Home Fire Alarm System Set Off | Two Alarm With Pre-Alarm Smoke Detector Activation

Поделиться
HTML-код
  • Опубликовано: 15 авг 2024

Комментарии • 72

  • @nics-systems-electric
    @nics-systems-electric  Месяц назад +13

    At 5:45 I meant to say those devices in corridor and stairwell are less sensitive. Thanks for watching!

    • @Fredengle
      @Fredengle Месяц назад

      Hi Nic my specialty is more home smoke alarms you name a very specific scenario can you explain to me what has happened? Or is there a link

    • @Fredengle
      @Fredengle Месяц назад

      Again will say the thing you mentioned was not covered in the research I studied

    • @thethirdrail8397
      @thethirdrail8397 20 дней назад

      @ 3:37 you said that you need the furnace on a hot day??? tell me you are kidding me... and meant the Air Conditioner...

  • @user-pg7ii3zs3m
    @user-pg7ii3zs3m Месяц назад +8

    I was actually going to ask you to test the pre- alarm feature of the smoke detectors in a monthly system test. Nice to see the system working and protecting your house. Great video! Keep up the good work!

  • @FI-TECH-250
    @FI-TECH-250 Месяц назад +4

    Nice! Soooo cool that i shows you the percentage of smoke in the smoke chamber on the announciator

  • @All_ConsumingBandu
    @All_ConsumingBandu Месяц назад +4

    Perfect system! Not only are low frequency sounders good for the rooms, but code 3 especially because I once saw you put them in continious, and they hurt my ears pretty bad, and horns (especially for me) are bad because they will increase panic attacks no matter if it is a system sensor horn or a Wheelock horn. Also I thought for a while that the sounders were horns but you didn't call them horns once.

  • @GaryBeltz
    @GaryBeltz Месяц назад +6

    Jackson: GRRRRRR me: be quiet lol

  • @joeycaridi3030
    @joeycaridi3030 Месяц назад +6

    The cast iron skillet returns again, causing an alarm that isn't false and the system worked like how it should

  • @VOLTRONDEFENDER4440
    @VOLTRONDEFENDER4440 Месяц назад +3

    Nice to see your system working as it should!

  • @EASsirenVids01
    @EASsirenVids01 Месяц назад +1

    I was going to recommend swapping the heads from the bedroom and the stairs to see if one head is less sensitive, but the explanation you made on the sensitivity setting makes sense. If they were set the same then I would try that.

  • @aerhardt
    @aerhardt Месяц назад +8

    I think that it would have been concerning if it didn’t go off. The system was doing its job.

    • @adventuresquadofficial
      @adventuresquadofficial Месяц назад +1

      Yes I agree I can’t believe People would say it wasn’t doing it’s Job

  • @Firealarmperson902
    @Firealarmperson902 Месяц назад +1

    You should put a small exhaust fan in the house love the videos keep up the great work

    • @nics-systems-electric
      @nics-systems-electric  Месяц назад

      For what?

    • @Firealarmperson902
      @Firealarmperson902 Месяц назад

      @@nics-systems-electric when the fire alarm system gets off and when there is a real fire

    • @nics-systems-electric
      @nics-systems-electric  Месяц назад

      @@Firealarmperson902 you wouldn't want to have air movement in a building like that during a fire that would make it larger

    • @Firealarmperson902
      @Firealarmperson902 Месяц назад

      @@nics-systems-electric ok thanks love the videos

  • @hotbytesB
    @hotbytesB Месяц назад +2

    You need to do July testing

  • @AlphaCelebrities874
    @AlphaCelebrities874 Месяц назад +1

    *I just had a fire drill at school today.*

  • @wibwabz
    @wibwabz Месяц назад +2

    great video! im writing a mod for Minecraft (fabric 1.19.2) that adds some fire alarm devices and exit signs. i currently have a BG-12 pull station, a white exit sign, and a key for the pull station.

