എങ്ങനെ എളുപ്പത്തിൽ എർത്തിങ് ടെസ്റ്റ് ചെയ്യാം | How to Check Earthing Proper or Not in Malayalam
HTML-код
- Опубликовано: 21 апр 2020
- എങ്ങനെ എളുപ്പത്തിൽ എർത്തിങ് ടെസ്റ്റ് ചെയ്യാം | How to Check Earthing Proper or Not in Malayalam
Hi,
Welcome to TechCorner Malayalam.
What is PLC - • What is PLC|എന്താണ് PLC
What is HMI - • Video
എന്താണ് VFD - • What is VFD in Malayal...
PLC Programming വീട്ടിലിരുന്ന് സ്വന്തമായി പഠിക്കാം - • PLC Programming Tutori...
SCADA vs HMI - • SCADA vs HMI | Differe...
Siemens TIA Portal PLC and HMI Programming Tutorial in Malayalam - • Siemens TIA Portal PLC...
What is Earthing and its Importance - • What is Earthing and i...
Difference between Earthing and Grounding - • Difference between Ear...
എന്താണ് ന്യൂട്രൽ - • Neutral | എന്താണ് ന്യൂ...
What is MCB in Malayalam - • What is MCB in Malayal...
How MCB works - • How MCB works|എങ്ങനെയാ...
എന്തിനാണ് സബ്സ്റ്റേഷനുകളിൽ ഗ്രേവൽസ് വിതറിയിരിക്കുന്നത് - • Why Gravels are used i...
Dampers and Insulators - • Dampers and Insulators...
Types of Insulators - • Insulators | Types of ...
എന്താണ് Relay - • What is Relay in Malay...
What is an Electrical Control Panel - • What is an Electrical ...
How to Design an Electrical Control Panel - • What is an Electrical ...
What is MPCB - • What is MPCB in Malaya...
How MPCB works - • How MPCB works|Inside ...
Difference between ELCB and RCCB - • Difference between ELC...
What is Contactor - • What is Contactor|എന്ത...
Follow us or Contact us on -
Fb Link : / techcornerm
Insta Link : / techcorner_malayalam
Please subscribe and support if you like our channel.
#CheckEarthing
#100thT_Video
#BasicElectricals Наука
നമ്മുടെ പുതിയ ചാനൽ ആണ് ഒന്ന് subscribe ചെയ്യണേ ruclips.net/video/CUcSIz9rsv8/видео.html
CFL ഉപയോഗിച്ച് ടെസ്റ്റ് ചെയ്താൽ brightness മനസ്സിലാക്കാൻ ബുദ്ധിമുട്ടാണ്... ബൾബാണ് നല്ലത്...
Correct...
Yes
LED/CFL bulbs, LED tubes low voltage lum bright aayi kathuum..
100 watts filament bulb aanu test cheyyan nallathu.. voltage kuranjal bulb dim aayirikkum..
Phase ലും Earth ലും ബൾബ് കത്തിച്ചു വമ്പിട്ട് അതു തമ്മിൽ Voltage നോക്കിയാൽ കൃത്യമായി എർത്തിങ് എത്ര ശക്തമാണെന്ന് പറയാനൊക്കും. Bulb watage കൂടുന്നതിനു ആനുപാതികമായി Voltage ൽ കുറവ് കണ്ടേക്കാം.
