Incorrect inverter setting causes AC /Heavy Load to Trip continuously

Поделиться
HTML-код
  • Опубликовано: 6 фев 2025
  • In this video I have explained tha reason that causes the AC or heavy load to Trip again and again

Комментарии • 197

  • @LifeLab365
    @LifeLab365 6 месяцев назад +2

    good way to educate audience about knox 5600

  • @SSGGOD666
    @SSGGOD666 4 месяца назад

    Assalam alaikum sir i appreciate your effort and work you put in these videos and thankyou for sharing your knowledge with us.
    I have kryton 8000 6kw hybrid.
    Kindly provide detail of 60 and onwards setting for 48 volt set up.
    Jazakallah.

    • @Chobkar
      @Chobkar  4 месяца назад

      Dear you can use simple formula for 60 and onward setting. 2-3 v less than original volts of the battery. Original volts of your battery is 48 that means you can keep low dc cut out around 45 if tou have lead acid batteries and around 25-30% if you have lithium ion Phosphorus battery

  • @Dfgyvghh
    @Dfgyvghh 6 месяцев назад

    Boht zabardast or logically smjhaya ap ny. Bro ye inverter konsa h apka or kitny kw ka h

    • @Chobkar
      @Chobkar  6 месяцев назад +1

      Knox Pv 5600 4KW

  • @asimhunainlife
    @asimhunainlife 4 месяца назад +1

    Ye video ap ne subha kitne baje banai he? or ye normally watts aana kitne baje tak shuru karta he inverter?

    • @Chobkar
      @Chobkar  4 месяца назад

      Around 7:00 in winter and around 6:00 in summer

  • @AaaAa-w5j
    @AaaAa-w5j 2 месяца назад +1

    bhai frequncey up down hoti ha both .13amp sy 4 amp pa jti ha is ka koi hal ha.knox 6 kb . ❤

  • @mnewaz46
    @mnewaz46 Месяц назад +1

    سر یہ سیٹنگ sbu پر کام کرتی ھے

  • @islamicspeechesofficial1
    @islamicspeechesofficial1 9 дней назад +1

    Sir! iss trah to battery sare heavy load use kr le ge

    • @Chobkar
      @Chobkar  8 дней назад +1

      Dear nahi karay gi. Heavy load cut of ho jay ga

  • @jabirmahmood8466
    @jabirmahmood8466 25 дней назад +1

    Bhi main na Knox 6 KW PV 8000 hybrid inverter without battery lagaya ha aur is k sath Longi himo7 (610) watts k 8 panels aur 555 watts k 2 panels lagai han aur wapda sharing ha. Peak hours main solar 1500 watts bhi nahi de raha aur wapda k units bhi ziada consume ho rahe han. Load orient ka aik fridge aur kuch led bulbs han. Kum production ke kia wajah ha. Aur without battery aur wapda sharing k sath best setting bata den.

    • @Chobkar
      @Chobkar  25 дней назад

      Dear 555 watt walay utar dein. As per rule apka inverter lowest generation pe fix hota hay. Two different panels mein sy lower generation walay k hisab sy

  • @muhammadsalman1381
    @muhammadsalman1381 5 месяцев назад +1

    A.O.A Bhai main nay inverter only solar charging per set kia hay to jub take sunlight ho ti hay wo battery full dikhata ta hay but jaisay he sun off ho ta hay wo battery around 60% dikhata hay jubkay battery use bhi nahi ho ti hay please guiide jazak Allah

  • @junaidahmad7267
    @junaidahmad7267 5 дней назад

    Pv5000 pro ko setting per bhi video bana dain high load and low low poease

    • @Chobkar
      @Chobkar  4 дня назад

      Dear ye kaunsa model hay and kis company ka?

  • @basharatzia3525
    @basharatzia3525 4 месяца назад +1

    Second load again kese on ho ga battery charge less ho gi..? Jb pv he na ho...?

    • @Chobkar
      @Chobkar  4 месяца назад

      Ye jab charging start hogi to tab he on hoga

  • @AaaAa-w5j
    @AaaAa-w5j 2 месяца назад +1

    bhai knox 6 kb frequnecy both up down hoti ha is k koi hal ha 15 amp sy 6 amp pa ajti h

    • @Chobkar
      @Chobkar  Месяц назад

      It's firmware issue dear. Change the firmware

  • @WahSonyElectronics
    @WahSonyElectronics 6 месяцев назад

    Bhi knox 4000kv ka ivertr k sath 8 panel 545w k lagy hn 1parel ar 7 sires to kya sub panel sirse m best kaam krty hn ya jasy m ny ky hn wasy dosara ags 1800 battery lgi hy par 1tun ac iverter battry py ni chlta ?

