Earth Pit 1 = for ACDB & Inverter. Earth Pit 2 = for DCDB, Panals & structure. Earth Pit 3 = for Lightning Arrester. Is it proper way to do earthing for 3kw solar plant?
Sir ,if I want to measure the resistance between 2 wires (BSNL for ex 1km ) will this meter support. If it support at which I have to connect Plz reply me
my doubt is , it is necessary to fix both p2 & e2 in a same direction, then your answer is yes means, what will happen if we fix that auxiliary electrodes in a oposite opposite direction .can you please clear me
Thanks for your video sharing its very informative, i want to ask one question in this case we get resistance of 12.16 ohm how we will bring it to 5 ohm ? awaiting for your valuable reply
In order to reduce the resistance of the earth pit , we will have to increase the conductivity of the earth pit , so for that we usually drain 10L water mix with salt in the earth pit
as i know if we have current more than 200A we use minimum 2 earth pits than how we will measure earth resistance either we have to connect both earth pits and then measure or any other method plz reply
See usually in case of dual or tri vector earthing , we test the resistance of individual earth pit , not by connecting 2 together , as per the IEC standards an individual earth pit should offer a resistance of 5ohms or below it , which is a safe limit and ensures that if you have a heavy leakage current then at this resistance it will be smoothly absorbed by earth
Hi sir, You have taken the distance from E1(P1) to P2 as 10m and then P2 to E2 as 10m again. But in the connection diagram of the earth tester it's 0.62 D and 0.38D, which means they shouldn't be equal.
Thanks for your support Gourang, the value 1.25 is the material resistance of the GI strip and earthing rod, so this value has to be subtracted from final value to get exat resistance of earthing pit.
You again listen to the video.actually we want to find the earthing resistance of the earthing rod as well as the earthing resistance of the soil in which the earth rod is present that is rod+soil only.But since while measuring the resistance of those two things, you are using red and green and blue electric wires, the result on the meter will show a combination of three things( rod+soil+ colored wires).so in the video he measures the resistance of the colored wires separately which is 1.25 ohm.So to find only resistance of rod+soil,you have to subtract 1.25 ohm from the reading given on the meter( which was about 13).
Pit resistance is 12.16 ohms.. Is this good earthing ??? I heard that earthing should be less than 5 ohms.. Please share your views brother.. You explained well but conclusion is not clear..please explain .. I would be thankful to you
The reason why we conducted this earth resistance test because we had a doubt on this earth pit , as we detected that AC voltage between the neutral and earth was coming about 20-22v which was beyond limit , You are absolutely right the pit resistance should be below 5ohms , but ours was 12.16ohms , so what we did to improve it , we immersed 20liters mixture of water with rocksalt inside the earth pit to lower the resistance , and finally got value below 5ohms
Changing the direction can make the distance between earth electrode and test electrode E2 , close to the value of resistance which you will get will not be according to the standard test procedure of earth test
4mm conducter is actually underated , and not at used for earthing , and lightning surge are heavy , as you know the charges only flow on the surface of the conductor so you need higher cross-section conducter , only use 25mmx3mm GI flat strip
Brilliant and Detailed demonstration Only thing I want to ask, This one reading is suffice or we have to taken multiple readings on different distances and average out them all? Thanks in advance, Very informative video.
The electrode E1, P1 passes current in soil which is detected by earth pit at a fixed voltage by device so by formula V=I/R the device calculate R i.e. Resistance of soil
Yes ,our value was high , is leye humne earth test conducted keya tha, kyuki humara solar inverter was facing overvoltage issue ,the standard value of proper Earth pit should be below 5ohms
It it a method to complete the circuit, by shorting E1, P1, iske alawa soil resistance test ke time all 4 points E1, P1, E2, P2 is used no point is shorted
@@SustainableEveryDay Earth resistance meter should be done only with earthy tester,if you use multimeter it will only indicate continuity but not the actual healthy of the earth pit
@@SustainableEveryDay thank you for your prompt reply, another question if you may 😅. What is the resistance of a human body if corrected directly to earth
Chemical earthing is cheap in cost . If you want power full earthing then go for GI PIPE MINIMUM 38MM TO 50MM(ISI) (TATA,JINDAL) OR go for COPPER PLATE earthing. in both types of earthing coal and salt are used. minimum 8 feet depth. For better result. please provide watering pipe for regularly maintain earth resistance below 5 ohms by adding saulty water every 3 to 6 months as per your requirements
Take a bucket with water 10liters and mix rock salt half kg in the bucket and pour the water in earthing pit which you want to test it will increase the conductivity of ground electrode
This is a standard set in the industry to measure the resistance, for earth test because for different distance you will get different values, which will confuse you
Your demo is not clear. It wont help the beginners . your need to elaborate what is E1, P1, E2, P2. Similarly you then need to narrate why u short the E1 and P1.. Explain the depth of electrode. Explain it more to be more beneficial. Its not valuable..
