Diagnosing Daikin U0 Error⎪2

Поделиться
HTML-код
  • Опубликовано: 8 сен 2024
  • HVACR⎪HVAC⎪REFRIGERATION⎪AIR CONDITIONING⎪AIR CONDITIONER VIDEOS
    In this video I attend a break down where the unit is displaying a U0 Fault Code and won't run. I found the Outdoor Printed Circuit Board to be faulty.

Комментарии • 44

  • @bradgoodale3249
    @bradgoodale3249 17 дней назад

    thats the best brand of megger and multi meters around in my opinion Mitch.

  • @liqfx982
    @liqfx982 Год назад +2

    Informative video mate. I’m Keen to see the board replacement if you film it when you go back

    • @maracservices
      @maracservices  Год назад +2

      Thanks mate, I’ll definitely record it but I’m not sure when because according to Daikin’s Global Data Bank there are no PCB’s available in Sydney. Which normally means none in Australia. Hopefully soon though.

  • @robalexander7348
    @robalexander7348 Год назад +1

    Nice vid Mitch, and good to see you on the job bright n early 08.10 👍 and luv the way that outdoor compressor is only mounted on loose bricks, also No 240v isolator 🙄

    • @maracservices
      @maracservices  Год назад

      Definitely wasn’t installed by me that’s for sure 😂

    • @robalexander7348
      @robalexander7348 Год назад

      @@maracservices Mate, it's sure not your work, we all now your quality work by now, maybe the owner would agree to wall mounting brackets being fitted as well 👍

  • @JPI-c6v
    @JPI-c6v Месяц назад

    Thank you for the video🙏🏼 I got a serious problem with my Daikin 3MXM52N2V1B. Changed Mainboard, Valves, all sensors gas,water, main and the system runs 50seconds fine, after that 2.50min stop. This goes on and on for about 10 hours. On the outdoor machine the bulbs 2+3 are blinking> start with defective compressor. Then the Onecta App says error H0. Would be really greatful for any tips recomendations what to check for 🙏🏼

  • @MentalLapse09
    @MentalLapse09 Год назад +3

    Yeah definitely agree that inverter air conditioning pcbs are fragile when it comes to storms/surges.
    I like to put surge diverters in my quotes as a recommended option.

    • @maracservices
      @maracservices  Год назад +1

      That’s a good idea. I’ll have to start doing the same thing!

  • @softroadingnewzealand5210
    @softroadingnewzealand5210 Год назад +1

    I need to ship you a proper LA Dodgers hat haha. Great video and learning a lot from your channel…

    • @maracservices
      @maracservices  Год назад

      Haha this hats the best mate. Been through a lot together!

  • @BERESHIDA2008
    @BERESHIDA2008 Год назад +1

    Great videos

  • @nguyenthechung
    @nguyenthechung Год назад

    Thanks for your's share...!

  • @rodneycooper5474
    @rodneycooper5474 Год назад +2

    Hey mate just wondering why all the resistance readings the same? For single phase shouldn’t the highest be between run and start, then start and common, then run and common?

    • @maracservices
      @maracservices  Год назад +1

      It’s because it’s a 3 phase DC Compressor mate.
      Good question though!

    • @BERESHIDA2008
      @BERESHIDA2008 Год назад

      In iverter motor it should read the same reading

  • @thomasmarchant4054
    @thomasmarchant4054 Год назад +2

    Had this error before turned out to be eev. System was pumping itself down into a vacuum.

    • @josephwhite373
      @josephwhite373 8 месяцев назад

      Was there frost on one side of eev

  • @FreedomInMindtv
    @FreedomInMindtv Год назад +1

    Nice one Rodney 🤙🏻

  • @marzgtp
    @marzgtp Год назад +1

    what is a U4 long beep? And what should I look for on my Daikin unit

    • @maracservices
      @maracservices  Год назад

      Communication error between indoor and outdoor unit. It could be a fault in the interconnect wiring but most likely a faulty PCB.

  • @olliebulldog951
    @olliebulldog951 Год назад +1

    Hi, have you ever had a u0 04 error?
    Daikin cant seem to figure it out and blaming airflow, however system was working fine for 3 years through many 40c days.
    Gas has been reclaimed and checked.
    Indoor coil thermistor replaced.

    • @maracservices
      @maracservices  Год назад +1

      If it’s not short on refrigerant and a technician has confirmed this. You need to test the low pressure transducer is actually working. It might think it’s low on refrigerant when it actually isn’t.

    • @bmiadmin5784
      @bmiadmin5784 8 месяцев назад +1

      Change brand next time mate, this brand is too much problem and gives you headaches....

  • @ClimateAdaptation
    @ClimateAdaptation Год назад +1

    If the fuses don't have continuity could you replace them to try and get the PCB working again?

    • @maracservices
      @maracservices  Год назад +1

      Yeah definitely however unfortunately in this case the fuses are fine and do have continuity. The issue is in the board.

    • @adrianvisintin1961
      @adrianvisintin1961 Год назад +1

      @@maracservices I love how air conditioning company’s don’t put replaceable fuses 😅 . Can I ask what props you use to test small components

    • @maracservices
      @maracservices  Год назад +1

      @@adrianvisintin1961 I know it’s so ridiculous hey.
      So my fluke meter came with prongs that I use 99% of the time but I found a really cheap no name multi meter laying around that had really sharp prongs. So basically I put the prongs in my bag to test plugs and what not. So to answer your question, I use no name Chinese leads for plugs and decent fluke leads for everything else haha.

  • @chiller-on
    @chiller-on Год назад +1

    Well, at least they put it on the stones, they could just put it on the ground😁

  • @nettoyageplusplus4947
    @nettoyageplusplus4947 4 месяца назад

    Comment vous avez testez la carte électronique ? Merci

  • @kcomfortsystemshvac7060
    @kcomfortsystemshvac7060 Год назад

    Nice video 👍 let’s say if you the unit it short the gas …what the best away to add r32 ? What type tecnic are you use it ? Thank you

    • @BERESHIDA2008
      @BERESHIDA2008 Год назад +2

      when ever posible with a scale by weight , the unit has a label indicating how much the unit takes

    • @maracservices
      @maracservices  Год назад

      Find the leak, fix the leak, evacuate the system and then weigh charge the gas back in 👍🏻

  • @Rayray_unicornplayz567
    @Rayray_unicornplayz567 Год назад +1

    Are you going to make a part 2 for it?

    • @maracservices
      @maracservices  Год назад

      I am however Daikin don’t have any of those PCB’s in stock so we are currently waiting unfortunately.

  • @myrah_adzy
    @myrah_adzy Год назад +1

    hi mate ever had an e5 error?

    • @maracservices
      @maracservices  Год назад

      Yeah mate that’s just an error code that comes up when the compressor gets to hot. Unfortunately there’s many things that could cause that so it’s impossible to tell you the exact problem without checking stuff but I can tell you that the compressor got too hot. Error comes on when the thermal overload is tripped which is located on top of compressor.

  • @alfredgomo7149
    @alfredgomo7149 5 дней назад

    Lucifer Australia

  • @tarekabuhijleh5638
    @tarekabuhijleh5638 6 месяцев назад

    U0 error REFRIGERANT SHORTAGE

    • @maracservices
      @maracservices  6 месяцев назад +1

      lol I know but it was not short on refrigerant. It had a faulty board

    • @tarekabuhijleh5638
      @tarekabuhijleh5638 6 месяцев назад

      @@maracservices ok