    • @Chobkar
      @Chobkar  6 месяцев назад

      Waslam. Dear first of all connect all the panels in series. This inverter supports 500v DC so you can connect 10 panels in series very easily

    • @Chobkar
      @Chobkar  6 месяцев назад

      Dear it is always best to attach tubular battery with inverter instead of simple battery. It should run the inverter check your settings. Consult my other videos for the correct setting

  • @CoderStuDio
    @CoderStuDio 6 месяцев назад

    bhai jb wapda aa jaye per charging only solar ho toh 2nd output on ho jaye gi ya ni ?

    • @Chobkar
      @Chobkar  6 месяцев назад

      Yes dear start ho jay ga because tab apka load wapda sy run ho raha hota hay battery sy nahi

  • @chishtiamobilerepairing5241
    @chishtiamobilerepairing5241 6 месяцев назад

    Brother hybrid me knox or tesla me konsa best rahy ga?

    • @Chobkar
      @Chobkar  6 месяцев назад

      Knox and tesla both are from same family both are designed by voltronic and are sold sold here with company's own branding otherwise both are same and are sold by voltronic with different names in other part of the world

  • @3Idiotss32
    @3Idiotss32 Месяц назад +1

    Asalamu Alaikum bhai mera invertor night me automatically wapda se bettry pr shift hota hai again and again.i am worries plz help

    • @Chobkar
      @Chobkar  Месяц назад

      Bhai apnay volt meter ko check Karen aj kal Wanda sy over current aa raha hota hay to voltmeter wapda ko trip Kar deta hay aur inverter battery pe chala jata hay

  • @AaaAa-w5j
    @AaaAa-w5j 2 месяца назад +1

    bhai frequncey up down hoti ha both .13amp sy 4 amp pa jti ha is ka koi hal ha.knox 6 kb .

    • @Chobkar
      @Chobkar  2 месяца назад +1

      Sorry dear apka sawal nahi samjha

    • @AaaAa-w5j
      @AaaAa-w5j 2 месяца назад +1

      @Chobkar bhai .green meter laga ha .or revers load jo jata ha .us k ampire up down hoty ha

    • @AaaAa-w5j
      @AaaAa-w5j 2 месяца назад

      ap ka num mil sakta ha bhai

    • @AaaAa-w5j
      @AaaAa-w5j 2 месяца назад

      wapta ki tarf jo humri bijli jati ha .green meter laga ha. wo thk ni jati .kbi 14 ampire sy 4 ampire pa ajti ha

    • @AaaAa-w5j
      @AaaAa-w5j 2 месяца назад

      bta dy plz

  • @Gaming246-x6w
    @Gaming246-x6w 6 месяцев назад

    Please make a video on your batteries backup time and which load u can run

    • @Chobkar
      @Chobkar  6 месяцев назад

      OK inshahallah

  • @aaqibali9349
    @aaqibali9349 6 месяцев назад

    Bhai es k kiyey minimum kitny panel required hain On krny k liyey?

    • @Chobkar
      @Chobkar  6 месяцев назад

      Minimum two.

  • @wajahatali7929
    @wajahatali7929 6 месяцев назад

    Aoa. Bhai kya knox 5600 main jab voltage 220 sa down hotay hain exple 150-180 tu ya inverter same yahi voltage output main deata ha. 220 nahi karta ?

    • @Chobkar
      @Chobkar  6 месяцев назад

      Sorry dear apka question clear nahi hay. 220v kaunsay AC ya solar sy anay walay DC?

  • @TanveerHussain-o6o
    @TanveerHussain-o6o 6 месяцев назад

    Assalam u alaikum bhai mene naya lia hai konx krypton 5600 but is mn warranty card nh hai secondly service centers ka bi bta den my distt sahiwal hai thanks

    • @naeemasghar2573
      @naeemasghar2573 6 месяцев назад

      I am facing same issue no warranty card in box
      On enquiry the seller called the whole seller who replied that warranty can be claimed from serial no of the inverter.... And no warranty card required

    • @azharkhattak7751
      @azharkhattak7751 6 месяцев назад

      Ab compnay ne card khatm kar dya ha purchasing bill he warranty card hoga

    • @Chobkar
      @Chobkar  6 месяцев назад

      Warrant of this inverter is online. Your serial number and ID shall be used for warranty. And warrant center near to your area is in Lahore but it is not fully functional yet. Right now every claim is being sent to Islamabad. Hopefully in couple of months Faisalabad and Lahore centers would be fully functional

  • @ahssanmanzoor1818
    @ahssanmanzoor1818 6 месяцев назад

    Bhai agar same rakhen gy to heavy load on off ziada ho ga aur apka heavy load jal bhi skta hy..

    • @Chobkar
      @Chobkar  6 месяцев назад

      Bhai mera to on of nahi hota 1month sy ooper ho gaya hay is setting ko.