Correct 👍
RCCB എന്നാൽ Recidual Current circuit breaker. ഫേസ് ലൈനും നൂട്രൽ ലൈനും ഇതിൽ കൂടി പാസ് ചെയ്തതിനു ശേഷമാണ് വീട്ടിലെ എല്ലാ സർക്യൂട്ട്കളിലേക്കും പോകുന്നത്.. RCCB നോക്കുന്നത് ഫേസ് ലൈനിൽ കൂടി ഉള്ളിലേക്ക് പോയ അത്രയും current നൂട്രൽ ലൈനിൽ കൂടി തിരിച്ചു വരുന്നുണ്ടോ എന്നാണ്.. അകത്തേക്ക് പോയ അത്രയും കറൻ്റ് return ആകാതിരുന്നാൽ അകത്തെവിടെയോ current leakage to earth ഉണ്ടെന്നാണ്. ഇങ്ങനെ നഷ്ടപ്പെടുന്ന കറൻ്റിനെ residual current എന്നു വിളിക്കുന്നു. ഈ light ഉപയോഗിച്ചുള്ള ടെസ്റ്റിംഗ് നടക്കുമ്പോൾ ഫേസ് ലൈനിൽ കൂടി വന്ന കറൻ്റ് നൂട്രൽ ലൈനിന് പകരം ഏർത്ത് ലൈനിൽ കൂടി return aayi ഭൂമിയിലേക്ക് പോകുന്നു.. അപ്പോൾ RCCB ഫേസ് ലൈനിലെയും നൂട്രൽ ലൈനിലെയും കറൻ്റിൽ വ്യത്യാസം കാണുന്നതിനാൽ circuit trip ചെയ്യുന്നു.. സാധാരണയായി വളരെ ചെറിയ വ്യത്യാസം ( 0.03Ampere) മതി ഇത് ട്രിപ്പ് ആകാൻ... RCCB യുടെ ഉപയോഗം ആളുകളെ ഇലക്ട്രിക് ഷോക്ക് അടിച്ചു മരിക്കുന്നതിൽ നിന്നും രക്ഷിക്കുന്നു എന്നതാണ്.. കാരണം നമ്മൾ അറിയാതെ ഫേസിൽ തൊട്ടാൽ നമ്മളുടെ ശരീരത്തിൽ കടക്കുന്ന current ഭൂമിയിലേക്ക് പോകും... ഇത് RCCB തിരിച്ചറിഞ്ഞു ട്രിപ്പ് ആകും.
Good explanation
well expalined
.✌
നന്നായി വിവരിച്ചു thaks ബ്രോ
ബ്രോ sun diruct ന്റെ adaptor ൽ നിന്നും erth അടിച്ചു നന്നായി കിട്ടി 😂 adaptor complaint ആയിരുന്നു എന്നിട്ട് ഡ്രിപ് ആയില്ല erth ചെക്ക് ചെയുമ്പോൾ ഡ്രിപ് ആകുന്നുണ്ട് എന്താണ് കാരണം എന്ന് പറയാമോ
👏👏
ELCB ഉള്ള സ്ഥലത്തു Lamb use ചെയ്യാൻ പറ്റില്ലല്ലോ?
ചെക്കിങ്ങിനി ഏറ്റവും നല്ലത് ഫിലമെന്റ് ബൾബാണ്
You are a brilliant tutor.You explained it very simple way. Thanks a lot.
ഈ എൽ സി ബി ഉള്ള ഉള്ള വീട്ടിൽ ഇതുപോലെ ചെക്ക് ചെയ്യാൻ പറ്റില്ല ബ്രേക്കർ ട്രിപ്പ് ചെയ്യും
Ys
Meeter us
S
അങ്ങനെ ട്രിപ്പ് ആയാൽ proper എർത്താണ് 👍
Bro treep ayekil propper erth aaa
Fantastic......
ഇതു പോലെ Electrical videos ഇടണം .......നന്നായിട്ടുണ്ട് ....... നല്ല presentation ....... GoD's Blessings.......
Excellent demonstration thank you. Please demonstrate how to use the Multimeter. Regards Joseph
Appo socketl earth connect cheythitilaa nkil.. Engane aairikum multimeter reading kanikuka...?( Phase to earth and neutral to earth reading edthal). Pinneh Oru equipment nte (iron box)earth (metal partl ninula) correct aai work cheyunindo enna arian nthu cheyum?Mutilmeter vech neutralm erthnum across voltage nokumbol 0 alee varendath? Nthu kondan 1 varunath?
Super. വളരെ നന്നായി മനസിലായി.
Neutral n earth voltage chk cheyumpol 2.5 volt kanikunnu.. and neutral n earth continuty chk cheyumpol.. avide continuty kanikunnu..
. (single phase il energy meter il tv on cheyumpol mathram "Earth" avide red led theliyunnu.. )
Evideyaanu check cheyendathu.. earthing proper aanu..
Ellam MCB through aanu.. ELCB Connect cheythittilla..
Lamb test ok. It shows wiring is earthed n not earth resistance. If earthing is proper nutral to earth voltage varies depending on voltage drop in the nutral from transformer as the nutral is earthed in the transformer only.
Super bro... from base itself u explained .. its helpfull
Thank you 😊
CFL use cheythal voltage manassil aavilla .ordinary bulb ( incandacent bulb)use cheythal nannavum .
