FX5U Onboard Analogue Input Scaling Mitsubishi Melsec

Поделиться
HTML-код
  • Опубликовано: 14 дек 2024

Комментарии • 9

  • @zellerautomationandplc
    @zellerautomationandplc  3 года назад +2

    How to progam the onboard analogue input on a mitsubishi FX5U PLC ontroller. Also i show you how to parameter the built in scaling function.

  • @GregSampson-p1v
    @GregSampson-p1v 10 месяцев назад

    hi ive got a pressure trandsucer -1 bar to 12 bar 0-10v signal how do i get it read accurately

    • @zellerautomationandplc
      @zellerautomationandplc  10 месяцев назад

      Hello, thank you for your question. Please view my video at 1:55mins. Also calculate 12 Bars with a resolution of 4000 Units you will end up with an accuracy of 0.003 Bars. If you now set the "Scaling upper Limit value" to 1200, you will have a resolution of 0,01 Bar. If you set it to 120 the resolution will be 0,1 Bar. I hope this answers your question.
      Regards
      Gerd

    • @GregSampson-p1v
      @GregSampson-p1v 10 месяцев назад

      thanks for the response i have a q series plc so how can i enter the information i dont have the module parameter: analog input section@@zellerautomationandplc

    • @zellerautomationandplc
      @zellerautomationandplc  10 месяцев назад

      Hello, i have a Function block for FX CPU`s where i can make these calculations. Unfortunatley not in Q Series. If i send you a printout of the program can you write it in Q-series?

  • @vladimirkarcol9008
    @vladimirkarcol9008 Год назад

    Hi, how to convert to real temperature with PT100 and AL2-2TC-ADP converter so that it also shows minus temperatures? The converter gives signals 0-10V 0-4000. is the value
    thank you very much

    • @zellerautomationandplc
      @zellerautomationandplc  Год назад

      Hello, i do not work with alpha controller too much. In order to help you with that i would need some time.

  • @kapiltyagi6938
    @kapiltyagi6938 2 года назад

    👍