HOW TO WIRE Addressable Smoke / Heat Detector's (FDAS) | Fire Alarm System
HTML-код
- Опубликовано: 21 авг 2024
- In an addressable fire alarm system, all the devices such as detectors, call points and alarm bells are connected in a loop system to the fire addressable control panel and each device has an address (to tell about their location). This way, it is very easy to find the exact location of the device which has been triggered in the connected circuitry.
The basic idea behind the loop system is that in case of short circuit fault, only a small portion of the system affected while the rest will work properly with the help of isolation module connected in the loop. In a single loop, up to 99 devices may be connected and can be extended up to 3.3 km depends on the ability of fire control panel system.
The main purpose of addressable fire system is same as conventional fire system expect the wiring connection and DIP (Dual In-Line Package) switches for an address or a set of address showing the exact location of triggered component on main addressable fire control panel screen. Addressable is most accurate but costly as compared to conventional system while both are not smart as compared to intelligent fire system which show the exact reason behind the triggered device if it is a fault, pre-alarm or fire and extinguish them quickly.
How to WIRE Smoke / Heat Detector Conventional: • HOW TO WIRE Convention...
If this video helped you out, share it with your friends and give it a thumbs up, please drop a like and leave a suggestion or comment below.
----------------------------------------------------------------------------------------------------------------
Our daily routine as Maintenance Technician in our company.
#Please_Like_Share_and_Subscribe_RACkabayanTECH
➦ For more videos please SUBSCRIBE! 👍
©️ Disclaimer Under Section 107 of the Copyright Act 1976,
allowance is made for "fair use" for purposes such as criticism, comment, news reporting, teaching, scholarship, and research.
Fair use is a use permitted by copyright statute that might otherwise be infringing.
Non-profit, educational or personal use tips the balance in favor of fair use.
This video presentation is for educational purpose only
Now watching.. newly assigned para sa FDAs. Para dagdag kaalaman
Salamat sa panonood partner👍
good presentation of video must have wiring connection diagram and actual termination of units..salamat..
Thanks partner👍
Salamat master,.may natutunan nanaman dagdag kaalaman master.ask kulang po paano po ba isingit ang firemans phone jack master ibadin po ba ang loop ng f/phone jack.salamat sa tugon more power& godbless to yur chanel po
Partner Nagdedepende po yan sa FACP system! Kung ang FACP na ginamit nyo ay may BUILT-IN na Fireman Phone Jack.... may sarili pong linya para dyan........Sana nakatulong
More views and more power to your channel...
Thanks sister👍☺️
Nice Lodi
Galing naman...
Thanks
Thanks sir lakeng tulong.
can i use addressable fire alarm with PLC
Connected ba mcp jn kase may nakita ako na nakakabit yong mcp sa relay. Hindi nasama sa mga devices.
Videos of connections of FAC model AH-00212 Salamat sana makita ko un sir
Sir,,,ilang sounder ba sa isang loop? nakadepende po ba sa input device po ba?,salamat po godbless and keepsafe
Depende po kung gaano ka lawak yung pag i-installan partner......
@@RACkabayanTECH ty po sir
@@RACkabayanTECH nakasubscribe narin po ako
Sir magkaiba po ung FACP ng conventional at addresable?
Tama po kayo partner😊
Idol magtatanong lang po yung adress po ba ng smoke and heat devices is built in na po ba yan sa pagbili ng adressable Fdas? Or need pa yan e program bawat isa? Salamat po.
Kailangan pa i PROGRAM partner👍 makikita mo sa likod ng addressable smoke detector or heat detector may dipt switch😊
Sir tanong lang po pwede ba gamitin ang pang conventional na smoke detector sa addresable na FACP salamat
Hindi pwede....iba ang smoke detector na pang conventional at iba din yung smoke detector na pang addressable👍🤔
Reverse polarity ba iyan iyan sir?
Sir magtanong lang po ako pano po mag palit ng address na device cooper kasi gamit namin diko alam pano mag change. Sinubokan kuna mag palit kaso di binabasa sa panel
Partner...... Take note...na iba ang Heat/Smoke detector ng Addressable at Conventional Fire Alarm System.......make sure na pag addressable fire alarm system ang gamit nyo.....dapat lahat ng devices na gagamitin nyo ay pang addressable din.....Sana nakatulong..... salamat sa panonood👍
naka paralel po sir tama po ba
sir magandang araw po, pano malalaman na pang addressable or pang conventional yong device? salamat po.
