AEMC® - Understanding Ground Resistance Testing (3640 Discontinued Replaced by 6424)

Поделиться
HTML-код
  • Опубликовано: 19 июн 2024
  • Understanding Ground Resistance Testing
    A grounding system is a conducting connection by which an electrical circuit or equipment is connected to earth. This connection is used to establish and maintain as closely as possible the potential of the earth on the circuit or equipment connected to it. This connection to the earth provides a low impedance path for electrical currents to travel under fault conditions. The system ground can be a simple metal rod driven into the ground, a grid consisting of multiple electrodes, or another type of grounding system.
    When these disruptions of normal electrical operation do occur, it's very important for the grounding system to operate efficiently. For this to be possible, the grounding circuit must have a low resistance connection to the surrounding earth. And a grounding system will only perform properly if it is designed and installed with local soil conditions taken into consideration.
    This video is an introduction to grounding systems. Our goal is to provide you with a good basic understanding of why grounding is important, the environmental factors to consider when designing a grounding system, and the testing required to ensure your grounding is properly installed and performing to specifications.
  • НаукаНаука

Комментарии • 78

  • @spelunkerd
    @spelunkerd 4 года назад +3

    Well explained, I wish I found this a few years ago.

  • @kemusindi1577
    @kemusindi1577 5 лет назад +5

    Best tutorial for grounding ever, much appreciated

  • @dhadumia
    @dhadumia 5 лет назад

    Awesome video. Thank you!

  • @markdejong1984
    @markdejong1984 4 года назад

    Great video, helped resolve issue at work! Thanks.

  • @djmaidjmai6120
    @djmaidjmai6120 3 года назад

    شكرا لك يا احسن استاذ ياغالي والعزيز في قلوبنا. شكرا شكرا شكرا

  • @ellwalenndhejunny3229
    @ellwalenndhejunny3229 3 года назад +1

    the best explanation sir! thank you

  • @bienlaborte4583
    @bienlaborte4583 5 лет назад

    Too Awesome video. Thank you

  • @ravindraf2462
    @ravindraf2462 4 года назад +1

    INFORMATIVE VIDEO TO ELECTRICAL COMMUNITY-THANKS AEMC

  • @andysummersthxcinemaandmyc7748
    @andysummersthxcinemaandmyc7748 4 года назад +5

    26 dislikes wasn't grounded.
    Informative video.

  • @SillyPutty3700
    @SillyPutty3700 Год назад +6

    This video is pretty good at explaining how to test grounding electrodes and electrode systems. It does however muddle the differences between BONDING and Grounding. The grounding electrode system has little to do with clearing a fault (protecting equipment from faults 2:48).
    Think about that for a moment, apply 120v to a 25 ohm rod (NEC suggested target) will the resulting current flow cause a breaker to trip? 120/25= 4.8a that is not going to cause a 20a or 15a breaker to trip. Even if we lower the resistance to 5 ohms which is a common engineering standard we would only cause a 26a breaker or fuse to open thus clearing a fault. In a commercial building where breakers are often rated at 100a -1000a that could not realistically be relied on to clear a fault. Fault current for tripping breakers is dependent on a low resistance path NOT to earth as suggested here but to the center tap of the transformer or transformer neutral terminal which is a function of BONDING.
    The NEC in article 250.4(A)(1) states that grounded electrical systems “shall be connected to earth in a manner that will limit the voltage imposed by lightning, line surges, or unintentional contact with higher-voltage lines and that will stabilize the voltage to earth during normal operation.”
    Simply stated a grounding electrode system at a service entrance is for power quality not clearing faults. That is not to say it is not an essential part of your electrical system and the rest of this video does a great job explaining how that works.

    • @tfun101
      @tfun101 2 месяца назад +1

      True for the commercial and residential jobs..but for the utility multiple grounds are used which can assist with clearing the faults.

