Me on a no cooling call in which I found the condenser fan motor running but the compressor not! I almost misdiagnosed!The system is low on refrigerant as well.
Instead of taking the top off. Just the common wire ( usually black) to each of the other legs of power for the compressor. If open, you’ll have no continuity on the common
Looks like its a 3 phase unit as i dont see a run capacitor for the compressor only the fan. What happened was the burnt wire caused it to single phase, and not allow the comoressor to start.
thanks for sharing your video CJ !!!! 😁😁u Fixed it !!!!🙌🙌bet the customer were glad to get Cooling !!!!
Good job
Instead of taking the top off. Just the common wire ( usually black) to each of the other legs of power for the compressor. If open, you’ll have no continuity on the common
💪🏿💪🏿💪🏿
Looks like its a 3 phase unit as i dont see a run capacitor for the compressor only the fan. What happened was the burnt wire caused it to single phase, and not allow the comoressor to start.
@@seangriffon6502 Thats correct it was single phasing.