The 3 Pillars of Daikin Service Checker Analysis

Поделиться
HTML-код
  • Опубликовано: 16 фев 2023
  • The 3 pillars of Daikin Service Checker Analysis. This video focuses on how to use the basics of refrigeration to troubleshoot Daikin Service Checker Data. Regardless the number, high or low, we can determine what is happening within the system and investigate at a magnified level as to the issue.
    This RUclips channel is not affiliated with Daikin or it’s entities. This is a channel focused on strictly customer product support of Daikin related products from other customers with similar experience with said products. Any content within this channel is solely the opinion of said person within the channel and should not be construed as “factory authorized” advice. Use the information within this channel at your own discretion. Always reference the appropriate Installation, Operation and Service Manual regarding the equipment you are currently working on.

Комментарии • 77

  • @relaxalate
    @relaxalate Год назад +3

    Really good video . DSH is a new item I’ve been running into on VRV and Daikin applied equipment. This really helped me bridge my knowledge gap , thank you!

  • @jeffendrulat3530
    @jeffendrulat3530 Год назад +1

    Thanks Roman..... Best 20 minutes that I spent today!

  • @epicone2449
    @epicone2449 Год назад +3

    More videos please. Good job 👍🏼
    I thought VRV 3 and VRV 4 have different ranges in permissible values

    • @RomanBaugh
      @RomanBaugh  7 месяцев назад

      No same ranges as they share similar compressors.

  • @christopherhughes2482
    @christopherhughes2482 Год назад +2

    Excellent video!

  • @sameerpremlall8124
    @sameerpremlall8124 Год назад +3

    Hi Roman, this is brilliant. Thank you for the content. I started service checker analysis about a year ago when I started working at Daikin and it took me a while to get the hang of it. I've gotten alot better at it but this video hear made so much sense. Thank you once again. Keep the videos coming 💪

    • @sameerpremlall8124
      @sameerpremlall8124 Год назад +2

      One other question, the parameters that you speak about is all in degrees Fahrenheit correct ?

    • @platinumhvacrtechnologies457
      @platinumhvacrtechnologies457 Год назад

      Yes in ⁰F

    • @po65231r
      @po65231r Год назад

      Is he not talking about k so should still be the same amount if deg c or F ??

    • @johngrayer7773
      @johngrayer7773 Год назад

      @@po65231r Hey mate, K doesn't relate to F at all, K is absolute C, so if a water chiller (for example) has 12C entering and 6C leaving water temperature, this could be expressed as 6K of duty (12-6). 0K = -273C (absolute zero), 273K = 0C, 373K = 100C and so on. Cheers.

  • @hvacgirlo
    @hvacgirlo Год назад +1

    Brilliant information Roman. Thanks so much

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC Год назад +1

    Outstanding video and explanation

  • @platinumhvacrtechnologies457
    @platinumhvacrtechnologies457 Год назад +1

    Roman this is great keep the videos coming especially on vrv

  • @ping_me1vp
    @ping_me1vp Год назад +1

    That's soo excellent thanks a million

  • @nguyennam880
    @nguyennam880 Год назад

    Looking forward to you sharing your knowledge related to data analysis checker. Thanks you.

  • @johnchiarello1375
    @johnchiarello1375 Год назад +1

    Great video

  • @joshuavaldez4094
    @joshuavaldez4094 Год назад +1

    Great info 👍 👌

  • @guuuuustaf
    @guuuuustaf 6 месяцев назад +1

    Great explanation!

    • @RomanBaugh
      @RomanBaugh  5 месяцев назад

      Glad it was helpful!

  • @omegma87
    @omegma87 Год назад +1

    Thank you.

  • @Didik-cq8wy
    @Didik-cq8wy Год назад +1

    Trimaksih bos

  • @prowesstv
    @prowesstv Год назад +2

    Bro got me locked in for the deep dive then only has two videos 😅😅

    • @RomanBaugh
      @RomanBaugh  7 месяцев назад +1

      The wait is over

  • @americanpatriot9942
    @americanpatriot9942 Год назад +1

    Can we use this same method with all vrfs systems? Thanks in advance also great info god bless!

  • @BleedingEdgeHVACR
    @BleedingEdgeHVACR Месяц назад

    Sorry I’m confused is discharge superheat calculated by taking Discharge line temp-Discharge sat temp or Discharge line temp-Liquid sat temp?

  • @HVACR_VINYLS
    @HVACR_VINYLS Год назад +4

    Hey Roman. When I’m using my service checker on a VRV 4. I have noticed the eev pulses have 2 sets of data. Eg it has upper heat exchanger eev pulses, and then upper heat exchanger eev US pulse. What does the US dictate? I don’t use it in my diagnosis, I’m just curious to what it refers too.

    • @RomanBaugh
      @RomanBaugh  Год назад +1

      Yes there are two different sets, however do not us the (US) valve pulses as they are not for our market and will be misleading.

