
sir bon how to contact u??