    • @ahssanmanzoor1818
      @ahssanmanzoor1818 6 месяцев назад

      @@Chobkar apki setting k hisab sy to hona chaiye .. anyway ni ho raha to achi bat hy.

    • @Chobkar
      @Chobkar  6 месяцев назад

      @ahssanmanzoor1818 meray bhai ap is mechanism k baray mein clear nahi hein is leay keh rahay hein. Have load cut of tab he hoga jab battery discharge ho rahi hogi means apka wapda ya solar available nahi hay. Jab ye available nahi hein to it means ap bettery second load k cut of voltage k bad bhe use Kar rahay hon gy. Jab wapda ya solar availability hogi to battery second load automatically on ho jay ga uska battery k voltage sy koi taluq nahi hoga. J am sure ab apko mechanism samajh aa gaya hoga

    • @ahssanmanzoor1818
      @ahssanmanzoor1818 6 месяцев назад

      @@Chobkar theekh hy bhai men yeh kar k dekhon ga phir apko btaon ga... right now meny L2 cutoff 23 volt rkha hy aur 64 setting ko 27 volt rakha hy.. to jab tk battery again 27 par ni aati L2 start ni hota... dusri bat men wapda off rkhta hun din men... aur solar available hota hy lekin dhoop kam hony ki waja sy battery jab 23 par aati hy to L2 cutoff ho jata hy... solar current bi aa rha hota hy lekin kam hota hy...

  • @zeeshanarif6637
    @zeeshanarif6637 6 месяцев назад

    Bahi in inverter Ka WiFi kasay connect kartay ha smart life application Ka sath kindly is pr be aik video Bana day.

    • @Chobkar
      @Chobkar  6 месяцев назад

      G inshahallah after Aashur I shall upload the video with step by step guide

    • @Chobkar
      @Chobkar  6 месяцев назад

      Iski App watch power hay.

    • @zeeshanarif6637
      @zeeshanarif6637 6 месяцев назад

      @@Chobkar bahi maray pass Jo inverter ha vo smart life application say connect hotah ha lakin mouj say connect ni ho pa Raha. Flash company Ka inverter ha vo same is tarah Ka ha Jo ap video ma Dekh rahay ho.

    • @Chobkar
      @Chobkar  6 месяцев назад

      @zeeshanarif6637 OK I shall upload video today. Procedure is almost same I think

    • @zeeshanarif6637
      @zeeshanarif6637 6 месяцев назад

      @@Chobkar jazak Allah brother ❣️

  • @arslanmunir8699
    @arslanmunir8699 6 месяцев назад

    I am face same issue, i am using AGS sp tall 2000 battery with same inverter.
    Can i reset the sitting now? Or just change only this both sitting. Now my sitting is on 27.5

    • @Chobkar
      @Chobkar  6 месяцев назад

      Yes you can change but be clear about one thing AGS tall is just tall battery it is not tubular battery so backup would not be as good as tubular battery

  • @AdilAli-yd7dx
    @AdilAli-yd7dx 4 месяца назад +1

    I have 54v lithium ion battery...At 60 no my voltage is set at 52v and at 63 no my voltage is set at 47.5v.But during load shedding at night,heavy load does not cut off at 47.5v resulting in a complete black...share your thoughts plz

    • @Chobkar
      @Chobkar  4 месяца назад

      Have you checked setting No 61 and 62? These setting might have been making a conflict with 60 and 63

    • @AdilAli-yd7dx
      @AdilAli-yd7dx 4 месяца назад

      @@Chobkar I have changed the settings of 60 and 63 only

    • @Chobkar
      @Chobkar  4 месяца назад

      @AdilAli-yd7dx dear as far as I know it should work if there is no conflict of setting

    • @Chobkar
      @Chobkar  4 месяца назад

      Oh dear. You have Lithium battery? If you have lithium battery then you set SOC not voltage. Means state of charge or percentage of battery instead of voltage now in tour case you set voltage but inverter thinks of the value as percentage so it thinks to cut off the load on 52% and start load at 47.5%. Set the percentage to 80 at 60 and 45 or 50 % at setting No 63

    • @AdilAli-yd7dx
      @AdilAli-yd7dx 4 месяца назад

      @@Chobkar ok I'll do the same.What should be selected at no 5? LIB or LIC

  • @amirshahzad4643
    @amirshahzad4643 6 месяцев назад

    Brother 6 kw ka knox mai secnd out put on nh ho rhi or setting safe kerny py B 60 nb ki setting safe nh hoti is ki kya reason hy

    • @Chobkar
      @Chobkar  6 месяцев назад

      Setting kesay save Kar rahay hein? I have a video on how to save setting please consult that video for guidance