    • @HVACR_VINYLS
      @HVACR_VINYLS Год назад

      @Roman Baugh thanks legend. Appreciate it

  • @alanwang2900
    @alanwang2900 Год назад +1

    Great video! Thanks for sharing.
    Are these numbers different when unit in heating mode? I always see outdoor coil iced up after the main eev, and from service checker, it shows the valve 3000 pls

    • @RomanBaugh
      @RomanBaugh  Год назад

      The measurements discussed in this video are universal between all modes, however where we are measuring these temperatures changes. Measuring subcooling in cooling mode is using different temperature measurement locations than in heat mode.

    • @alanwang2900
      @alanwang2900 Год назад

      @@RomanBaugh thanks, hope you could do a video the troubleshooting when unit is in heating mode. 🙏

  • @user-wz6fw5sm7f
    @user-wz6fw5sm7f 10 месяцев назад +1

    Hi Roman, great video could you advise of these figures you refer to in deg C i.e. DSH range (27 to72), SSH range (3.6 to 32) & LSC range (11)

    • @RomanBaugh
      @RomanBaugh  7 месяцев назад

      Fahrenheit my friend

  • @shirvonseemungal7719
    @shirvonseemungal7719 18 дней назад

    How do we measure subcool on a vrv

  • @DaneSetser-nn9xc
    @DaneSetser-nn9xc 7 месяцев назад

    I’ve got a total of 9 systems of 4X heat recovery units. We have had multiple issues and lost compressors. Your video made me dive deep into these systems. One system in particular is running a high DSH 90-100. SSH is within range no higher that 32 sometimes drops less in five. Subcool is within range. I did an oil differential across the suction line and was getting 7F then jumped up to almost 40F. Do you have any more info. Also where did you get the 30 modes local Daikin rep doesn’t have it.

    • @RomanBaugh
      @RomanBaugh  6 месяцев назад

      Sounds like oil traps within the building. High DSH levels with normal range SSH and Subcooling means your compressors are low on oil. Sounds like piping errors or discrepancies.
      Meaning there are piping rules broken causing oil to become trapped in the system.
      Your local Daikin Rep will not have that list, as I translated it from Japanese. Daikin Japan is the only one with the list prior to now.

    • @DaneSetser-nn9xc
      @DaneSetser-nn9xc 6 месяцев назад

      Thank you I’ll start looking at the piping.

  • @mallkomoha6823
    @mallkomoha6823 Месяц назад

    Can rebroadcast the video in metric please?? I mean in degree Celsius.

  • @jorgevalladares179
    @jorgevalladares179 2 месяца назад

    Are the examples shown, reflect a system running on heat?

    • @RomanBaugh
      @RomanBaugh  2 месяца назад

      Heat, Cooling, heat recovery it’s all relevant as long as you know the correct locations of where to measure these temperatures.

  • @garypoplin4599
    @garypoplin4599 3 месяца назад

    1:34 - Where do you put your probes to get the numbers for calculating discharge superheat? My understanding of the discharge superheat calculation is discharge line temperature less liquid line pressure (converted to temperature). Is that right?

    • @RomanBaugh
      @RomanBaugh  2 месяца назад

      Discharge superheat is measured using discharge line temperature 6” down stream of compressor then subtracting it from liquid line temp converted to saturation temp. 180-110 = 70 DSH.

  • @cchurch816
    @cchurch816 Год назад

    But keeping them videos comming.

  • @cchurch816
    @cchurch816 Год назад

    Also sensors and transducers. How to verify they work right

    • @jorgevalladares179
      @jorgevalladares179 2 месяца назад +1

      Without getting into the math, Daikin has two apps that can help you convert that. Daikin tech and Daikin services, it’ll convert dc voltage to pressure (vise versa) and temps to ohm (vise versa). Then get gauges or temp probes and see if they correlate.

  • @LC-qi5ff
    @LC-qi5ff 10 месяцев назад

    How does overcharge cause low oil in compressor?

    • @tom24057
      @tom24057 9 месяцев назад +1

      Flushes out oil

    • @RomanBaugh
      @RomanBaugh  7 месяцев назад

      System never runs the compressor over half speed causing velocity to be low not allowing refrigerant to bring oil back from the indoor units. Couple that with liquid flood back then compounds the issue removing any remaining oil from the compressor.

  • @ashleydavies7863
    @ashleydavies7863 7 месяцев назад

    Are the temperature figures in Fahrenheit or Celsius? As I'm in the UK

    • @RomanBaugh
      @RomanBaugh  7 месяцев назад +1

      Fahrenheit good sir

  • @hugopalomo4222
    @hugopalomo4222 Год назад +1

    Hello Roman, could you put subtitles in Spanish? Thanks

  • @marcoferreira226
    @marcoferreira226 8 месяцев назад

    I have a question are your Temps F or C?

