How to Diagnose and Repair Restriction in Mitsubishi Mini Split HVAC Tech mini split troubleshoot

Поделиться
HTML-код
  • Опубликовано: 28 дек 2024

Комментарии • 75

  • @Brooks.Mechanical.Electric
    @Brooks.Mechanical.Electric 25 дней назад +2

    I have been in multiple training classes learning inverter systems and vrf technology. They truly are as bulletproof as you can get with HVAC systems. They can overcome so many things that normal systems would easily go down over. So many techs today have no understanding of these systems. The trade schools don't put in any time to teach it which is sad for the new guys since so many changes are coming our way and right out of the gate they are behind on the times. I service Bosch inverter heat pumps and i see guys open the cover and see that huge board and they will just shake their head. Its overwhelming until you spend the time to learn and as you said. Its not that bad, you just have to be willing to put in the work to understand.

  • @stevemas4966
    @stevemas4966 6 месяцев назад +4

    I had my doubts that you would fined the restriction but when you started to cut into the wall I figured you were onto something. Great job!

  • @AstelloAlbany
    @AstelloAlbany Месяц назад +1

    Good job! At 27:56, you put the core in and then open the valve, but the micron gauge is already removed. Is that correct? I believe that when you remove the micron gauge, a significant amount of air enters the system. Even if that’s not the case when you remove the micron gauge, the pressure in the system is negative, allowing air to enter through the core. We always open open valve first, then put core in, and remove micron gage.

  • @SusanRnewyork
    @SusanRnewyork 2 месяца назад +1

    NOt gonna lie, i doubted u at first but i stuck with the video! Great job bro!

  • @ericabercrombie6780
    @ericabercrombie6780 20 дней назад +2

    What about the temp change across the strainer? You think there was a blockage there as well?

  • @martinpinsonneault123
    @martinpinsonneault123 3 дня назад

    Merci!

  • @williamodle7715
    @williamodle7715 Год назад +4

    Really nice methodical, refrigerant circuit isolation diagnostic

  • @WatchmanNz
    @WatchmanNz Месяц назад +2

    This is why you need tell your installers to prepipe to left and have the flare joints under the unit! Not in the damn wall…

  • @jpenn727
    @jpenn727 4 месяца назад +1

    Wow, great diagnostic skills. Thanks much for sharing with us.

  • @robd7365
    @robd7365 8 месяцев назад +6

    Nice find, and great troubleshooting. Was the evaporator freezing in cooling mode? And was the condenser constantly self-defrosting in heating mode? I have a unit that runs fine all winter in heating mode, but freezes up in cooling mode often in the summer

  • @skipcurtin8546
    @skipcurtin8546 26 дней назад

    Great skills my friend !! Thanks for the video! 👍👍👍

  • @michaelglasser6923
    @michaelglasser6923 Месяц назад

    Nice video. Did you also address the strainer temp drop?

  • @willardwilson6707
    @willardwilson6707 7 месяцев назад +5

    Good find. Great video

  • @AirExcel-rb2je
    @AirExcel-rb2je 5 месяцев назад +1

    Thats was a great find man!! Very good video

  • @Fastandpro
    @Fastandpro 12 дней назад

    That was a blockage for a plumber I reckon. Nice job finding it.

  • @denuslevine210
    @denuslevine210 5 месяцев назад

    Interesting didnt know their woz a strainer in
    indoor liquid line flare section
    Youve a good understanding 😀

  • @michaelglasser6923
    @michaelglasser6923 Месяц назад

    Nice job. Was that a 1 to 1 setup, or was there a branch box?

  • @chrissipple1018
    @chrissipple1018 6 месяцев назад

    The bad thing about new equipment is the inverters. NASA started using them in 1960s for the project Mercury and they still can get them right. Good video

  • @JuanMorales-qn4tz
    @JuanMorales-qn4tz 7 месяцев назад +3

    Great video. Awesome job

  • @alexmontoya7258
    @alexmontoya7258 Месяц назад

    that was a good diagnostics

  • @aarongray503
    @aarongray503 6 месяцев назад +1

    Where did you get those meter lead tips from? I got the sc440 and lost one of mine.

  • @skipsaunders5974
    @skipsaunders5974 7 месяцев назад +1

    excellent video .... wish you were in my neighborhood ... :-) (Knoxville, TN)

  • @bmobley1
    @bmobley1 5 месяцев назад

    Whats the model of the fieldpiece bluetooth thermo couples your using?

  • @robertolopez8146
    @robertolopez8146 6 месяцев назад +1

    What kind of app you using with the felpice

  • @paulbryant68
    @paulbryant68 2 месяца назад

    nice find!!! very nice…

  • @mikestevenson1819
    @mikestevenson1819 Год назад

    Good find

  • @scoobtoober2975
    @scoobtoober2975 5 месяцев назад

    aciq startup quick list to retorque flares when first using heat pump mode. once hot.

  • @alexholland7102
    @alexholland7102 6 месяцев назад +1

    Good video, but we do not see you FIX the restriction that drops the inside unit temp from -7F to 40F. Was cleaning the sand the only thing you did to fix 1) the temp difference on the strainer 2) the low temp (-7F, then 40F) on the inside unit?
    I know nothing about AC, so I may have missed it. Thank you!

