Directional over current Protection | Cross polarized directional over current protection

Поделиться
HTML-код
  • Опубликовано: 19 окт 2024

Комментарии • 33

  • @user-bouhamida08
    @user-bouhamida08 3 года назад +2

    Merci pour votre excellent explication simple et non compliquée

  • @kumereshan
    @kumereshan 3 года назад +1

    Thank u barani ji

  • @livingstonechando2613
    @livingstonechando2613 2 месяца назад +1

    l have a question in Cross polarization.If the operating current leads the polarizing voltage ,are we not supposed to use negative on RCA settings?

    • @baranitech1026
      @baranitech1026  2 месяца назад

      need to use reverse direction settings

  • @SantoshKumar-nk5ve
    @SantoshKumar-nk5ve 3 года назад +2

    Sir, how we know which one polarization method used in p141 relay for o/c and E/F relay?

    • @baranitech1026
      @baranitech1026  3 года назад

      ITS CROSS POLARIZATION . THIS WE CAN CHECK IN RELAY MANUAL.

  • @ManojkumarSahoo_electrical
    @ManojkumarSahoo_electrical 2 года назад +1

    Hello sir
    For self polarization the RCA angel is taken in clockwise direction from reference phasors & for cross polarization the RCA angel is taken in anticlockwise direction from reference phasors. Is it correct sir ??

  • @balajikrish5842
    @balajikrish5842 3 года назад +1

    Excellent explanation

  • @ManojkumarSahoo_electrical
    @ManojkumarSahoo_electrical 2 года назад +1

    Sir please explain about negative sequence polarization for earth fault protection in transmission line & how to calculate its operating region

  • @魏伯-b2i
    @魏伯-b2i 3 года назад +1

    How do I test the digital protection relay in the field?
    1. After inputting the formal parameters, do you want to test each protection function?
    2. After testing with temporary parameters, do I need to test with formal parameters again?
    3. After changing the parameter settings, how to ensure that the input is correct? Is it re-testing or visual inspection on the equipment?

    • @baranitech1026
      @baranitech1026  3 года назад +1

      1. After input to formal parameter testing of all function will be good
      2. once if you tested with temporary setting itself okay but for 100% conformation you need to go for testing again once you have your formal parameters.

  • @zaynardilez7139
    @zaynardilez7139 3 года назад +1

    What is the suitable RCA for DGR Relay ??

  • @palashdas5346
    @palashdas5346 Месяц назад +1

    How to check REF615 relay phasor diagram/vector sum of current

    • @baranitech1026
      @baranitech1026  Месяц назад

      triggering on DR and possible to check
      Thank you.

  • @gurpreetsinghee
    @gurpreetsinghee 3 года назад +1

    Why some relays use torque angle or MTA for oc 45 lag and ef 15 lead(make avana npa141), but some relays oc 45 lead and ef 15 lag(make erl MIT121-131)

    • @baranitech1026
      @baranitech1026  3 года назад

      each relay has its own programing code and finding method.

  • @ammarhassan2288
    @ammarhassan2288 6 месяцев назад +1

    Shabash

  • @hitmancaptaincool4073
    @hitmancaptaincool4073 2 года назад +1

    Thank you sir

  • @ramkumarchakkaravarthy4170
    @ramkumarchakkaravarthy4170 3 года назад +1

    If RCA is negative then how we should take

    • @baranitech1026
      @baranitech1026  3 года назад +1

      we have to take Vref should be opposite

  • @chatmongkhonratchawong6045
    @chatmongkhonratchawong6045 3 года назад +1

    It phase between 90 angle