  • @shazogutu6091
    @shazogutu6091 2 года назад

    The best explanation. Thank you Sir

  • @thejunkbox
    @thejunkbox Год назад

    Thank you very much for very elaborateing explanation

  • @robvandijen8481
    @robvandijen8481 Год назад +2

    A professor from Siemens Germany came over for a complicated malfunction of a machine control. He did not allow us to talk about earthing. After all, planes and ships have no earth either. Equipotential bonding was the right word.😁

    • @mernokallat645
      @mernokallat645 Год назад

      Ships are literally grounded. The seawater is at ground potential.

  • @rakamuhammadyusuf44
    @rakamuhammadyusuf44 4 года назад +3

    this video really helps me to understand how to measure the grounding ressitance, and I have a question about it. is it possible to only use a voltmeter, ammeters, and current sources(current genertor) to measure ground resistance using the fall-of-potential method?
    Thank You

    • @AEMCInstruments
      @AEMCInstruments  4 года назад +4

      Yes, it is possible but not practical.
      A tuned voltmeter would be needed to reject all other frequencies than the source test frequency. Our meters use various frequencies to test and the voltmeter is tuned to that frequency for the most accurate readings, rejecting surrounding noise and interference.
      Also, the stack-up of tolerances from all the meters you described would need to be added together to determine the accuracy of the readings you took. With our meters, there is only one accuracy spec for the reading.
      Our multi-function meters also store the distances (in meters or feet) of each measurement needed to graph a full Fall of Potential plot. A minimum of 9 measurements are needed for a valid Fall of Potential plot. This plot is critical in proofing your measurements to know if they are valid.
      Good luck if you try this method!

  • @mc.esteban653
    @mc.esteban653 3 года назад +1

    Nice video!! tanks

  • @nbkk771
    @nbkk771 3 года назад

    Explained very well

  • @EDGEHILLBBKE
    @EDGEHILLBBKE 3 года назад +1

    very informative

  • @lucyelec
    @lucyelec 2 года назад

    Good vedio. Deserve for likes and sharing

  • @surendrakverma555
    @surendrakverma555 Год назад +1

    Very good. Thanks 🙏🙏🙏🙏

  • @eugenepohjola258
    @eugenepohjola258 3 года назад +1

    Howdy.
    1. Power lines.
    Low grounding impedances provide a parallel path to the neutral + earth wire. It hepls to uphold the voltage symmetry along the line during unsymmetrical loading. Some degree of limiting of avalanche voltages is also provided caused by lighting bolts.
    2. Consumer service panels.
    Low grounding impedances increase fault currents and speed up triggering of circuit breakers.
    However, more important is the potential equalizing of the environment of utilization. Therefore. The service gronding should be a copper wire in the ground that encircles the house.
    Regards.

    • @ganesanmuthiganesanmuthi5356
      @ganesanmuthiganesanmuthi5356 2 года назад

      Low impedance so thst the fault current flows, travels fast to earth without affecting others and surroundings.

  • @electroumit
    @electroumit 2 года назад +1

    Thank you.

  • @SundayOwens
    @SundayOwens 2 года назад +1

    great video, may I know if aluminum can be used for earthing? if there is no copper rod.

    • @AEMCInstruments
      @AEMCInstruments  2 года назад

      Bare aluminum is not recommended as a grounding electrode in contact with the dirt/earth. Bare aluminum will likely corrode quickly when in contact with the dirt and the ground system will become ineffective.

  • @copepaste
    @copepaste 3 года назад

    Thank you

  • @hamzalag2006
    @hamzalag2006 2 года назад +1

    Thanks

  • @saifahmed6131
    @saifahmed6131 3 года назад

    How ground resistance test will be performed for Hull floating on water

  • @livingfortomorrow.
    @livingfortomorrow. 2 года назад

    nice video

  • @nazrinrahman94
    @nazrinrahman94 3 года назад +1

    During the survey, you mentioned that the electrodes were planted 6 inches deep (5:50). May I know if there are any effects of different electrode depth? As far as I know, the injected current is regarded as a point source located at the air-ground boundary, regardless of the electrode depth planted.