Kafi informative lag raha tha, mahar mujhe to yeh samaj mai nahi aya khi yellow wire kaha se shuru hoti aur kah stop..Pls😮
Spikes jo E2 aur P2 ki through he kya earth pit k series or line me lena he ya kahi bhi lagaskte he bas 10m or 20m from tester ??
Earth Pit 1 = for ACDB & Inverter.
Earth Pit 2 = for DCDB, Panals & structure.
Earth Pit 3 = for Lightning Arrester.
Is it proper way to do earthing for 3kw solar plant?
EP - 1 no. DCDB + INVERTER body dc section+ panels + structure
EP - 2 Nno. ACDB + INVERTER AC section
EP - 3 For LA
@@SustainableEveryDay Thanks a Lot G
Sir oms ya mega oms hona chahiye.wese kam se kam 1megaoms hona chahiye kya bis k anusar.
Sir please hamen yah bataen ki hamare solar plate dhone se platon ko hath lagane se current padta hai
Hi
Can. We use this instrument to check underground water for bore well
Not possible
3 wires connected together and 1.25 ohms substract... is it right procedure?
Is it as per IS?
Sir ,if I want to measure the resistance between 2 wires (BSNL for ex 1km ) will this meter support. If it support at which I have to connect Plz reply me
This is earth tester , the test you want to do , you will require a megger device it will give you better result
Sir you said that resistance should be less then 5 ohm but here is 12.6 ohm?
my doubt is , it is necessary to fix both p2 & e2 in a same direction, then your answer is yes means, what will happen if we fix that auxiliary electrodes in a oposite opposite direction .can you please clear me
No you can fix it in different directions , I did it because the land was cemented , so I had no option
Sir which type of glouse are you using please tell
Normal PVC insulated
Thanks for your video sharing its very informative, i want to ask one question in this case we get resistance of 12.16 ohm how we will bring it to 5 ohm ? awaiting for your valuable reply
In order to reduce the resistance of the earth pit , we will have to increase the conductivity of the earth pit , so for that we usually drain 10L water mix with salt in the earth pit
as i know if we have current more than 200A we use minimum 2 earth pits than how we will measure earth resistance either we have to connect both earth pits and then measure or any other method plz reply
See usually in case of dual or tri vector earthing , we test the resistance of individual earth pit , not by connecting 2 together , as per the IEC standards an individual earth pit should offer a resistance of 5ohms or below it , which is a safe limit and ensures that if you have a heavy leakage current then at this resistance it will be smoothly absorbed by earth
Put water & salt into earth pit
@@SustainableEveryDay😊
Hi sir, You have taken the distance from E1(P1) to P2 as 10m and then P2 to E2 as 10m again. But in the connection diagram of the earth tester it's 0.62 D and 0.38D, which means they shouldn't be equal.
Nice information. Also tell about the value of voltage between Vm3 Inverter solar input points to ground value .
I want to buy earth resistance tester.Please advise me good type and brand I should buy at reasonable price
Waco
Thank you sir for your video,
Why you subtract 1.25 from main value
Thanks for your support Gourang, the value 1.25 is the material resistance of the GI strip and earthing rod, so this value has to be subtracted from final value to get exat resistance of earthing pit.
You again listen to the video.actually we want to find the earthing resistance of the earthing rod as well as the earthing resistance of the soil in which the earth rod is present that is rod+soil only.But since while measuring the resistance of those two things, you are using red and green and blue electric wires, the result on the meter will show a combination of three things( rod+soil+ colored wires).so in the video he measures the resistance of the colored wires separately which is 1.25 ohm.So to find only resistance of rod+soil,you have to subtract 1.25 ohm from the reading given on the meter( which was about 13).
Pit resistance is 12.16 ohms..
Is this good earthing ???
I heard that earthing should be less than 5 ohms..
Please share your views brother..
You explained well but conclusion is not clear..please explain ..
I would be thankful to you
The reason why we conducted this earth resistance test because we had a doubt on this earth pit , as we detected that AC voltage between the neutral and earth was coming about 20-22v which was beyond limit ,
You are absolutely right the pit resistance should be below 5ohms , but ours was 12.16ohms , so what we did to improve it , we immersed 20liters mixture of water with rocksalt inside the earth pit to lower the resistance , and finally got value below 5ohms
@@SustainableEveryDay thank you so much for your assistance....if you could have made a video of remaining part ..it would be a piece of cake...