  • @GamingChanal1003
    @GamingChanal1003 3 дня назад

    Sir trion inverter Mai 61 error kaisy khatm kary or lithium battery lagi Hy please batao

    • @Chobkar
      @Chobkar  3 дня назад

      Dear uska manual check Karen error 61 kia hay. Aisay to idea nahi hoga

  • @saddamkhan7980
    @saddamkhan7980 28 дней назад

    Bhai meray 2 Knox pv 8000 lagay howay hai. Alag alag os mei say 1 inverter grid feeding krta hai or dosra nahi. Dono mai se sirf 1 feeding krta hai. Wapda voltage 250 tak hota hai.
    Kindly reply

  • @Few_yt
    @Few_yt 6 месяцев назад

    ye inverter infinix max hai?

    • @Chobkar
      @Chobkar  6 месяцев назад

      No, KNOX PV5600

  • @muhammadashla5463
    @muhammadashla5463 6 месяцев назад

    Assalam-o-alaikum sir mere pas abh issue ye aarha hai k battery full charge hone k bawajood thora sa load barhane pr inverter foran trip ho jata hai or battery bh bht jaldi drain horh hai

    • @Chobkar
      @Chobkar  6 месяцев назад

      Apki solar ki generation kitni hay aur kitna load daltay hein

  • @shanubhatti313
    @shanubhatti313 6 месяцев назад

    AGR INVER JIS B WIRRING PAY LGA HO OR USKI WIRRING PICHAY SAY PHASE CHANGE KR DIYA JAYE TO US SAY INVERTER KO KOI ISSUE HO GA???
    WIRRING SAY MURAAD PHASE OR NUTAL HAY...

    • @Chobkar
      @Chobkar  6 месяцев назад +1

      Sorry dear apka question nahi samjha

    • @shanubhatti313
      @shanubhatti313 6 месяцев назад

      @@Chobkar BHAI METER SAY WIRING AGR PHASE KI JAGHA NUTAL WIRE LAGA DI OR NUTAL KI JAGHA PHASE (RED & BLACK)
      TO AGR INVERTER KI WIRING HONAY K BAD USKO CHANGE KIYA JAYE METER SAY TO KOI ISSUE TO NI HO GA??

    • @Chobkar
      @Chobkar  6 месяцев назад +1

      @shanubhatti313 bhai apnay polarity ka khayal rakhna hay means neutral ki jaga neutral aur phase walay slot mein phase wire k colour sy koi farq nahi parta Wo hamari asani k leay hota hay. Secondly ab jab wiring ho chuki hay aur ap change Karen gy to apko meter sy inverter tak poori wire ki length Change karni hogi bashart e k apkay installer nay inverter ki wiring standard procedure pe ki hay means red for phase and black for neutral

    • @shanubhatti313
      @shanubhatti313 6 месяцев назад

      @@Chobkar G US NAY INVERTER KI ISI LIYE CHANGE KI Q K BY MISTAKE YA JESE B METER SAY WIRING THEEK.NAHI HUI THI... Q k installer ko pta ni tha pehlay to ulta lagnay ki wajha say generation nahi ho rhi thi is liye wiring ko samjh k ulta lganay pay chal gya tha mera inverter primax glaxy hay...

    • @Chobkar
      @Chobkar  6 месяцев назад +1

      Yes zaroor hoga. Inverter k mother board pe Jo components lagay hotay hein wo short circuit ho jain gy aur inverter ko nuqsan hoga

  • @Few_yt
    @Few_yt 6 месяцев назад

    brother aik jaga pr inverter jis diwar pr lga hai us diwar pr hath rakhny sy halka halka earth mehsos hota hai !!! inverter ko zameen me earth b kiya hai lekin phr b aisa q ho rha ha?

    • @Chobkar
      @Chobkar  6 месяцев назад

      Dear earth proper nahi hua hoga. Kitnay feet pe earth kia hay? Aur kia mechanism use kia hay earth ka?

    • @Few_yt
      @Few_yt 6 месяцев назад

      @@Chobkar Apna whatsapp kindly share kr dien

    • @Few_yt
      @Few_yt 6 месяцев назад

      @@Chobkar earth proper hai ! almost 30feet tk ha

    • @Chobkar
      @Chobkar  6 месяцев назад +1

      You can contact at nabeelraza.geo@gmail.com

    • @Few_yt
      @Few_yt 6 месяцев назад

      @@Chobkar 😁

  • @khuzicrib5788
    @khuzicrib5788 6 месяцев назад

    Please tell me can we run this inverter on pv without wapda or battery,direct on pv only

    • @Chobkar
      @Chobkar  6 месяцев назад

      No hybrid inverter should be run without battery or wapda sharing ever. Same is the case with this inverter. It will run on sharing from either battery or wapda. All those RUclipsrs claiming to run any hybrid inverter without battery are lying and not telling that ultimately it will fail. They are misguisinh the public for viewership only. We have to see the effects on the long run because no one buys costly inverter to run short time only. I would not recommend at all

