Big Thanks man! After measuring the RS485 voltage on the cable and on the inverter like you showed in the video, i have finaly succeeded to comunicate with the meter.
That's very helpful. However, I still can't find a reason why the PV production and self use are the same. The more sun the more self use it shows. When I turn the grid off left side comes back to normal. Also, the system doesn't allow any self use after the sunset. I noticed that on the 2nd screen meter power and current are zero for the grid and PV meters. How to solve that issue?
self-use is calculated incorrectly, and i requested it get removed from soliscloud as it was bringing in too many questions with regards to its inaccuracies (not possible to fix within SC).
Big Thanks man! After measuring the RS485 voltage on the cable and on the inverter like you showed in the video, i have finaly succeeded to comunicate with the meter.
That's very helpful. However, I still can't find a reason why the PV production and self use are the same. The more sun the more self use it shows. When I turn the grid off left side comes back to normal. Also, the system doesn't allow any self use after the sunset. I noticed that on the 2nd screen meter power and current are zero for the grid and PV meters. How to solve that issue?
I am having this exact issue, did you ever find a solution?
Is the energymeter correctly connected? Dubbelchek if the grid is connected to the grid side on the meter.
self-use is calculated incorrectly, and i requested it get removed from soliscloud as it was bringing in too many questions with regards to its inaccuracies (not possible to fix within SC).
"2nd screen" If you are running multiple Solis inverters, I believe you need an EPM1-5G (Export Power Module) to control them properly.
Hola algún manual para configurar inversor Solís con batería pylon? Gracias 🫂