Kyy load connect ho tab resistance check hoga???
hello sir how are you please can you share with me the prices for those earth tester meter
Sir Earth testing apne kaha ki iski veleu 5ohm se km honi chahiye to fir 13ohm kyu aari h
Ye site mai overvoltage ka issue tha , that's why we were testing this Faulty earth pit
How earthing linked with overvoltage.
10qu is it possible to use earth tester for installation of diesel generator
Bhai aapne 10 ohn pe range set kiya tha, to phir value 13 ohm kyu aaya, aur as pe standards 5ohm hona chahiye
Bro 10 ka matalv 2 digit.vala 😊 Agar achha lage to subscribe kar dio Merko ko
@@jitendrajhafitnesssir ager hum es ku 1000ohm pye set kregye tu kya es ka value 00.13ohm hi ayyega pl tell us thanks u
Hi sir the direction of E2 changes what will be happen?
P2 after E2 is necessary or not?
Changing the direction can make the distance between earth electrode and test electrode E2 , close to the value of resistance which you will get will not be according to the standard test procedure of earth test
Sir ek baat bataiye pls meri earthing ki reading 0.2 aa rahi h to kya galat h
I don't have an earth tester. Is there a way to test it with a multimeter.
No
Can we use 4mm thickness Aluminium wire to connect LA with earthing?
If not then what is the alternate of GI strip?
4mm conducter is actually underated , and not at used for earthing , and lightning surge are heavy , as you know the charges only flow on the surface of the conductor so you need higher cross-section conducter , only use 25mmx3mm GI flat strip
Sir earthing response stay n ho rha ho lgatar up down Ho rha ho to kya kiya jae ki sahi response mile chemical earthing me
Put 25L of water mix with rocksalt in earth pit
@@SustainableEveryDay Sir responce thik aa jaega fir sir
20 feet deep tk chemical earthing huwa hai sir fir bhi response me up down Ho rha hai aisa kyu ho rha hai sir aur Kaise thik hoga
Yes
Contacts proper hai na aap check kar lo, especially Earth & all Neutral line contact joints
Why earth resistance tester is not working in EHV transmission lines
Please reply sir as early as possible . Thank you
EHV transmission line usually have end to end transformer earthing , so even it Earth test is conducted it is done at transformer end
Can I use earth resistance tester for measurement of earthing of EHV 400 kV transmission lines
Yes definitely
@@SustainableEveryDay thank you
Bhai koi batiyga ki 115 kv ka kitna ohm hona chya or 13.8 kv ka kitna or 440 ka kitna hai standard
How did ypu get to the yellow wire from the blue wire. Not explained properly.
Brilliant and Detailed demonstration
Only thing I want to ask,
This one reading is suffice or we have to taken multiple readings on different distances and average out them all?
Thanks in advance, Very informative video.
Correct we will take av of 3 reading
Tin taar ke baare me kuchh information dijiye na
What is the Reason behind 10 and 20 mtr electrode. Why it is necessary.
The electrode E1, P1 passes current in soil which is detected by earth pit at a fixed voltage by device so by formula V=I/R the device calculate R i.e. Resistance of soil
nice video jeethe raho..
Thanks for the support
Sir how will be check the 100 ton weighbridge earth resistance ?
Sir what is output voltage range of DET 2000 used . AC or DC volts
Sir value jyada nahi hai???
Earth resistance value kitna honi chahiye sir??
Yes ,our value was high , is leye humne earth test conducted keya tha, kyuki humara solar inverter was facing overvoltage issue ,the standard value of proper Earth pit should be below 5ohms
That means the value you are getting it shows the earth pit is not correct..?
Yes this Test show the earth pit failed
Analog insulation tester best company name please
Meco
CIE INSULATION TESTER BEST
ANALOG Okva
Electrode kitna metre Jamin mai gaadna hai
Hi sir , in indian we are using different earth pits for both AC( inverter & LA) & DC( stru & invr) is there any particular reason for this ?
Better protection
@@SustainableEveryDay
Solar Panel K moveable stand c LA ki hight kitni honi chaye?
Top level of Pv Panel c above honi chaye ?
Hi, What is the standard value for earth pit resistance??
Below 5ohms
E1 p1 ko short kyun karte hai
..?
It it a method to complete the circuit, by shorting E1, P1, iske alawa soil resistance test ke time all 4 points E1, P1, E2, P2 is used no point is shorted
awesome video thanks for this great content.
