Baah! Baah! You explained very nicely. Anyone can understand that. That's why, I demand to you a video on APFC Panel in where Thyristor is used. Please do that with 2d drawing and practically. Please please.
keep it up very nicely present the control wiring and actual display of APFC panle. Please make vdo on how to calculate the KVAr rating for PF from 0.5 to 0.99 to design APFC panel
nice video... One thing that is missing ,auto contactor and manual contactor . In circuit diagram it is mentioned but in the real presentation of APFC it is missing.
Ise demping resistor kahte hai. Smooth switching karane ke liye ham log iska istemal karte hain Kyunki Jab capacitor start hota hai to Jyada current leta hai aise Mein capacitor aur contactor donon ko hi damage hone ka khata rahata hai. Ye ek heavy duty contactar hai jo ki bhut costly aata hai. Isliye jab contactor me jyada current paas karta hai us samay ye current ko resistor karta hai jisase contactar jyada current flow hone par kharab hone se bach jata hai
Sir hamare yaha 20 kvar reactor lagaya he aur out put me 20 kvar L & Tsuper heavy duty 480 capacitor lagaya he hya. Kya me L &T ke jagah koi dusra 480 v ya 525 volt capacitor laga sakte he kyu ki L & T ka capacitor mil nahi Raha he kya me epcos ka use kar sakta hu??? Pls reply
automatic mode pe relay se CDC ke A1 terminal pe direct connection nhi ho skti? qki CDC bhi contactor ke jesa hi to work karta h? agr hm capacitor bank lgate h to jis number ka relay on hoga us number ka CDC?
sir jee mai electrician hu. bahut jagaha mai dekh raha hu. capacitor sehi hai, but reactor bahut heat hai. 1.reactor kiu heat hota hai 2.reactor se kiu sound ata hai 3.reactor test karneka prossess keya hai please sir RUclips mai bahut search kiya nehi mila. mughe janna hai?
All circuit right but normally contactor besd. it mince. this work normal riley efinitely working ok. So auto an manual function opreting. this contractor very wrong.....
It's damping inrush current of capacitor। मतलब जब capicitor स्टार्ट होता है उस समय वह अधिक मात्रा में करंट लेता है जिससे capicitor और normal कॉन्टैक्टर जल्द ही खराब हो जाता है। cdc में damping resistor होता है जो inrush करंट को रोकता है जिससे capicitor और कॉन्टैक्टर कि लाइफ ज्यादा दिन तक रहती है।
Ek baar wiring check kar ke dekho. Kahi per bhul connection hoga. .Full load ka kam se kam 20% load rahne per hi capacitor bank automatically start hota hai
@@JigyasaElectricals Sir Syd yahi problem he . Mera apfc panel 15 kw ka he aur me testing kr rha hu total 3 motor ( total 3 kw ) at no load , Meri apfc relay sahi work kr rhi he But thodi der baad "CURR: Phase current error " likha aa jata he
@@JigyasaElectricals Sir , Mene 30 kw ke apfc panel ko 5 kw ke load prr test kiya Power factor " 0.6 " se upar nhi jaa rha he aur all capacitor ON hoo gae What is the problem ? Please Reply
superb, superb explain to topic with practical example. and very deeply information.
Veri veri good sir aise hi sir sapot karte rahe thanks sir
Brother your hindi explain is superb. I don't know hindi, but fully understand the everything.. Best wishes for keep up your good work..
Yutube per bahut se log control wiring diagram banakar dikha to dete hai lekin apke jaise Samjha nahi pate hai.
Thank you very much 🙏
Supper clear voice and 100% very nice video.sir up ko hum 100000 like dediya
nice videos and good presentation keep up the good work make a more videos..
Beautiful sir🎉thanks for explaining
Bhai aap ke jaisa vedio koi nahi banata Or v alalg alag type ke pannel ka wiring digram bato sir thnaks
Very nice video sir
Thank you
Very nicely Explained 💯💯💯
Vv nice bro
Wow!! So nice presentation
Thenks. Appka. Bidio. Bahut. Acha. Laga
Very good presentation thank you sir
Sir apne digram banakar bahut Achche tarike se samjhaya hai ki power supply kaise Kaise jayegi jiske karan Sara confusion dur ho gaya
Baah! Baah! You explained very nicely. Anyone can understand that. That's why, I demand to you a video on APFC Panel in where Thyristor is used. Please do that with 2d drawing and practically. Please please.