100 w ന്റെ ഫിലമെൻറ് ബൾബാണ് Earth ചെക്ക് ചെയ്യാൻ എളുപ്പം. CFL ലൊLED ലൊ മനസ്സിലാകില്ല.
ningaludey kazhivineyum arivineyum 100% manikkunnu,ente oru doubt mathramanu,electrician alla,pls reply
Very informative n useful 👍👍👍
Neutral fault 12v കാണിക്കുന്നു.Bulb test ൽ OK Neutral fault കുറയ്ക്കാൻ ഒരു മാർഗ്ഗം പറയാമോ?
Power socketum,cable socketum oru boardil sett cheita aa midukkanaya wiremane guru akkam.🙏🙏🙏🙏
Use normal bulb 60 watt currect brightness kittum cfL not ok voltage kurajalum cfl and led prakashikkum
Cfl ,led bulbil bright arrliyoola
Filement bulb venam
Dear.
Firstly u want to have study the electrical theory. It is not possible to check like this way.
In both the elcb/rccb trip if the earth is proper.
Sir, is there is any chance of earth leakage between isolater and main switchboard....I have the same problem which mentioned below..... Even I use only 2 fans for night and 1 fan for day the daily consumption was 5 units.....pls reply
Rccb undenkil earth leakage undel detect cheyyum... pine ee parenje fan load thanne almost 2-3 unit consumption undu... appol vere cheriya enthalum okke device use kanille
ELCB ഉള്ളസ്ഥലത് ബൾബ് ഉപയോഗിച്ച് ചെക്കുചെയ്യാൻ സോക്കറ്റിൽ പറ്റില്ല മൾട്ടി മീറ്റർ മാത്രമേ പറ്റുകയുള്ളു അതുകൂടി വിശദമായി പറയണം
താങ്കളുടെ അഭിപ്രായം ശരിയാണ്. ELCB കണക്ട് ചെയ്ത ഭാഗത്തിനു ശേഷമുള്ള എവിടെ ചെക്ക് ചെയ്താലും ട്രിപ്പ് ആകും
Earthing ഉണ്ടെന്നു മനസ്സിലാക്കാം എന്നു മാത്രം. മൾട്ടിമീറ്ററിൽ Resistence വാല്യു നോക്കുകയാണ് ELCB/RCCB വച്ച സ്ഥലത്ത് നല്ലത്
വളരെ വ്യക്തമായ രീതിയിൽ മനസ്സിലാക്കിത്തരുന്ന ഒരു ക്ലാസ്സ് ആയിരുന്നു എൽഇഡി ക്ക് പകരം ബൾബ് ഉപയോഗിക്കാമായിരുന്നു
Thank you .Good information
Welcome 🙏
bro ente veettil. neutrel to earth 4 volt kaanikkunnundu athu kuzhapamano.? bakkiyoke correct aanu
Good info, thanks . Elcb trip aavo multimeter use cheyyumbol
No
Earthing checkucheyyan 60 watts bulb use cheyuka. CFL Led bulb Do not use pls
Phase and earth connect cheyyumbol bulb kathunnilla. Mathramalla elcb trip aayi. Why this is happening???
Bro 3 pahse line aanu db il 3 phase varunnh 4 pole mcb nu split aayi 3 single phase aakunnh oro phase rccb aayi connected aanu Ac supply off akkiyittu on akkiyal 3 phase il ethengilun rccb trip aakum rccb on akkiyal normally work aakum.current poya veedum sams avastha...3 phse ile rccb maari maari ethengilun oke trip aakunnh
ഏർത്തും ഫെയിസും കൊടുക്കുമ്പോൾ e l c b tripp ആകേണ്ടതല്ലേ
Electrician നിർബന്ധമായും കണ്ടിരിക്കേണ്ട video ആണ് ഇത്... എല്ലാരും കാണണം... എനിക്ക് വളരെ ഉപകാരപ്പെട്ടു... Thankyou sir.
Welcome 🙏
എന്റെ വീട്ടിൽ Nutral to Earth voltage വ്യത്യസ്ത സമയങ്ങളിൽ വ്യത്യസ്ത വോൾട്ടേജാണ് കാണിക്കുന്നത് ചിലപ്പോൾ അത് 4 to 5 volt കാണിക്കാറുണ്ട് മറ്റു സമയങ്ങളിൽ ചെക്കുചെയ്താൽ അത് 12v to 15v കാണിക്കാറുണ്ട് എന്തുകൊണ്ടാണ് ഇങ്ങനെ സംഭവിക്കുന്നത് ഇത് കൊണ്ടെന്തെങ്കിലും problems ഉണ്ടോ? ഉണ്ടെങ്കിൽ ഇത് എങ്ങനെ പരിഹരിക്കാം ഇത് Earth proper അല്ലാത്തത് കൊണ്ടാണോ സംഭവിക്കുന്നത് ?
