we have cmc 256-6 omricron relay test kit at our site. it has only host interface. Can we connect to pc using parallel to usb adapter or we must use the cmusb-p cable supplied by omicron? please reply.
For reverse Vby is a reference 90(Vby)+20(RCA) = 110 is a MTA angle... pls reply. I think u made mistake in this video. And the operating region for reverse is 30 - 90 - 190 degrees inbetween. Kindly reply sir. If I am wrong pls correct me
@@baranitech For #R phase fault in reverse condition.... For self Pol, Ref(-Ir) =180 deg Then 180 - 20 = 160 is a MTA So that we will get, Self polarization 80 - 180 - 240 (Operating region) For Cross Pol, Ref(Vby) = 90 deg Then 90 + 20 = 110 is a MTA So that we will get, Cross polarization 30 - 90 - 190 (Operating region) Sir Pls reply If am wrong Thanks for your previous reply
very very thank you sir one small request please do this video in tamil also for all our barani tech tamil friends
awesome video. keep posting. So much things to learn . good job.
I appreciate you
thank you
Please make a video of directional Earth Fault
definitely
we have cmc 256-6 omricron relay test kit at our site. it has only host interface. Can we connect to pc using parallel to usb adapter or we must use the cmusb-p cable supplied by omicron? please reply.
you can try with usb adapter . but i am not sure 100%
For reverse Vby is a reference 90(Vby)+20(RCA) = 110 is a MTA angle... pls reply. I think u made mistake in this video.
And the operating region for reverse is 30 - 90 - 190 degrees inbetween.
Kindly reply sir. If I am wrong pls correct me
for Reverse. Ir start from 180 and its ref with VYB so operating region is 80 to 240 thank you
@@baranitech ruclips.net/video/jFWSkz-km4Y/видео.html
Sir in this video at 6:38 you mentioned differently Sir. I am confused
@@baranitech
For #R phase fault in reverse condition....
For self Pol, Ref(-Ir) =180 deg
Then 180 - 20 = 160 is a MTA
So that we will get,
Self polarization
80 - 180 - 240 (Operating region)
For Cross Pol, Ref(Vby) = 90 deg
Then 90 + 20 = 110 is a MTA
So that we will get,
Cross polarization
30 - 90 - 190 (Operating region)
Sir Pls reply If am wrong
Thanks for your previous reply
In ref670 differential relay the display is not see its dark what is the problem
Please make a video on testing of autoreclosurers in distance relay in detail
Thank you
Where r u from
@@baranitech which part of india?
You ve mistaken unintentionally.😂 You should say make 45 from VYB since its the reference not from IR as you said .. ie -90 deg+45 deg =-45.
Video Blurred, Can't see anything
please try to increase video quality , i will also try to increase my quality of video . thank you