How to do ACB breaker settings | Overload | Short circuit | Earth fault | Instantaneous fault

Поделиться
HTML-код
  • Опубликовано: 8 сен 2024
  • How to do major protection settings in Air circuit breaker like overload current setting, short circuit current setting, earth fault current setting, instantaneous current fault setting.
    Please watch the video completely and more about electrical engineering please subscribe to our youtube channel " Electrical Mastar"
    #ACBsetting #ACBprotectionsettings #Aircircuitbreakersetting #ACBrelaysetting #ACBmicrologicsetting

Комментарии • 34

  • @sheikabbas1207
    @sheikabbas1207 4 месяца назад

    Thank you very much for good explanation.

  • @owinookello9358
    @owinookello9358 2 года назад +1

    i 💕 your teachings sir great

  • @vinzers1311
    @vinzers1311 2 года назад

    Very Informative and detail video. ACB's are usually recommended on 800A - 6300A.

  • @rameshtripathy5978
    @rameshtripathy5978 2 года назад

    Nice description & definitely helpful to commissioning engineers & maintenance technicians !

  • @africantales124
    @africantales124 2 года назад

    Nice video. Very explicit.
    Please talk on shunt trip and under voltage release coil.

  • @shankargoudapp9472
    @shankargoudapp9472 3 года назад +1

    Hi sir super teaching thank you 👍

  • @KKumar-sk2kd
    @KKumar-sk2kd 3 года назад

    Good explaining thank you sir

  • @sohailjanjua123
    @sohailjanjua123 Год назад

    Hi, I like your video. Thanks

  • @prakashksp2918
    @prakashksp2918 Год назад

    Good explain sir

  • @gopalakrishnanc.p4415
    @gopalakrishnanc.p4415 2 года назад

    Excellent

  • @TIGREinVOLO
    @TIGREinVOLO 2 года назад

    Good video

  • @azuram6261
    @azuram6261 2 года назад

    Thanks

  • @Sourav8692
    @Sourav8692 5 месяцев назад

    Ii and Isd can be kept switched on simultaneously?

  • @pavankumar-ey3bw
    @pavankumar-ey3bw 3 года назад

    Good sir

  • @abomohamedalrubee5287
    @abomohamedalrubee5287 3 года назад

    Hi there, thank you for video. the tg began from A to J what this mean?

  • @pavankumar-ey3bw
    @pavankumar-ey3bw 3 года назад

    Hai give me some information. Dip switchs is 1 2 3 4 but setting value is 3 numbers available. In Abb ACB breaker relay setting

  • @anbarasansss1673
    @anbarasansss1673 2 года назад

    How to setting in Ir value amps micrologic 6.0.A

  • @majifscreation
    @majifscreation 4 года назад

    👌

  • @Sourav8692
    @Sourav8692 5 месяцев назад

    Why I2t on and I2t off term has come for alarm ??

  • @thklran6400
    @thklran6400 Год назад

    Hi sir, please help, i have trouble at my site, we install transformer 20kv/0,69kv LV side going to ACB siemens 3wl 2000A, load 1 motor 250kw, with DOL starter, the problem indication ground fault in ACB ON status (alarm) during motor start, after 3 second motor run, alarm ground fault is missing, if the setting Ground fault adjust min to max , acb will be trip , ground fault adjust to off, motor normal running, indication ground ON only < 2 seconds

  • @benignojeciel7252
    @benignojeciel7252 3 года назад

    Hi Pare, can u help me, sace tmax7 is tripping without load how can i fix it and set it to rated current 1200amps, nominal current is 1600 amps. Thanks Pare for helping me.

    • @electricalmastar
      @electricalmastar  3 года назад

      Hi pare, thanks for your comments and could you tell me when it was Tripp what are the relay been activated

  • @arvindchauhan-mi2rh
    @arvindchauhan-mi2rh 2 года назад

    From which point it will give to external breaker command for tripping.

  • @mohammadafroz4611
    @mohammadafroz4611 3 года назад

    Sir,
    In Abb relays for HT panel how to know what current is dangerous when earth fault occurs while charging the transformer...as the settings 0.3 In where In is 100. But when earth fault occurs how to know what current is dangerous and what is not so that we can charge again.

  • @siddeshaj552
    @siddeshaj552 3 года назад

    Please upload working principle of oltc

  • @basavarajus9383
    @basavarajus9383 4 года назад +2

    What is instantaneous current fault in ACB

    • @electricalmastar
      @electricalmastar  4 года назад +1

      Instantaneous fault means phase to phase fault will occur it produce large current that time ACB will trip immediately without time delay

  • @bejoyfrancis5598
    @bejoyfrancis5598 2 года назад

    Hi IG values of the breaker differs based on rating. Which was not explained

  • @prakashksp2918
    @prakashksp2918 Год назад

    How to select the relay settings
    L.over load
    Flc*0.80 or 0.85
    S. Short circuit
    Flc* 2times or 3times
    Instantaneous current
    Flc*4 times or 6 times
    G ground
    Flc*0.10 or 0.15
    Sir but
    Short circuit current
    2 time or 3 times sent pandra thu epdi sir enna formula
    Instantaneous current
    4 times or 6 times set in what formula

  • @akhildogra7017
    @akhildogra7017 2 года назад

    Sir.
    My breaker capacity is 800amps all breaker setting is ok but still my breaker tripped at 300amps of load

  • @vamshiganapavarapu7885
    @vamshiganapavarapu7885 Год назад

    Earth fault
    A to J means

  • @ismailajarju8222
    @ismailajarju8222 2 года назад

    thanks