    • @khuzicrib5788
      @khuzicrib5788 6 месяцев назад

      @@Chobkar thanks brother also tell me the app which they recommended don't show many options like apps like solar man do, do u recommend any app I have 3 apps soalrpower energy mate and smart ess

    • @Chobkar
      @Chobkar  6 месяцев назад

      @khuzicrib5788 Watchpower app is recommended by the company

  • @Muneeb_Nasir
    @Muneeb_Nasir 6 месяцев назад

    AOA!!! aik problem aa rhi hai k mne inverter SUB mode main rkha howa aur grid sharing k doran light load pr generation nhn krta magr jese hi heavy load chalaen ya SBU mode main jaen ya wapda breaker off kr dein to generation shuru kr deta hai. Ye kis wja se ho rha???

    • @Chobkar
      @Chobkar  6 месяцев назад

      Hybrid Inverter sharing kartay hein. SUB mode mein solar utility and battery ka sequence hota hay magar hybrid inverter load k mutabiq generation karta hay. Ap is ko SBU pe rakhein aur ho sakay to breaker of Kar dia Karen. Breaker on hoga to ye sharing karay ga aur kyun k wapda stable hoti hay solar stable nahi hota to inverter automatically stable ko select Kar let's hay

    • @Muneeb_Nasir
      @Muneeb_Nasir 6 месяцев назад

      @@Chobkar lekin ye pehle nhn ho rha tha jb batteries lgai hain tb se shuru howa. brother pehle maine isko batteries k bagher isi mode main chalaya tb ye solar se leta tha priority pr but ab ye issue srf smart load yani fans lights fridge grid sharing kro to solar se generation nhn kr rha magr heavy load yani iron ya A/C grid sharing k saath kro to solar se hi max power generate krta aur 100 watt wapda se leta

    • @Chobkar
      @Chobkar  6 месяцев назад

      @Muneeb_Nasir charging source priority aur time check Kar lein 99 aur 100 number setting

    • @Muneeb_Nasir
      @Muneeb_Nasir 6 месяцев назад

      @@Chobkar wo 00 hain dono

    • @Chobkar
      @Chobkar  6 месяцев назад

      Setting number 99 ko SUB ya SBU Kar dein aur value 00 23 Kar dein aur 100 wali ko OSO kar dein aur wo bhe 00 23 Kar dein

  • @h.a.hamza345
    @h.a.hamza345 6 месяцев назад

    100 Amp 4 Battery pr kya voltage rakhyn ?
    Knoc krypton 8000 ..48 volt hai

    • @Chobkar
      @Chobkar  6 месяцев назад

      Kaunsay voltages dear?

  • @AaaAa-w5j
    @AaaAa-w5j 2 месяца назад

    bhai frequncey up down hoti ha .knox 6kb

  • @Umair_aditter
    @Umair_aditter 6 месяцев назад

    Bhai ya good inveter ha????

  • @bilaltahir3693
    @bilaltahir3693 6 месяцев назад

    Sir MRI 60 no ki seting nai change ho rhi ingenier kahta hy k by default is ki seting set hy ab nai change ho g Mera havy load cut out nai hota

    • @Chobkar
      @Chobkar  6 месяцев назад

      Engineer nahi hay Wo shakah Jo ye keh raha hay k setting change nahi hoti. Ap aik Kam Karen setting to restore factory setting Kar lein. 60 number setting change na honay ki waja ye bhe ho sakti hay k koi aur setting is sy conflict Kar rahi ho is leay change nahi ho rahi hogi

    • @bilaltahir3693
      @bilaltahir3693 6 месяцев назад

      @@Chobkar ok try karta hn

    • @heellal
      @heellal 5 месяцев назад

      Set 5 number setting to user, than save 63 setting and than save 60 setting that should be less than 63

  • @oldisgoldjhankar9476
    @oldisgoldjhankar9476 6 месяцев назад

    Zeonic duamond 4.5kw with 8 junko 580watts panel. Ac 1.5ton ok or microwave ok. But trip on 1000watts iron. Kindly help

    • @Chobkar
      @Chobkar  6 месяцев назад

      Iron 1000 watt nahi hoti dear iron kam sy kam 1800 watt hoti hay. Ap wapda sharing Kar lein ya battery sy

  • @muhammadalibhatti6503
    @muhammadalibhatti6503 6 месяцев назад

    اسلام علیکم ورحمتہ اللہ وبرکاتہ
    بھائی جان انویٹر کے ڈسپلے میں جو نمبر شو ہو رہے ہیں برائے مہربانی ہر نمبر کا مطلب بتا دیں شکریہ