    • @WaffleStaffel
      @WaffleStaffel 6 месяцев назад +1

      Yes, it was the sand packed hard which was restricting the flow, acting as a metering device, causing the refrigerant to flash at the union, resulting in the temperature differential. An extremely sloppy install, allowing the uncapped line set to dig into the ground. It looks as though it was recirculating for a long time to make such an impacted obstruction, but it only traveled through the line and the 'evaporator', as there's a filter in the outside unit to protect the compressor. There must be even more sand in the screen or accumulator.

    • @HVACTechKnowledgy
      @HVACTechKnowledgy  6 месяцев назад +1

      Thanks! Yes, cleaning the sand was the only thing causing the restriction

  • @hakimsarif5191
    @hakimsarif5191 Месяц назад

    I have a Mitshubishi 24k btu multi split. When i turned it on. Only the bottom part of the evaporator coil is cold and the top part takes ages to cool down. Could this be due to a restriction?

  • @mariusm3595
    @mariusm3595 5 месяцев назад

    Awesome video !

  • @TheLastBoyScout1976
    @TheLastBoyScout1976 6 месяцев назад +1

    Why don’t you torque your flares to spec?

    • @denuslevine210
      @denuslevine210 5 месяцев назад

      That & little bit more
      Only found 1/4inch flare nuts can crack

  • @ekie85
    @ekie85 7 месяцев назад

    That was a great search 💪🏽🤝🏼

  • @rickross7796
    @rickross7796 7 месяцев назад +6

    The installer should not have put the flares in the wall they could have come in with their linesets from the bottom left of the unit for access

    • @Jason-wc3fh
      @Jason-wc3fh 6 месяцев назад +1

      No. Can't comment on this particular Mitsubishi, but the vast majority of them give you roughly 18" of either brazed/metric style flares on their equipment that we don't use to adapt to our standard fittings. Their copper lines are always an off-size in millimeters that we don't typically use. It is stupid when the fittings are going to be left in a finished wall. Only when it runs out on exterior wall does it allow for proper servicing.

  • @hernanjoseprietoherrera4839
    @hernanjoseprietoherrera4839 3 месяца назад

    Thanks

  • @christopherprince3332
    @christopherprince3332 5 месяцев назад

    So at 4:10 you mention you have 31 psi on low side and 56 on high side. Not so. Those are temperatures, specifically saturation temperatures hence the degree symbol along with and F just below the number. The psi reading you refer to is below your sat temps.

    • @HVACTechKnowledgy
      @HVACTechKnowledgy  5 месяцев назад

      Good catch yeah just misspoke and probably forgot to correct it in post appreciate the heads up and thanks for watching!

  • @crowderglen
    @crowderglen 5 месяцев назад

    Great video!

  • @juanrobles9511
    @juanrobles9511 8 месяцев назад

    Very informative video , thank you 🙏

  • @VincentCiani
    @VincentCiani 8 месяцев назад

    Awesome job!!!!

  • @gregorygalati3435
    @gregorygalati3435 3 месяца назад

    If my log gets into the stream even when using little, gets into strainers

  • @Daniel-vd9yb
    @Daniel-vd9yb 11 месяцев назад +2

    Bro where’s your gloves ! Shout out from Naperville good find

    • @HVACTechKnowledgy
      @HVACTechKnowledgy  11 месяцев назад +1

      I know sometimes I just neglect to wear them I definitely need to do better LOL

  • @andyreyes6464
    @andyreyes6464 6 месяцев назад

    what is the name of those small leads ?

  • @juanlanda2561
    @juanlanda2561 7 месяцев назад

    Tough find!

  • @Jason-wc3fh
    @Jason-wc3fh 6 месяцев назад +1

    Impressive troubleshooting skills. I dread coming across these, but they're becoming a lot more common. Your thumb gives me the creeps with how far back your joint allows it to bend. Aside from your creepy thumb, this is good stuff here. I would assume install error with guys not sealing off their linesets.

  • @squiglyace7346
    @squiglyace7346 6 месяцев назад +1

    I’m trying to be like you

  • @eastcoast186
    @eastcoast186 11 месяцев назад

    👍👍👍thanks for video

  • @mountainklima5602
    @mountainklima5602 6 месяцев назад

    why wood some one put those flares inside a dry wall , Better to weld them

  • @jbouchard667
    @jbouchard667 4 месяца назад

    You had 100 psi on your low side and 161 on hi side. Not 31 psi and 56 like you said in video.

    • @HVACTechKnowledgy
      @HVACTechKnowledgy  4 месяца назад

      yes sir, my bad I meant to say saturation temps on the video. thanks for the heads up

  • @scoobtoober2975
    @scoobtoober2975 5 месяцев назад

    Don't dip the lines in mud, yikes i worry about where that stuff has gone.

  • @chrisguillen1495
    @chrisguillen1495 Год назад

    I thought Mitsu didn’t want us to ever hook up gauges anymore.