Excellent technical information. Thank you. Did you get the part case from navien directly, I assume the case is a complete rebuild case for that model? Keep up the good work.
If it only happens when using hot water for shower and not on heating side or vise versa then yes 3 way valve because it's not switching the flow of water causing the heat exchanger to boil and hit the code e001.
Great help!
Glad I could help!
Excellent technical information. Thank you.
Did you get the part case from navien directly, I assume the case is a complete rebuild case for that model? Keep up the good work.
Thanks. I got it from my supplier FW Webb. It's for this model only.
Thank you for posting this. I have a ncb 240. Supply is getting up to 210 tripping e001. Don’t know if it’s the 3 way valve or circulating pump.
It's 90% 3 way valve 8% internal circulator and 2 % air in system not letting water circulates.
If it only happens when using hot water for shower and not on heating side or vise versa then yes 3 way valve because it's not switching the flow of water causing the heat exchanger to boil and hit the code e001.
terrible.camera man could barely see to follow along because camera was all over the place
Sorry I tried I don't have any go pro yet. Also I don't make any money from this. Just trying to share what I can.