    • @AEMCInstruments
      @AEMCInstruments  3 года назад +2

      At that moment in the video, the electrodes were placed 10-feet apart performing a Wenner Soil Resistivity Test method.
      To use the simplified formula for the Wenner method, AEMC recommends no more than 1/20th of the spacing for the depth of the electrodes. 1/20th of a 10-foot spacing is 0.5-ft (6-inches)
      There’s no concern when you are at, or shallower than, these depths and using the simplified formula.
      Our meter assumes you are using the simplified formula method and therefore calculates the Rho based upon the simplified formula and the 1/20th depth-to-spacing guideline.
      If you push the electrodes deeper than recommended by us, the simplified formula is no longer valid and the long formula must be used. Our instrument does not perform the long formula calculations automatically. These calculations must be done manually.
      Please contact AEMC Tech Support (techsupport @ aemc . com) for more information.

  • @BYENZER
    @BYENZER 3 года назад +1

    In residential, with a 200 Amp service, what is the MAX AMPS allowed to RETURN back to the utility, VIA the UFER?

    • @djhatton6858
      @djhatton6858 2 года назад

      There is a problem with this video incorrectly describing ground fault current traveling "thru" the ground...doesn't happen/won't happen to trip a breaker. The service neutral wire performs the effective fault current path. Earth cannot be used as an effective fault current path. NEC 250.4(A)(5)

  • @fikaarsyad
    @fikaarsyad Год назад +1

    is it possible to measure on the transmission tower? if the Z electrode is placed 80 feet from the ground rod. Or can we use clamp on tester on transmission tower?thanks

    • @AEMCInstruments
      @AEMCInstruments  Год назад

      We sell a 6474 Tower Testing Kit for tower testing.
      Here's a video describing the process:
      ruclips.net/video/R_exTjDshM4/видео.html

  • @MM10-us1rv
    @MM10-us1rv Месяц назад +1

    Hi! Thank you for the video, how do we find the standard deviation of the results after testing has completed using the Wenner method on the 6471? Thanks!

    • @AEMCInstruments
      @AEMCInstruments  Месяц назад

      Here is an online standard deviation calculator:
      www.calculator.net/standard-deviation-calculator.html
      Just plug your numbers in and hit "Calculate"

    • @MM10-us1rv
      @MM10-us1rv Месяц назад +1

      @@AEMCInstruments Thanks! Is there a way to show the standard deviation numbers on the screen of a 6471 ground tester machine?

    • @AEMCInstruments
      @AEMCInstruments  Месяц назад

      Unfortunately, no. Any standard deviation calculations will need to be done externally from the 6471. The calculator linked above can be useful if you wish.

  • @npcasp5279
    @npcasp5279 Год назад +1

    buena explicación, tengo una duda, porque en los manuales la distancia "A" debe ser mayor a 80 metros ?, no será un error y es 80´to 100`,gracias

    • @AEMCInstruments
      @AEMCInstruments  Год назад

      Hola, la distancia A sugerida es entre 8 y 10 veces la profundidad de la pica de puesta a tierra con el fin de evitar que se empalmen las áreas de resistencia efectiva de la pica Z(H) y del sistema de puesta a tierra bajo prueba. Asumiendo que la pica de puesta a tierra está enterrada 8 m, la distancia A sugerida sería de 80 m. Aún con 80 m de distancia, es necesario realizar tres mediciones posicionando la pica Y(S) a 52%, 62% y 72% de la distancia de A con el fin de verificar la validez de los resultados. Si tiene más preguntas, no dude en contactarnos en techsupport @ aemc.com.

  • @cameronrampersadh889
    @cameronrampersadh889 3 года назад +1

    Hey, can you please explain why the resistance of an earthing system (ie in a power substation) has to be sufficiently low?

    • @AEMCInstruments
      @AEMCInstruments  3 года назад +1

      A grounding system should provide a low-impedance path for fault currents and lightning-strike currents to enter the earth/dirt. This ensures maximum safety from electrical system faults and lightning. The low impedance ground protects equipment and buildings from being damaged by directing this dangerous energy to the earth/dirt.
      More importantly, this provides a level of safety for people and any living animal nearby.

    • @cameronrampersadh889
      @cameronrampersadh889 3 года назад +1

      @@AEMCInstruments great thank you so much

    • @zog0017
      @zog0017 Год назад

      @@AEMCInstruments I like the video, it is very informative. I don't like your wording about "a grounding system should provide a low-impedance path for fault currents and lightning strike currents to enter the earth/dirt". These are very different situations; one requires a 25 ohm impedance and one does not. They should be looked at separately.