Multimeter upayoogichu test cheyyumpool phasil multimeterinte black wire koduthaal valla kuzappavum undoo
M
Sir, In my house earth to neutral showing 4 volt.also phase and earth showing more volt than phase and neutral.what may be the complaint?
4 volt is not thatmuch high,it can be even due to load unbalancing
എർത്ത് ലീക്കേജ് സംബന്ധമായി ചെക്ക് ചെയ്യാൻ ഏറ്റം നല്ലത് സാധാരണയുള്ള ബൾബാണ് നല്ലത്.
കൊള്ളാം പക്ഷെ ആദ്യം rccb എങ്ങനെ bypass ചെയ്യണം എന്ന് കാണിക്കണം ആയിരുന്നു
Bro, ship ile generator nte neutral insulated aanu. Ath enthanu ennu padich Oru video make cheyth elarkum paranj koduthal aalukalk athoru puthiya arivaayirikum oppam thaankalkum . Just a suggestion from a viewer.😊😊😊😊. Your doing an awesome job. Keep it up.
Thank you so much..thanks for your suggestion..will make a video
Hi Tech corner.. I needed an advise from you. Electricity bill in my home is coming upto 2500-5000 rupess in last 3 years even without using high load equipment like AC, heater, invertor etc. We have tried almost everything to find out the high load consumption like,
1. Checked for current leak in all JBs, switch boards
2. Checked for earth leaks
3. Checked the kseb meter more than 5 Times with parallel one
4. Changed the old fridge to new one
5. Changed the whole wiring of the House
6. Changed few mcbs which were faulty
All of these done and still no change in the meter reading, we have a consumption of 7-8 units per day as per the meter.
Please guide if you have any other suggestions to mitigate this issue
Hi, Issue seems to be interesting.Few of our observations in your query is. Normally electricity consumption depends on 1.Total load 2.Age of Appliances 3.Any wiring issues. But i hope you have cross checked all the same. So in additionally i would suggest to check your total load and updated load in KSEB. If the updated load is much lesser than the current load,Then there is a chance of penalty every month. Also please ensure that no else is connected to your supply without permission. As its domestic load. chance of power factor issue is very low but still suggest to check your power factor too.
@@TechCornerMalayalamThank you for replying.
yes we have updated the connected load just recently too. It was actually higer(not in actual usage) than the previous load. And no other connections are taken from ours.
Ok let us discuss this issue internally, Will let you know If we find out any other possibilities.
@@TechCornerMalayalam Please.
Waiting for the same.
@@TechCornerMalayalam please send ur mob no
N + E =1 Acv നു പകരം 30 VAC വന്നാൽ earth correct ചെയ്യാൻ എന്ത് ചെയ്യണം ....?
ELCB OR RCCB connected allengil ok
connected aanengil test cheyyan kazhiyilla ..........
Phase ലും Earth ലും ബൾബ് കത്തിച്ചു വമ്പിട്ട് അതു തമ്മിൽ Voltage നോക്കിയാൽ കൃത്യമായി എർത്തിങ് എത്ര ശക്തമാണെന്ന് പറയാനൊക്കും. Bulb watage കൂടുന്നതിനു ആനുപാതികമായി Voltage ൽ കുറവ് കണ്ടേക്കാം.
ഇലക്ട്റിക്കൽ ജോലിക്ക് ഉള്ള ഇന്റർവ്യൂ ന് പൊതുവെ ചോദിക്കുന്ന ചോദ്യങ്ങൾ എന്തൊക്കെയാണെന്നും അതിന്റെ ഉത്തരങ്ങളും ഉൾകൊള്ളിച്ചുകൊണ്ട് ഒരു വീഡിയോ ചെയ്യ്മോ ചേട്ടാ
Cheyyam udene ...ee oru topic note cheythit undu
Experience അത് മാത്രമേ ചോദ്യമുള്ളൂ,..
BULB ഉം CFL ഒഴികെ മറ്റു Load കൾ (TV MIXI FAN)
phas to Erth ൽ work ചെയ്യുമോ ?