  • @MuhammadAmin-d7l
    @MuhammadAmin-d7l 6 месяцев назад

    Salam
    If I set option 60 on 23 volt
    My battery will cutoff on 21volt (night)
    So can I set setting 60 and 63 on 26 voltage if my floating volt is 27

    • @Chobkar
      @Chobkar  6 месяцев назад

      Dear if you want to instantly cut the load then yes go ahead because 27v are jus to make battery hold 25v which are actual voltage of any battery lithium or lead acid or gel no battery holds 27v in actual so if tou set 26v then your inverter will instantly cut the load because on battery it shall instantly drop to 25v and load will be cut

  • @sameedaftabb
    @sameedaftabb 6 месяцев назад

    Brother mere pas 585 k 8 panel lagay howay hain, lekin 2800 watt se zyda load ni uthaa rha 2800 py jaty hii screen py load 100% ho jata hai.... Aur har time wapda se 200 se 300 watt le rha hai iski kya waja ho sakti hai?

    • @Chobkar
      @Chobkar  6 месяцев назад

      Dear 585w panel actual mein 585 nahi hota ye lab k figures hein. Apka panel max 9-10amp current and 40v dy sakta hay Wo bhe peak time in optimal condition in real life it should be like 35vx9amp=315w now 315x8=2520w.now as per your given data it is giving you 2800w that I belive is very good generation. In other scenario 40x9=360w 360x8=2880w even then your system is generating max output. If you can check the amps of your panel then kindly check short circuit amp of your panels one by one. And check it for few seconds only and remember don't check them when connected in series and also check voltages of the panel one by one also. this way it will help you troubleshoot the problem l. First check the panels and also confirm your firmware version of inverter

    • @Chobkar
      @Chobkar  6 месяцев назад

      Ap apnay panels ka tilt angle and direction bhe check Karwa lein un sy bhe generation pe farq parta hay

  • @oldisgoldjhankar9476
    @oldisgoldjhankar9476 6 месяцев назад

    Plz guide this setting for zeonic 4.5 kw diamond model

    • @Chobkar
      @Chobkar  6 месяцев назад

      This setting is usable for every inverter that runs on 24v setup

    • @ahssanmanzoor1818
      @ahssanmanzoor1818 6 месяцев назад

      @@Chobkar is sy battries healt par koi farak pary ga....

  • @qammerjavaid7996
    @qammerjavaid7996 6 месяцев назад

    AOA brother mera inverter phly battery use krta gy jab full discharge ho jaye to charging start hote hy kia koi aese setting hy k SBU me rhty hovy shaam ko instead discharging agr battery full ho to wapda py transfer ho jaye ya jitne remaining ho wo wapda sy charge kr k standby rhy ta k jab light off ho jaye to battery backup use ho like UPS. PLZ guide

    • @Chobkar
      @Chobkar  6 месяцев назад +1

      Waslam dear ap inverter ko sub pe rakhein aur charging sirf solar sy karwain yani OSO in setting 16 and in setting No 100 set OSO to 00 23. Wapda breaker subah off Kar dein 5-5:30 k around and sham ko on Karen around 5-5:30pm. In this way apka inverter sara din solar and battery pe run hoga aur sath he usay charge bhe karta rahay ga. Sham ko 5 bajay k around jab ap wapda on Karen gy to apki battery with 10 minutes solar sy he charge ho jay gi aur apko wapda sy charging nahi karni paray gi because agar battery wapda sy charge karni hay to phir solar ka koi faida nahi bill to utna he ay ga

    • @qammerjavaid7996
      @qammerjavaid7996 6 месяцев назад

      @@Chobkar thank you so much sir for kind guidance. 1 guidline r kr den plz shaam ko jab solar incoming nahe aate to inverter phly discharge krta hy till end r pher wapda sy charging start krta hy jo k 2amp set ke hy wo enough charge nahe hota r raat ko agr light off ho jaye to backup nahe milta. S ka kia solution hy plz advise

    • @Chobkar
      @Chobkar  6 месяцев назад +1

      @qammerjavaid7996 ap battery solar pe charge Karen only solar OSO. Aur sham ko 5 bajay wapda on Karen within 10-15 sunset honay sy pehlay battery charge ho jay gi inshahallah. Battery charging amps 20 rakhein

    • @qammerjavaid7996
      @qammerjavaid7996 6 месяцев назад

      @@Chobkar i don't think even the installer can define or guide the way you have guided. Allah aap k lia hamesha asania ataa farmaye🌹

    • @Chobkar
      @Chobkar  6 месяцев назад

      @qammerjavaid7996 my pleasure dear

  • @farhansh-j3h
    @farhansh-j3h 5 месяцев назад

    Brother many Sath wapda shre ki hi but wapda sy he curnt use rehta hi batry b Sath lagi hi semjh nhi aa Rahi kia kro