  • @JakeOfficial2002
    @JakeOfficial2002 Месяц назад +2

    Nice video

  • @thecomputech3353
    @thecomputech3353 Месяц назад

    In your next monthly test, you could test the heat detector in the store room in the garige and the heat detector in the shed that is attached to the house.

  • @Siren_StrObE
    @Siren_StrObE Месяц назад

    I agree that smoke alarms are unreliable more often than they should be, so I also installed a fire alarm system in my house monitored by an American monitoring company, ADT. I don't recommend getting it monitored because it already sends emails and notifications to your phone without monitoring, and the monitoring fees are at least 100 USD each month, which is extremely expensive. Overall, the system is exceptionally high quality and has a pre-alarm to prevent false alarms. I have had the system for nine years, and it has picked up a real fire in an oven caused by debris being left in the stove, which got me and my family safely evacuated and quickly notified the fire department before the fire spread further. The system also does CO as well. Just yesterday, my house had a dangerous outlet that sparked so horrifically it split in half and crumbled into pieces, but I was much less worried even knowing there was an active fire hazard because of the fire alarm system. I encourage everyone who reads this to stay as safe as possible by at least getting residential smoke and co-detectors in recommended areas of the house. Stay safe and even safer with fire protection.

    • @Fredengle
      @Fredengle Месяц назад

      HI Nic or Siren so are you saying if I am looking at alarms options I are you saying I should be able to get something like adt and not get it monitored and if I manage to get it installed but not monitored I would save on the monitoring fee?

    • @Siren_StrObE
      @Siren_StrObE Месяц назад

      @@Fredengle yes that is the case but you have to set it up yourself and can’t get a premium system.

    • @Fredengle
      @Fredengle Месяц назад

      @@Siren_StrObE so if I could not do it my self would it in theory be possible to see if it an option if there is an electrician that understands how to assemble the parts?

    • @Fredengle
      @Fredengle Месяц назад

      I mean If I thought for my home a professonal system was best would you recommend something like adt and see If I can find an electrician who can install it as a non monitored system ? thoughts please thank you

    • @Siren_StrObE
      @Siren_StrObE Месяц назад

      @@Fredengle Adt has there own employees who are trained to help you learn you way around the system and install it after you set up an appointment online after consulting a specialist about what sensors and how many would be best for your home.

  • @The_FireAlarmGuy
    @The_FireAlarmGuy Месяц назад +2

    Nice video and nicely explained 😊, does Notifier/Honeywell make any multisensors ?

    • @nics-systems-electric
      @nics-systems-electric  Месяц назад +2

      Yes they do

    • @The_FireAlarmGuy
      @The_FireAlarmGuy Месяц назад +1

      ​@@nics-systems-electricOh nice 😊, why did you not use them in the generator building?

    • @nics-systems-electric
      @nics-systems-electric  Месяц назад +1

      @@The_FireAlarmGuy because I want smoke or heat to be able to set it off and not need both to be set of might be possible to separate but they are way to expensive anyway.

    • @The_FireAlarmGuy
      @The_FireAlarmGuy Месяц назад +1

      ​@@nics-systems-electricAh ok👍 😊

  • @Rainbowhockey
    @Rainbowhockey Месяц назад

    Jackson is really unhappy with the alarm huh! Poor guy! Give him some pats from me and tell him he's a good boy! 🐶 🐕

  • @AndrewKatzmakes
    @AndrewKatzmakes Месяц назад

    Only at 1:53, so I'll edit if it changes, but I recall reading in a US Notifier (or maybe firelite, but I think it was notifier) brief that you can have detectors grouped and it will look at the chamber values of that group. Not a notifier tech, so I don't have access to manuals that would confirm how this is setup, but I assume if you haven't enabled that then it's not what is going on here. If this feature does exist, it might be something to play with in the future.

  • @Fredengle
    @Fredengle Месяц назад

    Nic do you think than its possible that I could have something like adt installed than and then ask it is a requirment to have a monitoring fee I mean theoretically it should work and be able t dodge the monitoring fee ? I guess in theory it would work but it does not mean they allow it ?