ഇല്ലെങ്കിൽ അത് എന്ത് കൊണ്ടാണ് ?
Erth to phas ൽ BULB കൂടുതൽ നേരം work ചെയ്താൽ എന്തെങ്കിലും കുഴപ്പമുണ്ടോ ?
Earth orikalum oru normal return path alla...athu safetik faulty conditionil maatrem pokan olla path aanu... earthil koduthal work okke cheyum pakhse pine atheen oru safety undakilla, chillepol nammal appliances bodyil thottal polum namuk shock adikanum chance undu
ruclips.net/video/aCOOkoftc3o/видео.html
Thanks....Excellent explanation😁
Neutral voltage kooduthal anenkil engine solv cheyyam chek cheythappol 7.8 volt und neutral to earth. earthing nalla mazhayathu anu
Kseb load unbalanced aakam...value change aakunundo ennu nokku..vaiketheke neutral earth voltage, ravlethe nokkuka... change undel kseb issue aakam
JIDESH
ELCB or RCCB connected loadil check cheyyan phase& earth atho neutral& earthano?
Difference between ELCB and RCCB in Malayalam| ELCB ,RCCB തമ്മിലുള്ള വ്യത്യാസം
ruclips.net/video/L8BqE6D0i20/видео.html
Megger use cheyth direct socket vazhi nokkaan pattumo
Informative .... thank you....
Welcome 🙏
rccb fit cheyyatha instalation ano? anenkil mathrame lamp testing nadakkullu.koodathey earth um phase=256v,phase um nutral =256v ,wiring test cheyyanam earth um nutral um link undo?
Earth ഉം nutral ഉം തമ്മിൽ direct ആയി ഒരു ലിങ്കും ഇല്ല പക്ഷേ ചില സമയത്തു earth nutral ആയി prevathikkam
N and F 250v
E and F 250v
E and N 0 v .മൾട്ടി മീറ്ററിൽ ചെക്ക് ചെയ്തു.കുഴപ്പമുണ്ടോ
Neuter earth connect ചെയുമ്പോൾ 14 V value കിട്ടുന്നുണ്ട് വീട്ടിൽ പ്രോബ്ലം ആണോ
നല്ല ഒരു അറിവ് പകർന്ന് തന്നതിൽ നന്ദി
Thank you 😊
CFL & LED ബൾബ് ഉപയോഗിക്കു മ്പോൾ വെട്ടത്തിൽ ഉണ്ടാകുന്ന നേരിയ വ്യത്യാസം അറിയില്ല ഫിലമെന്റ ബൾബ് ആണ് ചെക്ക് ചെയ്യാൻ ഉപയോഗിക്കാറ്
Normely voltage is 240 v then how you can 256 v please explain
Voltage orikalum constant alello athu veraam itremokke
Rccb, Active ആണെങ്കിൽ ലാംബ് കത്തിക്കൽ ചെക്കിംങ്ങ് നടക്കില്ല. Rccb ട്രിപ് ആകും.
Athe
Yes
Yes
Parihaaram
Athenkne rccb drip aakum ??
elcb elllathe vedu annale ok allale trip akumm/ felement lamp annnuu super
N-E value 059 multimeter ill kanikunne so earth complaint allee
കിടു. ഉപകാരപ്രദം.
Thank you 😊
CFL വച്ച് എർത്ത് ചെക്ക് ചെയ്യുന്നത് ആദ്യമായി കാണുകയാണ് തങ്കളുടെ അറിവിന്റെ പരമാവധിയെ ഞാൻ അഭിനന്ദിക്കുന്നു
പരമാവധിയോ 😂😂
I think instead of cfl incandescent bulbs will be better
Then only we can find the difference in brightness
Bro 256 volt kaanichal athu lightinum mattulla equpmentsnum enthegilum problum ondo oruvitham ella led lightinum maximam 240v.250 volt aanu parayunathu
Ei kuyepmla Atrem fluctuations okke namude device pattum
Edengilum oru sokkattil chek cheidalmadyo?
