Guided Workflow Tutorials w/ Joe: Installation - Part 3
HTML-код
- Опубликовано: 31 май 2024
- Joe Medosch, Client Success Manager with measureQuick, dives deeper into the new Guided Workflows found in measureQuick 2.5, from profiling the job site to documenting indoor issues.
00:00 Beginning
00:05 Recap of Parts 1 & 2, Introducing
00:35 Populating the profile
00:53 Navigating the helper functionality
01:20 Geolocate & Name Site
02:14 Deploying Indoor Probes
05:06 Zeroing Manometers
05:51 Enter Filter Information
07:47 Enter Installation Info
09:27 Photo Document Indoor Issues
10:59 Enter AHU/Furnace M/N & S/N
12:32 Power On & Profile System
15:46 Electrical & Electrical Meter
17:03 Document Indoor Issues
17:51 Wrapping up Part 3 - Наука
In an air handler your low side pressure probe needs to see the resistance of the filter, but also the resistance of the coil. The placement location you showing for the probe is not correct. The probe needs to be after the coil, not after the filter.
Depends on if the air handler is rated with the filter and you are using the manufacturer supplied filter.
Most today are not rated with the filter, so after the filter is correct. The filter is external to the air handler.