Salamat po sa tanung partner.....Yung device na pang ADDRESSABLE malalaman mo sa likod ng device makikita mo ang dip switch.....Yung device nman na pang CONVENTIONAL wala kang makikita na dip switch sa likod plain lang na terminal sa likod....may video po ako nyan partner panoorin mo dito ruclips.net/video/T7_FD3OOJH4/видео.html sana nakatulong👍👍
Sir good morning ask kolng po if yong addressable need paba ng resistor? Or yong tinatawag po nating end of the line
Hi partner kapag ka addressable fire alarm system ay wala pong end of line resistor 😊salamat
Ask lang sir Dba Yung Sounder my sariling wiring dpwde masama sa mga MCP AT SD
It depend sa FACP system na gamit sir kapag CONVENTIONAL system na wiring ang sounder may sariling linya po yan Sounder-1,234 or more...... Sa ADDRESSABLE system naman ay lahat ng devices ay nasa iisang twisted wire lang po naka kabit like MCP, SD, HD etc. Panoorin mo ang conventional and addressable system nasa channel ko ang mga videos ko sana nakatulong😊
sir question po, ang connection po ba na to is by floor or sa kabuuan na mismo ng building? tnk u po
Kabuohan napo yan partner.......
Master, kahit alin dyan sa smoke ang mag trigger, magiingay lang ung 3 bell na kasama dyan sa 1 loop?
Yes partner👍
You have in English
sir question po, ano po layo na kaya ng 1 fdas system,
newbie po
Anong FDAS SYSTEM ang tinutukoy nyo partner Conventional, Addressable, Intelligent, Wireless, Fire alarm system....... actually no specific distance it depends on the situation on-site....... Partner sana nakatulong😊
hello po.. san po nakakabili ng fire alarm system na mag automatic call agad sa fire department?
Saan po ba ang location.....Marami po sa online.....
anong recommended na fire alarm cable sa pwede gamitin na wire size? pwede ba gamitin sa facp, detectors, manual call point at sounder iisang wire size?
Hi, partner....sa tanong mo... Pwedeng pwede partner sana nakatulong.....
1.5 lng boss
2c x 1.5
#16 TF wire
Boss tanong ko lng bakit po nakasama ung "sounder at trouble light" sa loop ng mga detectors? Dba dapat ho nasa output terminal sila? Thanks boss medyo nalito lng ako hehe.
Kapag ka addressable fire alarm system ang gamit mo ganyan po ang installation partner tinatawag sya na (LOOPING o RING CIRCUIT)Tandaan partner kapag ka FDAS SYSTEM ang pag uusapan APAT na systema dapat mong malaman, magkakaiba sila ng installation process sana nakatulong partner panoorin mo lahat ng FDAS SYSTEM nasa Channel kopo lahat yan salamat
Noted boss thank you!
Sir kapag po ba may na detect ang isang detector tutunog lahat ng sounder niya??? 🤔
Yes partner☺️
Sir tanong lang po. Kasama b talaga sa isang loop ang detectors at sounder at beacon? DI/DO
Hello partner salamat at napadaan ka dito sa channel ko...... regarding sainyong tanong kapagka addressable fire system po ang gamit nyo yes magkasama po upto 150 - 190 devices ang sa iisang loop 'o' ring circuit.....Sana nakatulong😃
Sir pano po mag testing ng adressable
Partner salamat sa tanong mo......Need mo magtanggal ng smoke or heat detector device or press mo yung manual call point mag trouble yung FACP o control panel mo at makikita mo ang address na naka assign....sa devices na nag trouble...ibig sabihin ay perfect na pagka gawa ang addressable fire alarm system ninyu......
sir tanong ko lang po, pwede po na naka end of the resistor ang dulo instead na loop?? malayo na kc masyado ang dulo sir. possible po yon?
Hi partner! Kung ang control panel mo ay addressable system.......hindi pwede partner........kailangan naka loop po yan......... Sana nakatulong....salamat👍
@@RACkabayanTECH ok po sir.salamat po ng marami
Hi ser Yung sa horing lih ser parehas din ba Yung diagram nyan sa addressable
Addressable Ng ibang adddresable FACP
Most of them are the same! better to double check the manual thanks🎄
sana sir may video tutorial ka din sa intelligent at wireless
Abangan nyo nalang po sating Channel sir Godbless
Good PM ser,,,may tanning lang ako, Kong address able ilang panil sa poydi sa Isang building
Depende po sa laki ng building sir at dami ng initiating device na ikakabit😊
@@RACkabayanTECH salamat ser.. May sub panel siya ser patongo sa main panel paano Ang connection Nyan ser poydi gawan mo ng video... salamat ser...
Hintayin mo nalang sa channel ko partner salamat😊
Sir pano po ung wiring ng dalawang conventional fire alarm link together
Abangan nyo nalang po
pano po ba malaman na kailangan ng module?? o anong kondisyon po na kailangan ng module? thanks po
Base sa tanong mo partner ang paglalagay ng mga module ay nakadepende po yan sa nagpapa install ng FDAS sana nakatulong
@@RACkabayanTECH pano po malaman na kailangan mg module?