    • @Chobkar
      @Chobkar  5 месяцев назад

      Ap battery k sath sharing Karen

    • @farhansh-j3h
      @farhansh-j3h 5 месяцев назад

      @@Chobkar batry b lagi hoi hi but wapda sy curnet leta hi solar sy nhi leta wpda of kr do to solar aur batry use krta hi mjhy problem hi jab sun 🌞 na ho to solar off ho jata is lie wpda Sath shre Kiya phr b wpda he use Hoti solar nhi

    • @Chobkar
      @Chobkar  5 месяцев назад

      Change setting to SBU

  • @naqqashsarwar138
    @naqqashsarwar138 6 месяцев назад

    Same setting in knox pv8000?

    • @Chobkar
      @Chobkar  6 месяцев назад

      Yes sir

    • @h.a.hamza345
      @h.a.hamza345 6 месяцев назад

      Knox pv 8000 48 volt hai​@@Chobkar

    • @Chobkar
      @Chobkar  6 месяцев назад

      @h.a.hamza345 bhai ap kaunsay voltages ka puch rahay hein

  • @imranmalik6902
    @imranmalik6902 5 месяцев назад

    23 Ampere discharging ho Rahi ha par volt Kam NAHI ho Rahe, mere 4 batteries ke tezi se Kam ho hate han, Konsi batteries lagai hean

    • @Chobkar
      @Chobkar  5 месяцев назад

      Phoenix tall Tubular TX1800

  • @abdullahabdull6828
    @abdullahabdull6828 6 месяцев назад

    Sir Knox 5600 ko battery aor Wapda k bagrai kesy chalaye.
    Mainy ajj wapda aor battery Breaker off kyay to Second Load Off hogaya.
    aor battery breaker off krny k baad bhi Inverter ki screen pr Battery voltage 27.0 likha araha hai

    • @Chobkar
      @Chobkar  6 месяцев назад

      Dear hybrid inverter ko kabhi bhe sharing k baghair nahi chalatay Wo sharing wapda sy ho Ya battery sy. Why do you want to run it without battery? I would not be able to bear torque load of your appliances and will generate fault code 4 that would be overload with red led light and continuous beep. As far as your second part of the question is this inverter is designed with capacitors and other electronic components that store charge for few minutes if you switch off all the Input of this or any hybrid inverter still it has charge stored that would light the LED screen for few minutes

    • @abdullahabdull6828
      @abdullahabdull6828 6 месяцев назад

      @@Chobkar sir its is draining battery 20 to 30 ampere discharging

    • @abdullahabdull6828
      @abdullahabdull6828 6 месяцев назад

      Aor inverter k sath jo Dc fuse hota hai wo inverter mai kha pr lagta hai

    • @Chobkar
      @Chobkar  6 месяцев назад

      Wo extra hay uski abhi zaroorat nahi hay Wo inverter k andar laga hota hay jahan sy pv input jati hay

    • @Chobkar
      @Chobkar  6 месяцев назад

      What is firmware version of your inverter?

  • @Muneeb_Nasir
    @Muneeb_Nasir 6 месяцев назад +1

    is main masla ye aa rha hai k same 23v 60 aur 63 set nhn ho rhi kam az kam 1 ka difference dena prh rha hai

    • @Chobkar
      @Chobkar  6 месяцев назад +2

      Ap watch app k though inverter ko aik dafa reset Kar lein phir ho jay gi. Maybe apki koi aur setting value aisi hay jis ki waja sy ye value set nahi ho rahi. Ya phir aik value 23 hay to doosri 23.1 Kar lein

    • @Muneeb_Nasir
      @Muneeb_Nasir 6 месяцев назад

      @@Chobkar ye bta do brother k jb wapda off krte hain to inverter batteries se 100 watt kiun leta continuously yani 4 5 ampere ki discharging krta

    • @Chobkar
      @Chobkar  6 месяцев назад

      @Muneeb_Nasir it is natural it will not drain your battery. It is designed like this by the original designer which is voltronic. no need to worry about it. It will automatically charge the battery as well. It uses the battery because that way it will not damage the battery plates and and socondly we continuously switch of and switch on different appliance and during the switch on process every appliance uses torque load that is managed by the inverter through sharing, either it is wapda or battery. So now a days if we look at electricity price it is better to be shared with battery instead of wapda

    • @Muneeb_Nasir
      @Muneeb_Nasir 6 месяцев назад

      @@Chobkar another question today when i was using wapda sharing sir it is not sharing like it used to and there is a sudden decrease but it is working fine when on batteries. This did not happen before??