  • @vinothy3858
    @vinothy3858 3 года назад

    Boss I want some doubt

  • @baobaoyang1840
    @baobaoyang1840 4 года назад +1

    Can this product test larger metals underground? For example, gold and silver buried by wealthy people in the past.

    • @AEMCInstruments
      @AEMCInstruments  4 года назад +1

      Doubtful. It is true that gold and silver is very conductive and will help lower the overall soil resistivity readings. The problem is that measuring low readings does not automatically indicate lode or placer gold and silver deposits below. For example; subsurface water, ashes, cinder and brine will also lower the readings significantly. Prospecting for gold and silver would be a frustrating trial and error operation using this method. Good luck!

  • @mightyhandengineeringmight6289
    @mightyhandengineeringmight6289 3 года назад +1

    Why was 3711 discontinued?

    • @AEMCInstruments
      @AEMCInstruments  3 года назад +1

      To introduce the next generation of handheld ground testers, the 6416 and 6417.
      As of December 2020, we still calibrate, repair and service the 3711.

    • @mightyhandengineeringmight6289
      @mightyhandengineeringmight6289 3 года назад

      @@AEMCInstruments thank you

  • @johngreen6421
    @johngreen6421 Год назад

    I really like earth grounding resistance meter. I have it on my wish list. Do you need a electrical salesman in Northern California. I love to market your product.

    • @AEMCInstruments
      @AEMCInstruments  Год назад

      Thank you for your kind feedback!
      We currently have a sales representative in the Bay Area who's very good.
      Send an email to techsupport @ aemc . com and I can get you in touch with them about any opportunities in CA.

  • @luisalejandrocardozogutier9365
    @luisalejandrocardozogutier9365 4 года назад +1

    por favor este vídeo se podrá ver en español gracias

    • @AEMCInstruments
      @AEMCInstruments  4 года назад

      Por ahora no tenemos la versión en español de este video.
      Por favor consulte la versión en español del libro de trabajo Entendiendo las Pruebas de Resistencia de Tierra, en el siguiente enlace:
      www.aemc.com/userfiles/files/resources/workbooks/950-WKBK-GROUND-SP.pdf
      Este video está basado en el contenido de este libro de trabajo.

  • @sandipnshinde6504
    @sandipnshinde6504 4 года назад

    My observation that when we give earthing then electricity meter revel fast and bill increase why it happened please reply must

    • @AEMCInstruments
      @AEMCInstruments  4 года назад +1

      I am unclear.
      Did you say that when you add earthing to your system, your electricity bill increases?
      This is unusual and should not happen.
      Please give more detail.
      Thank you

    • @James_Bowie
      @James_Bowie 4 года назад

      I don't understand your question, however one interpretation may be that your earth current is too high, which can be an indication of a lost/bad neutral connection which is a HIGHLY dangerous situation and needs to be checked by a qualified electrician.

  • @thakurarvindsingh5239
    @thakurarvindsingh5239 5 лет назад +1

    hello i need help regarding earthing issue,

    • @AEMCInstruments
      @AEMCInstruments  5 лет назад

      Please contact our Tech Support Hotline at 1-800-343-1391 x351 or email us at techsupport @ aemc . com

  • @djhatton6858
    @djhatton6858 2 года назад

    The explanation of fault current from a ground rod (and as not explained to create the circuit to the service transformer) is an incorrect understanding/explanation of effective ground-fault current path. The NEC does not allow earth as an effective fault current path as the resistance is too high to allow the fault current to flow of sufficient magnitude to trip source breaker. Suggest redoing this part of the video as the information is not being correctly discussed. NEC 250.4(A)(5) "the earth shall not be considered as an effective ground-fault currrent path".

  • @nancyhulan8106
    @nancyhulan8106 3 года назад

    8

  • @cesarelicano3679
    @cesarelicano3679 Год назад +1

    Your explanation is too broad but non substantial for me, what we need is the actual testing at site not like people working construction on their desk or table only.