@@RACkabayanTECH ok lang po ba na generic design lang ng detectors, Bell at manual pull station at facp lang gamitin?
Pwede partner basta angkop ang mga iniating devices na ikakabit sa system mo...may mga cases kasi na hindi sila compatible.....
Sir, iyong addressable smoke at heat detector device magkaiba ba sa conventional o both pwedeng gamitin.
Magka iba yan partner....😊
Sir dito ba sa addressable termination sa loob ng device pwede po bang i loop lang iyong wire o pwede rin i cut ang wire bago i terminate sa loob ng mga devices
I cut mo ang wire saka mo i terminate partner that's the best way to do it sana nakatulong at salamat sa panonood😊
Sir bakit yong iba pong tutorials walang potol ang return nila..
Pag addressable system partner walang putol po ang return nyan....Ring Circuit o' Loop system ang tawag nyan👍
Sir ask po sa supplier na pwede kuhanan po ng AFAS
Marami po.....kung saan ka malapit.....meron din online.....👍
Boss iba un wiring namen sa sounder may sariling loop
Ganun talaga partner pag conventional system ang gamit nyo may sariling loop po ang sounders....
Boss dba hiwalay ung bell,sounder strobelight s sd,hd at mcp
Partner yung magka hiwalay! conventional fire alarm system po yun....👍 dito sa Addressable Fire Alarm System magkaiba yung locations ng bawat devices pero iisang pair nangwire lang po ang pinagcoconneckan naka loop lang po yan.... partner🔥
Sir tanong ko lang. Ung example niyo po bang strobe and sounder dito is an addressable device? If addressable, yes i agree na pwede mo siya itap sa nearest addressable device. Second question is reasonable po ba ang price ng addressable strobe and sounder device rather than mag conventional ka na strobe and sounder and rewire ka ng bago for the conventional strobe and sounder papunta ng panel? Thank you boss.
Yes po sir! Base sa Titulo ng videong pinanood.... addressable fire alarm system po lahat ng devices na nka connect dyan ay pang addressable po yan.....Sa pangalawa mong tanong! Ang pag install ng FIRE ALARM SYSTEM ay nagdedepende sa laki ng building na pag installolan...... Pangalawa nagdedepende din sa gusto ng client....Kung anong klaseng FACP ang gusto nyang ipakabit.......Kung ang detector devices na ipapa install ay lalagpas ng 150 - pataas.... I highly recommend mag Addressable Fire Alarm System kana para hindi hassle ang pagtrouble after installation at makakatipid din sa gastos pagdating sa wire......Pero kung less than 50~80 pieces na detector devices lang, mag Conventional Fire alarm system kana.......Takenote! Hindi reverssable ang detector devices ng Fire Alarm System....Iba ang pang (ADDRESSABLE at pang CONVENTIONAL) Overall, the conventional fire alarm is inexpensive and used in small building. however, the addressable fire alarm is very smart and sophisticated system which is very expensive but it is more reliable. Bottom line, conventional fire alarm should be installed in building where it is easier to spot the fire (such as in building having fewer rooms) While the addressable fire alarm should be installed in large buildings. (FACP) Sana nakatulong...👍
Marami salamat sir!
Likewise partner👍
Parallel po ba yan?
Yes partner
@@RACkabayanTECH so pwede po ba sya kahit saang device kukuha ng return o dun ka lang talaga sa pinakadulong device kukuha ng return?
Tama po partner sa addressable FACP ang
Pinaka dulo na twisted wire
mo ay babalik sa FACP mo🤓
paano po kung nagstopped ang boung looped ano po possible problem?
thanks
Salamat sa panonood👍 check your wire sir might be naputol ang linya somewhere. Hope nakatulong😊
what we did was we removed the detector after sandstorm to clean,,then bigla na lang nagappear and tx fault,,disablement at loop stopped
Na ayos nyo ba sir?
@@Broskie-tm5jh ano naging problema sir ?
we don't know Indian :)
🤐
Sir ask ko lng diba poh kylangan u png iprogram ang addressable bago man or mag aadd k lng ng detector tnx poh sa reply
Yes kailangan po i program pag addressable system ang FACP, Ang bawat initiating devices/detective devices ay may kanya-kanyang address ang mga yan ..kapag ka isa mga device ang maka detect ng usok/fire yung device na yun ang madedetect ng FACP......sana nakatulong🤓👍
Need b for computer and sofware or sa Panel n mismo n lng iprogram salamat poh ulit sir 😊😊😊
Dyan mismo ipoprogam sa FACP ang mga initiating devices or detective devices👍