Assalamualaikum. I have 6 longi himo 6 585 panels. 2 battery Exide185A aur primax galaxy inverter 5500 pro lga hua hay. Plz send me settings for this setup if u can
@@Rplagend I have sub, and snu settings. But problem occurs with my battery settings. Abi b default agn wali pay main nay settings ki Hain. Q k Kisi b setting say proper result NAHI AA raha tha.
Assalam o alikum Bhai sahabb.. Knox 4kw Din ki mukammal dhoop hoti hai.. Phir bhi knox inverter solar ko utilize nahi karta. Battery discharge ka option aa rha hota hai. Jab solar ka breaker off kr ke dobara on karta hoon to masla hal ho jata hai. Phir battery charging mode par chali jati hai aur sara load solar par shift ho jata hai. Lekin 20, 30 seconds ke baad dobara wohi battery discharging problem aa jati hai. Battery discharging current 10 amp. Kindly solution batayein.
Walikum Assalam It's normal thing. It's actually calibration error. It has nothing to do with battery discharge. In actual your battery level will not fall. If you shut down the breaker of battery you will see solar production will equal the load. So nothing to worry its same with everyone. Even in my Knox 5600 i.e. 4kw.
@Rplagend Ap ne jo kaha bilkul theek kaha. Meine aaj clamp meter se check kiya.. Battery discharge nhi ho rhi thi, jab ke screen par discharging show ho rha tha. Phir mjhe yaqeen hua ke ye calibration ka fault ho skta hai. Aur saath mein ap ne bhi confirmed kar diya to ab mukammal yaqeen hua. Apka bht shukriya JazakAllah
Hy
Assalamualaikum. I have 6 longi himo 6 585 panels. 2 battery Exide185A aur primax galaxy inverter 5500 pro lga hua hay. Plz send me settings for this setup if u can
Walikum Assalam. Add priority to Solar~Utilities ~batter.
and charge only on solar.
@@Rplagend and what about other settings
Please specify which settings do you need. Have you installed App?
@@Rplagend I need battery settings. System is installed since May
@@Rplagend I have sub, and snu settings. But problem occurs with my battery settings. Abi b default agn wali pay main nay settings ki Hain. Q k Kisi b setting say proper result NAHI AA raha tha.
Assalam o alikum
Bhai sahabb.. Knox 4kw
Din ki mukammal dhoop hoti hai.. Phir bhi knox inverter solar ko utilize nahi karta. Battery discharge ka option aa rha hota hai.
Jab solar ka breaker off kr ke dobara on karta hoon to masla hal ho jata hai.
Phir battery charging mode par chali jati hai aur sara load solar par shift ho jata hai. Lekin 20, 30 seconds ke baad dobara wohi battery discharging problem aa jati hai.
Battery discharging current 10 amp.
Kindly solution batayein.
Walikum Assalam
It's normal thing. It's actually calibration error. It has nothing to do with battery discharge. In actual your battery level will not fall. If you shut down the breaker of battery you will see solar production will equal the load. So nothing to worry its same with everyone. Even in my Knox 5600 i.e. 4kw.
@Rplagend
Ok Sir,
Thank you very much
@Rplagend
Ap ne jo kaha bilkul theek kaha.
Meine aaj clamp meter se check kiya.. Battery discharge nhi ho rhi thi, jab ke screen par discharging show ho rha tha.
Phir mjhe yaqeen hua ke ye calibration ka fault ho skta hai.
Aur saath mein ap ne bhi confirmed kar diya to ab mukammal yaqeen hua.
Apka bht shukriya
JazakAllah
I have problem with pv 8000 Load 2 not working
Please set Battery voltage to turn off AC2 to 46V and Battery Voltage to turn on Ac2 to 48 V. It will solve the problem.
@@Rplagend thanks for guiding. Pl inform at which numbers setting are the battery settings in knox pv80000 inverter.
Please set 14 No setting to use, 19 No to 41, 20 No to 46 and 60 No to 48.