Worcester Leaking Supply/ Flow Manifold. Fault Finding and Repair

Поделиться
HTML-код
  • Опубликовано: 10 сен 2024

Комментарии • 4

  • @bahiaharjinder
    @bahiaharjinder 8 месяцев назад

    Hi raj, is there any issues with the erp + 4000 greenstar range condense traps not draining properly, as they seem to be a lot different to the junior type
    Thanks

    • @BoilerMend
      @BoilerMend  8 месяцев назад +1

      Hi.
      No known issues on the 4000 Condens trap. But only thing I've observed on the Erp Condens trap is that it is a slow run trap with a tiny internal hole. Which, if blocked, can cause no condensate flow through the trap.
      Hope it makes some sense

    • @BoilerMend
      @BoilerMend  8 месяцев назад +1

      Regarding the Erp trap, if it is actually blocked, the trap most probably needs replacing 😬

    • @bahiaharjinder
      @bahiaharjinder 8 месяцев назад

      @@BoilerMend thanks for reply trap can be clear but still doesn't want to discharge seems to be on a lot of occasions u take it out nothing wrong or blocked the old junior style traps were better as the new ones trickle thru +then siphon 👍🏻