  • @Scottyboyhvacdude
    @Scottyboyhvacdude Год назад +1

    How long before you have to take this down?

    • @tom24057
      @tom24057 Год назад

      Why?

    • @RomanBaugh
      @RomanBaugh  4 месяца назад

      Still up Scott 😂

    • @Scottyboyhvacdude
      @Scottyboyhvacdude 4 месяца назад

      @@RomanBaugh I only say that because there's been some other helpful daikin content that was taken down. I don't understand the secrecy. We as technicians need any tools we can get, thank you!!

  • @guuuuustaf
    @guuuuustaf 5 месяцев назад

    Do you know the process of Daikin minisplit, how do they calculate evaporating temp and condensing temp. Since they do not have pressure transmitters. Only discharge probe, ev probe and condensing probes, and air thermistor probes. Do they calculate evaporating and condensing temperatures via the compressor load ampere, and also take into account the heatexchanger probes? Its bugging me for real. Hope you have somewhat of an answer.=)

    • @ryanbrown7134
      @ryanbrown7134 5 месяцев назад

      Short answer is they don’t. Thermistor data is all that is used to control the motor speeds and valve pulses. At least that’s what is taught in the mini split class.

    • @guuuuustaf
      @guuuuustaf 5 месяцев назад

      @@ryanbrown7134 Then how can they get correct sh and sc? Its been bugging me how are they actually know how to adjust the eev. Some of the data needed for correct sh, sc is unknown. They must use ampere drawn by the compressor too trying to get somewhat of correct ev pressure and condensing pressure... 😁

    • @ryanbrown7134
      @ryanbrown7134 5 месяцев назад

      @@guuuuustaf It bothered me too when I first started working on them. They don’t monitor superheat or subcooling. They may have an algorithm that determines wet operation with compressor current and discharge temp but I doubt it. Even if they did, they wouldn’t tell us anyways. Other than the logic, mini splits are very simple units.

    • @guuuuustaf
      @guuuuustaf 5 месяцев назад

      Haha okeey thank you for the answer=). may be therefore they often have two accumulator tanks beside compressor. Cause the sh cant always be 100%.They are indeed very simple. The logic as you say is the more tricky part.
      @@ryanbrown7134

    • @Jonathan-li1xh
      @Jonathan-li1xh 5 месяцев назад

      If the units don’t have the pressure sensor , it should have thermistor at the evap and at the condenser coil . These temperature will be used for evap temperature and condensation temperature instead pressure reading converted into sat temperature.

  • @dcfabrication2097
    @dcfabrication2097 Год назад

    VRV
    DSH
    Discharge SuperHeat
    Discharge pipe temp - Tc ( condensing saturation temperature)
    Range 27-72
    Below range ( overcharge)
    Above range ( low oil or low refrigerant)
    SSH
    Suction SuperHeat
    Suction pipe temp - Te ( evaporation saturation temperature)
    Range 3.6-32 (5-32)
    Below range (wet- liquid refrigerant at compressor)(overcharge or bypassing refrigerant In system)
    Above range ( low charge or restriction in system)
    SUB
    System SubCooling
    Tc - liquid pipe temp after heat exchanger(s)
    Range 11 +/- 3
    Below ( undercharge or restriction )
    Above ( overcharge or bypassing )

    • @RomanBaugh
      @RomanBaugh  Год назад +6

      Unfortunately thats not the whole story, I will be making a video in depth of each item and all the intricacies that go with it.

    • @sydneyabbas7999
      @sydneyabbas7999 Год назад

      ​@@RomanBaugh
      Thanks Roman fantastic video, will help a lot.
      Really looking forward of your next video.
      👍🏼

    • @nguyennam880
      @nguyennam880 Год назад

      @@RomanBaugh Watting

    • @NotOurRemedy
      @NotOurRemedy Год назад

      @@RomanBaughare these numbers for VRV3 and 4?

  • @cchurch816
    @cchurch816 Год назад +1

    U sound like u think all techs have basic schooling in refrigeration theory.

    • @epicone2449
      @epicone2449 Год назад +1

      You need to know the basics before diving into VRV. Like experienced in service on package units or split systems

    • @cchurch816
      @cchurch816 Год назад +1

      ​@@epicone2449 looked for the dsh, sc and sh on a daikin fit heat pump couple days using the daikin btsc app. The symbols arnt matchin on the app. Reverted to just using to probes. Went after the dsh and sh in heating mode. Looked normal. Last tech suspected low charge after the tstat error history shows low pressure trip. Found the data wire was grounded at the equipment chasis and corrected it.

  • @andrewkozik4666
    @andrewkozik4666 Год назад +1

    Excellent video!

  • @buggedmechanics
    @buggedmechanics 4 месяца назад

    Great video