  • @keithpierce8458
    @keithpierce8458 Месяц назад

    nice and nicely explained

  • @NewEnglandAviaton987
    @NewEnglandAviaton987 Месяц назад +1

    1:12 Jaxon?

  • @Jazzdog393
    @Jazzdog393 Месяц назад +2

    fire

  • @ATK_J.Y.S_I.N.D_Offical
    @ATK_J.Y.S_I.N.D_Offical Месяц назад +1

    Cool! :3

  • @gamerboy12970
    @gamerboy12970 Месяц назад

    Yes thank you for uploading

  • @ConnorMartchenke
    @ConnorMartchenke Месяц назад

    What's the fifth monitor module above the panel (the one above the garage tie-in module) for? Also, what were you cooking when the smoke detectors went off?

  • @benrodriguez4905
    @benrodriguez4905 Месяц назад +1

    Jaxon or what ever how you say his name

  • @cyberlight22
    @cyberlight22 Месяц назад +1

    Dog is going crazy

  • @Fredengle
    @Fredengle Месяц назад

    HI Nic I may have watch this video but I also tried to look it up on line are you saying that the pre alarm is a condition in a professionally installed system that raises the sensitivity of certain alarms or am I missing something thoughts please thank you!

  • @nickguzman2865
    @nickguzman2865 Месяц назад +2

    It's like last time in November it went off

    • @nickguzman2865
      @nickguzman2865 Месяц назад

      When your going to start july testing

  • @noghaahnassay2895
    @noghaahnassay2895 Месяц назад

    at 3:15 is the door closer attached to the door thats its supposed to be closing and the door mounting location?!

  • @antoinemartin2626
    @antoinemartin2626 Месяц назад

    I need ramplacing smoke detector to heat detector ???

  • @stampynate0007
    @stampynate0007 7 дней назад

    I wish my family gave in and let me install a fire alarm system as one time something burnt in the oven and there’s aton of smoke and the only smoke detector thats on the floor did not go off. I have been living in this house for over 10 years and those smoke detectors need to be replaced

  • @apctech1
    @apctech1 Месяц назад

    do you clean your heads out with compressed air every so often or dust build up can cause them to go off for no reason

    • @nics-systems-electric
      @nics-systems-electric  Месяц назад

      I usually open them right up to clean it out

    • @apctech1
      @apctech1 Месяц назад

      @@nics-systems-electric that works to

  • @mxslick50
    @mxslick50 Месяц назад

    You shouldn't have taken off your work boots near the detectors. 😅

  • @jaxonkeefer3536
    @jaxonkeefer3536 Месяц назад

    Like many commercial fire systems when a alarm goes off it automatically calls the fire department. Does your system call the fire department or do you have to call the fire department yourself?

  • @erikmorozov1740
    @erikmorozov1740 Месяц назад

    0:45 fire alarm goes off 0:52 fire alarm stops 0:54 alarm signs stop

  • @an_official_scratcher_alt
    @an_official_scratcher_alt Месяц назад

    Try putting an annunciator for the garage system next to the house front door pull.

    • @Harper_DobniYT
      @Harper_DobniYT Месяц назад

      I remember he replied to a comment saying you can’t silence alarms from a different building

  • @collectionandroblox706
    @collectionandroblox706 2 дня назад

    Your dog hates alarm

  • @ElevatorsWithOwen
    @ElevatorsWithOwen Месяц назад

    In my personal opinion, pre-alarm shouldn’t be used because every second counts in a real fire and or smoke situation. I find it ridiculous that Disney World has pre-alarm set to 2 minutes on attractions but that’s just me lol

    • @nics-systems-electric
      @nics-systems-electric  Месяц назад

      That's not how it works your set pre-alarm level is not a time delayed alarm. It's an entirely different set level below the alarm level it does not affect your alarm response time. You are talking about pre-signal which is entirely different.

    • @ElevatorsWithOwen
      @ElevatorsWithOwen Месяц назад

      @@nics-systems-electric Ah i see. thanks for telling me