how to deign gemco dc drive according to motor? max AMP or max KW

Поделиться
HTML-код
  • Опубликовано: 3 дек 2024

Комментарии • 9

  • @ashishgoyal9565
    @ashishgoyal9565 4 месяца назад

    Sir rotor lock test pe video banyi sir

  • @suneelkumar1411
    @suneelkumar1411 Месяц назад

    Sir card ka burden or 680 parameter ka burden ka kisi motor ke hisab se calculation bataiye.

    • @automation7571
      @automation7571  Месяц назад

      4000/motor current (in drive)

    • @suneelkumar1411
      @suneelkumar1411 Месяц назад

      @@automation7571 Good morning sir thanks for reply plz tell for card also.
      I am in Steel industry and in our plant we have Fuji Gemco/Sprint Electric DC controller.
      Motor current is 243A in drive burden is 16 and at card 2 resister are connected in parallel so burden resistance is 6 ohms. This motor application is start stop so sometimes the motor tripped at armature overcurrent or Internal error 0005. Plz help.

    • @automation7571
      @automation7571  Месяц назад

      CT rating??
      And check all control connection if any loose plz tight

    • @suneelkumar1411
      @suneelkumar1411 Месяц назад

      @@automation7571 Sir CT ratio 1000/1A and all power and control connections are Ok.
      Motor RPM 1500 for brake the TMT bar rpm go down till 400 after that 1500. Acc/Dec time is 0.5 sec. Overcurrent fault occurs when motor goes down to up speed. And internal error 0005 occurs when motor is stopped and when we give start command

    • @automation7571
      @automation7571  Месяц назад

      Check actual current for clamp meter when breaking time,
      If current motor rating Thane current limit upto open 10 to 20 % high