Earth പോയിന് എന്ന് എങ്ങനെയാണ് മനസ്സിലാക്കാൻ means കറന്റ് ബില്ല കൂടുതലാണ് അങ്ങനെ ആകുമ്പോൾ earth faise vai പോകുന്നുണ്ടങ്കിൽ എങ്ങനെ ചെക്ക് ചെയ്യും
ph and neutral -210v
ph and earth - 65v
neutral and rarth -60v coming.my neighbour's house also the same problem. what is the reason
May be earthing will not be proper. Or there will be any earth leakage
Erthleakege
Rccb undenkl phase earth connect chythu on akeya appo thanne trip akullo bro
Orikkalum ore pole voltage kittilla. Cfl nu pakaram bulb use cheythu nokk voltage alpam kuravayi aayirikkum kathuka apol manasilakkam voltage difference
Angane theerthum parayan sadhikilla ,cfl m voltage sensitive aanu pakshe athil drive ullethukond capacitor circuit ullethukond ath normal bulb pole cheriya difference ino peten oru fluctuationo undakunilla ennathan sathyam... ivde pine voltage difference illa ennu multimeter il kanikunundello... pine sheriyan lamp test in sadha bulb aanu koodthl apt but still we can do with cfl too no issue.
House wiaringle erthinu. Idenda wiare size etrayaa
Lamb vache test cheyupol filamet bulb alle use cheyende, apol alle variation thiriyu?
അതേ ഫിലമെന്റ് ബൾബ് ആണെങ്കിൽ മാത്രമേ ശരിക്കും ഉള്ള പ്രകാശ വ്യത്യാസം അറിയാൻ പറ്റുള്ളൂ.
അതു പോലെ തന്നെ ഏർതിങ്ങിനുപയോഗിക്കുന്ന പൈപിന്റെ ഖനവും നീളവും വയറിങ്ങും ഏർതിങ്ങും ആയി കനക്ട് ചെയ്യുന്ന കോപ്പറിന്റെ ഖനവും ഇതിനു അനു ബന്ധ ഘടകങ്ങൾ ആണ്
Earth tester use cheyyunna method onnu kanikkamo?
Supply ulla orotta color le ull 3 cable (long) enthengilum karenethal cutt ayi ennirikettea
ithil ninne Erth cable eadhane enne
Identifi cheyyan pattumoo?
(Join cheyyan veandi)
Continuity test cheyth nokki kandu pidikaalo
ഒരു പോയിന്റിൽ ചെക്ക് ചെയ്താൽ ആ വീട്ടിലെ എർത് എല്ലാം പ്രോപ്പർ ആണോ അല്ലയോ എന്ന് മനസിലാക്കാൻ കഴിയുമോ
Oru wiring pipe il ninnum 3 linukal varunnu.. same colour, same size... athil phase tester upayogich manasilakkaam.. neutralum earthum engane verthirich manasilakkaaam?? Phase to neutralum phase to earth um light kathumallo...
Neutral veruneth kseb een alle so ah verunne point vechu continuity nokku
Main swichle fuse ozhivaakkiyaal porey simple
@@nizambinzubair2393 manasilayillaa..
ഇപ്പം എല്ലായിടത്തും ഇ എൽ സ് ഇ ബി ഫിറ്റ് ചെയ്തിട്ടുള്ളതുകൊണ്ട് എർത്തും ന്യൂട്ടലും കുടികൊടുത്താൻ E L C B ട്രിപ്പായി പോകും
Bro I have a doubt , in your multi meter showing 256v , normally line volt is 240v or below. Plz clear me.
?
Bro fluorescent lampinekaalum nallath incadicent lamp ale check cheyan nallath
Athe
ന്യൂട്രലും ഫേസും തമ്മിൽ കാണിക്കുന്നതിനേക്കാൾ കൂടുതൽ വോൾട്ടേജ് ഫേസും എർത്തുമായി കാണിക്കുന്നു എന്തായിരിക്കും കാരണം
P to N-243. ; P to E 246
???🙄
നിങ്ങൾ ചെക്ക് ചൈതത് ഫൈസ് to ന്യൂട്ടർ ആണ് ചെക്ക് ചൈതത്
👍👍👍Good information
200w bulb anu earth test cheyyan
Thanku
Welcome
Rccb set cheyda veetil anengil idu check cheyyan pattila
ഇങ്ങിനെ ചെക്ക് ചെയ്യണമെങ്കിൽ ELCB connection വിച്ചേദിക്കേണ്ടിവരില്ലെ ?
my house i am getting 3.5 volt between nutral and earth
what is reson
same problem enikum undu
Earth leakage engane check cheyyam?