Thanks for the support
Why you are combining the yellow 🟡 and red 🔴
Clear nahi ho pa Raha hai
Simple hai pr AAP ne critical bana diye
What is differences between Multimeter and Earth resistance meter?
Can I use multimeter?
Both are different equipment , and work differently
@@SustainableEveryDay Earth resistance meter should be done only with earthy tester,if you use multimeter it will only indicate continuity but not the actual healthy of the earth pit
@@oroknowledge2232 only with Earth resistance tester
@@SustainableEveryDay is it possible to use earth tester for installation of diesel generator
@@oroknowledge2232dear sir pl tell if we check voltage between earth and neutral wire it is 5volt
It means our earth is ok pl pl
What will be depth of each electrodes P2 and E2?
Thanks
Why short E1 and P1..?
Himanshu kya haal chal h kis company me ho abhi......
Bhai agar value zada ho to kaise thik kare Gaye earthing ko
Yes put rocksalt mix 15L water in earth pit
thanks for video
Thanks for the support
What is the Optimal earth resistance
Below 5ohm is all accepted ,
@@SustainableEveryDay thank you for your prompt reply, another question if you may 😅. What is the resistance of a human body if corrected directly to earth
So it will totally depends on how harsh or dry the skin will be , it starts between 100,000ohms for extremely dry to 1000ohms for wet skin
link to second part please
Why use 2 electrode for earthing value test
in vit students do not know hindi so please speak in english
Sure
How many meter deep ground a electrod
3.5
Sir mene 200 V~ pr check kiya h mere meter ka nam DT830D digital multimeter pls sir bata dijiye
Hi, aap mujhse call kar k apne doubt clear Kar sakte ho 9876976705
@@SustainableEveryDay hi
Hi
Y ethna distance se placed electrodes
Yes its the standard method as per IS norms
👌
Thanks for the support
I have found 18 ohm in chemical earthing , how will come below of 5 ohm.
Chemical earthing is cheap in cost .
If you want power full earthing then go for GI PIPE MINIMUM 38MM TO 50MM(ISI) (TATA,JINDAL) OR go for COPPER PLATE earthing. in both types of earthing coal and salt are used. minimum 8 feet depth. For better result. please provide watering pipe for regularly maintain earth resistance below 5 ohms by adding saulty water every 3 to 6 months as per your requirements
price
3500₹
Nice
How to short 3 wire
Simply by connecting them physically
Why earthpit connection disconnected
Repeat the same with analog meter
Range 10ohm but reading is more than 10ohm, How?
but you said it should be less than 5ohm
Yes so this earth pit failed the test , its value is more than 5ohm
But earth value is less then 1 ohm's honi cahiye na
Correct , isleye video mai jo earthing hai wo Earth test mai fail ho gaye
Resistance to under 5ohm hona chahiye tha
My earthing resistance is coming 0.12 is it perfect
Hi Brijesh what is the condition of the soil near earth pit is it dry soil or moisture soil
@@SustainableEveryDay its normal dry and little bit sandy soil
@@SustainableEveryDay please tell me what how it could be resolve
0.45,0.27.0.80
Take a bucket with water 10liters and mix rock salt half kg in the bucket and pour the water in earthing pit which you want to test it will increase the conductivity of ground electrode
Why should take 10m distance
This is a standard set in the industry to measure the resistance, for earth test because for different distance you will get different values, which will confuse you
Or sir how much value suitable for earth resistant,
When grid is connected resistance should be less than 1ohm and when grid is not connected it should be less than 5ohm.
What if the resistance is more than 5 ohm ?
Hi kartik
Then the inverter will experience Abnormal performance as leakage AC and DC CURRENT will find it hard to travel towards the earth pit
👍👍👍👍👍
Thanks
@@SustainableEveryDay sir apne E2, P2 wire ko distance me kyo le gye isko justify kr dijiye pls
What language is he speaking?
Hindi
But iska to 5 ohm jada hai, is it ol
Is it ok
No it's not ok, that is why we were testing it, there was lot of Inverter tripping so we checked the earth pit resistance
What is the solution... Have u poured water and salt in earth pit?
Need help
Your demo is not clear. It wont help the beginners . your need to elaborate what is E1, P1, E2, P2. Similarly you then need to narrate why u short the E1 and P1.. Explain the depth of electrode. Explain it more to be more beneficial. Its not valuable..
Well Akram you are right , many people have pointed out this , surely I will upload a better version
This is not Standerd Earth Testing
Most fake device ,
Don't use it.
nice