    • @Chobkar
      @Chobkar  6 месяцев назад

      @Muneeb_Nasir it is because if setting No 1. Setting No 1 is SUB means solar utility battery, USB means utility solar battery and SBU solar battery utility. These setting set the sequence of energy source check setting No 1

  • @MajidKhan-wy2bl
    @MajidKhan-wy2bl 6 месяцев назад

    Knox 5600 jab trip hota hai tu screen pe 15 number option beep aate hai ye kya masla hai?

    • @Chobkar
      @Chobkar  6 месяцев назад +3

      Ap inverter without battery ya wapda sharing chala rahay hon gy. Jab solar sy input low ati hay aur consumption load Zyada hota hay to ye 15 number error dy k trip Kar jata hay. Isko sharing lazmi dein wapda ya battery sy

    • @YasirYasir-gi5hh
      @YasirYasir-gi5hh 6 месяцев назад

      💖

  • @lovebirds9291
    @lovebirds9291 6 месяцев назад

    Solarmax 4 kw
    Crwon 8.2 kw
    Same setting inki 60 numbr py volts save nai ho rhy

    • @Chobkar
      @Chobkar  6 месяцев назад

      4kw is 24 volts setup and 8.2kw is 48v setup. 4kw starring to same video wali hogi but 8.2kw mein 42 ya 43v hogi

  • @scrapstation6823
    @scrapstation6823 6 месяцев назад

    Look like so many issues or manual handling in KNOX inverter.

    • @Chobkar
      @Chobkar  6 месяцев назад

      Every electronic device has its own problems but the more facilities the device has the more complex it becomes

  • @Affan_Nasir
    @Affan_Nasir 6 месяцев назад

    Assalam-o-Alaikum

    • @Chobkar
      @Chobkar  6 месяцев назад +1

      Waslam

    • @Affan_Nasir
      @Affan_Nasir 6 месяцев назад +1

      @@Chobkar My name is AD Nasir

    • @Affan_Nasir
      @Affan_Nasir 6 месяцев назад +1

      Renala Khurd

    • @Chobkar
      @Chobkar  6 месяцев назад +1

      Mashahallah. AD nasir sb kesay hein. Allah pak sehat o salamti ata farmain

    • @Affan_Nasir
      @Affan_Nasir 6 месяцев назад +1

      Plz contact me

  • @alijee6
    @alijee6 6 месяцев назад

    Ap ka number kya he

    • @Chobkar
      @Chobkar  6 месяцев назад

      For any query you can contact at nabeelraza.geo@gmail.com

  • @sajidnaeem3278
    @sajidnaeem3278 6 месяцев назад

    Assalamu alaikum meri bhi 60 number ki setting save Nahin Hoti vah default 21 per rahti hai

    • @Chobkar
      @Chobkar  6 месяцев назад

      Dear ap apni setting ko reset Kar lein app k through

    • @Zafarali-zm8ef
      @Zafarali-zm8ef 5 месяцев назад

      63 ki setting pehly kr Le bde me 60 ki setting kr Le ho jayega

  • @AaaAa-w5j
    @AaaAa-w5j 2 месяца назад +1

    bhai frequncey up down hoti ha both .13amp sy 4 amp pa jti ha is ka koi hal ha.knox 6 kb .

  • @AaaAa-w5j
    @AaaAa-w5j 2 месяца назад +1

    bhai frequncey up down hoti ha both .13amp sy 4 amp pa jti ha is ka koi hal ha.knox 6 kb . ❤

  • @MuhammadAmin-d7l
    @MuhammadAmin-d7l 6 месяцев назад

    Salam
    If I set option 60 on 23 volt
    My battery will cutoff on 21volt (night)
    So can I set setting 60 and 63 on 26 voltage if my floating volt is 27

  • @AaaAa-w5j
    @AaaAa-w5j 2 месяца назад +1

    bhai frequncey up down hoti ha both .13amp sy 4 amp pa jti ha is ka koi hal ha.knox 6 kb .

  • @MuhammadAmin-d7l
    @MuhammadAmin-d7l 6 месяцев назад

    Salam
    If zI set option 60 on 23 volt
    My battery will cutoff on 21volt (night)
    So can I set setting 60 and 63 on 26 voltage if my floating volt is 27

  • @AaaAa-w5j
    @AaaAa-w5j 2 месяца назад +1

    bhai frequncey up down hoti ha both .13amp sy 4 amp pa jti ha is ka koi hal ha.knox 6 kb .

  • @MuhammadAmin-d7l
    @MuhammadAmin-d7l 6 месяцев назад

    Salam
    If zI set option 60 on 23 volt
    My battery will cutoff on 21volt (night)
    So can I set setting 60 and 63 on 26 voltage if my floating volt is 27

    • @Chobkar
      @Chobkar  6 месяцев назад

      Sorry can't understand your question