Cheyyunna timil elcb tripp ayal endangilum kuyappa mundo
D B. യിൽ. E. L. C. B. ഉണ്ട് എങ്കിൽ. എന്ത് ചെയ്യും അഴിച്ചു മാറ്റുമോ ഒന്നു കൂടി പഠിക്കുന്നത് നല്ലതാ
(1)bro...erth phase conetion ayal (elcb) rccb break akum.....
(2) maldimeeter 256 volt engane undayi.....no chance
Elcb rccb trip ആയിട്ടില്ല അതുകൊണ്ടാണ് ചെക്ക് ചെയ്യാൻ സാധിച്ചത്
Iyalk engine 256 volt kitti.kseb 220volt alle tharunnulloo. Reply venam
Single phase 230v.
Earth um nutral agana identified chyam
VDR വച്ചേ ഉണ്ടണ്ടാക്കുന്ന SPD നമുക്ക് വിശ്വസിക്കാമോ ഇതിൽ എന്തെങ്കിലും കുഴപ്പം ഉണ്ടോ
മറുപടി തരണേ
What is Surge Arrestor and Metal Oxide Varistors in Malayalam
ruclips.net/video/TtxUWLEVEp8/видео.html
മുൾട്ടിമീറ്റർ വെച്ചു Earth - Neutral ലൈനിൽ continuity ചെക്ക് ചെയ്താൽ continuity കാണിക്കുമോ ?
Ella
veetil karand chornnu povunnundo yenn yengine nokkam onnu parayumo
ന്യൂടലിലും എർത്തിലും ചെക്ക് ചെയ്യുമ്പോൾ 15 വോൾട്ട് കിട്ടുന്ന വെങ്കിൽ 2 തരത്തിലാണ് എന്ന് പറഞ്ഞു, 1 അൺ ബാലൻസ്ഡലോ സ്, 2 എർത്ത് ശരിയല്ല - എർത്ത് ശയി യല്ല എങ്കിൻ എങ്ങിനെയാണ് ന്യൂട്രലിൽ Vol tage കാണിക്കുന്നത്?
2, (N + E) ന്യൂട്രലിൽ വോൾട്ടേജ് കാണിച്ചാൽ N+ P വോൾട്ടേജ് കൂടുതൽ ഉണ്ടാവുമോ? അഥവാ ഒരു ഫേസ V 220 ആണെങ്കിൽ p+N 220 V ൽ കൂട്ടതൽ ആയിരിക്കുമോ?
1 . Sheri Alla ennu paranjal Avde Earth chythitilla enn maatram Alla artham, earth pit or Ningade earth value okke depend cheyam, low resistance path undakilla.
2 . Angane Illa...
Enthan earthing ennu video chythit und onn kandu noku
കര ണ്ട് ബിൽ കൂടുന്നു. എറത് തിന്റെ പ്രശനം വന്നൽ ഇഗിനെവരുമോ. മറുപടി പ്രേതീശിക്കുന്നു
Bro earh bhoomiyilekku alle bro poyirikkunnathu..pinne enganeyanu phase lun earth pinnilum bulb kodukkumbol kathunnathu..
Earthing enthan neutral enthan okke video undu channelil onnu kandu nokku appol concept manasilakum
If we are using first method, is there chance of elcb tripping?
Ya , It will trip.
@@TechCornerMalayalam അപ്പൊ ബ്രോ യുടെ വീട്ടിൽ RCCB ഇല്ലേ
വീടിന്റെ വയറിങ് ൽ എവിടെ എങ്കിലും കറന്റ് എർത് ആയി പോയി കറന്റ് ചാർജ് കൂടുന്നു അത് എങ്ങനെ ആണ് എന്ന് എങ്ങനെ അറിയാം
bro ടെസ്റ്റ് ലാംമ്പ് ഉപയോഗിച്ച് നമ്മൾ ഇങ്ങനെ എർത്ത് ടെസ്റ്റ് ചെയ്യുമ്പോൾ Rcc B കണക്ട് ചെയ്തിട്ടുള്ള സ്ഥലത്താണെങ്കിൽ RC CB ട്രിപ്പ് ആകുമല്ലോ അതും കൂടി ഒന്ന് സൂചിപ്പിക്കാമായിരുന്നു
👍 ..rccb olle oraal lamp test cheyende aavsym verunillelo athaan...still good suggestion.
Rccb undangil trip aakum ennukoodi parayamayirinnu karanam pala veedukalilum rccb unde