What do you do if the short circuit data is unavailable from the electric utility company? Can you use an “infinite source” calculation?
Many say an infinite source is not the worst case. Jim states that this is actually an incorrect statement - Watch Jim explain a work around using the infinite source when the utility company is not available.
How can short circuit current increase with time from the utility? Jim explains from his own experience earlier in his career, as the head of the Transmission Studies Group of a large electric utility why the current can increase. What X/R ratio would you assume (and what is an X/R ratio.
Learn the answer to these questions and more from this 13:38 minute video taken from Jim Phillips’ 16 hour class: How to Perform an Arc Flash Study - IEEE 1584. This class by Jim Phillips is scheduled as a live streaming/interactive class by several times a year and is also available on demand at our Online learning platform: brainfiller.co...
Notice: Although Jim Phillips, is the Vice Chair of IEEE 1584, International Chair of IEC TC78 Live Working Standards, Technical Committee Member of NFPA 70E and Member of the ASTM F18 Electrical Protective Equipment for Workers, the views in this video are those of Jim Phillips and may or may not represent views of any of the aforementioned standards.
For questions about the training programs, contact brenda@brainfiller.com or 800-874-8883 (U.S.)
-------
Since the planet is a large place and Jim can't be everywhere, we are bringing Brainfiller training programs to you by offering arc flash safety, power systems engineering and regulatory update programs through this online learning program. Most classes offer professional continuing education units, so you can meet your annual compliance requirements through brainfiller.co.... FREE classes and CEU’s are also available for those on a budget. Visit Brainfiller Online at brainfiller.co....
About Jim Phillips: Electrical Power and Arc Flash Training Programs. For four decades, Jim Phillips has been helping tens of thousands of people around the world understand electrical power system design, analysis, arc flash and electrical safety. He has developed a reputation for being one of the best trainers in the electric power industry. See Jim’s upcoming training events: brainfiller.co...
Read Jim Phillips’ bio - click here: brainfiller.co...
Sign-up for Jim Phillips’ monthly publication “Grey Matter” which contains news about new standards, conferences, technical articles, electrical engineering and more! bit.ly/2BB083d
Brainfiller was founded in 1987 by Jim Phillips. Visit Brainfiller brainfiller.com.
Can you show your work for the infinite bus calculation. I can not get the 31374 amps.
Sure thing.
SCA = short circuit amps (on secondary)
FLA2 = Full Load Amps (on secondary)
SCA = (FLA2 x 100) / %Z
FLA2 = 1500 kVA / [sqrt(3) x 0.48 kV] = 1804 Amps
SCA = [1804 Amps x 100] / 5.75
SCA = 31,374 Amps