Ok
Thank you sir. You are the mentor of us.
Superb one keep on explaining such concept which will clear our doubts easily
Clear Cut presentation...thank you.
keep it up very nicely present the control wiring and actual display of APFC panle. Please make vdo on how to calculate the KVAr rating for PF from 0.5 to 0.99 to design APFC panel
Ok I ll do very soon
Kvar = KW (tan@1-tan@2)
Suppose pf1= .80 ansPf2=.0.98
Kvar = 100kw×{.060}
= 60 kvar capacitor
@@sunilsahu2525qqqqq
Good daigaram
Very clear good job well done
Very good explanation
Thank you for valuable information..
Very good
Excellent
Well explained
Good explanation
Very nice bro
Good vedio very nice
Very nice
Super bhai
Thanks 🙏
Sir Ek simocode based BDOL starter ki pawer and control wiring par video banaiye
Ok bro
Nice sir
Kindly make a video of APFC program
nice video...
One thing that is missing ,auto contactor and manual contactor . In circuit diagram it is mentioned but in the real presentation of APFC it is missing.
Sir app jo dekhayea power wiring samjgya... Control wiring practically samjhao
Bhut.khoob.sir.aap.kaha.work.karte.hai.
Hyderabad,😊😊
Nice
1200 k v r ke bar me 1 video bano sir ji
Sure
Good
Sir isme reactor ka use kyu kiya hai
Uski kya jarur hai
Pls uspe ak video banaaye
Why capacitor duty contactor 3phase looping with add on block
Ise demping resistor kahte hai.
Smooth switching karane ke liye ham log iska istemal karte hain Kyunki Jab capacitor start hota hai to Jyada current leta hai aise Mein capacitor aur contactor donon ko hi damage hone ka khata rahata hai. Ye ek heavy duty contactar hai jo ki bhut costly aata hai. Isliye jab contactor me jyada current paas karta hai us samay ye current ko resistor karta hai jisase contactar jyada current flow hone par kharab hone se bach jata hai
Zakkkaaaaasssssss bossssss
11kv power distribution system
Sir power control panel ka video banayiye na please please please please please
Ok I ll make
Hello sir
Hello
sir, 5 stage may work krayangay to kaya auto contactor ek hi denay say work kar kayayga
PLC and cancer k bary me samja do
Sir hamare yaha 20 kvar reactor lagaya he aur out put me 20 kvar L & Tsuper heavy duty 480 capacitor lagaya he hya. Kya me L &T ke jagah koi dusra 480 v ya 525 volt capacitor laga sakte he kyu ki L & T ka capacitor mil nahi Raha he kya me epcos ka use kar sakta hu??? Pls reply
Sir Ghar k lea use kr sakta hai 7kva k load k lea .
Mujeeb electric
Please sir
automatic mode pe relay se CDC ke A1 terminal pe direct connection nhi ho skti? qki CDC bhi contactor ke jesa hi to work karta h? agr hm capacitor bank lgate h to jis number ka relay on hoga us number ka CDC?
O k
Sir I have a question, capacitor is connected between the source and final load. How is it connecting to the final load
What if I have 4 capacitors how will I loop the A1 and A2 if the Mc and CDC Auxiliary
Neutral not connected with rely?
Not required
sir jee
mai electrician hu. bahut jagaha mai dekh raha hu. capacitor sehi hai, but reactor bahut heat hai.
1.reactor kiu heat hota hai
2.reactor se kiu sound ata hai
3.reactor test karneka prossess keya hai
please sir RUclips mai bahut search kiya nehi mila. mughe janna hai?
Hi
Hello
🙏🙏🙏🙏👍✅👌👌👌👌👌🖥️
Agar isme reactor nai lagaye ge to kya hoga???
All circuit right but normally contactor besd. it mince. this work normal riley efinitely working ok. So auto an manual function opreting. this contractor very wrong.....
Bhai aapse baat kaise karein?
Sr
Copasitor panel to LV panel 2core ka wire kyu use hota hai kisakeliye
Good question . LT panel ke busbar ke CT se APFC relay ko connect karna parta hai.
@@JigyasaElectricals s1 s2
Thank you sr
Reactor k control wire ke bare mai nahi bole
Why CDC use...any special reason..why we cant use normal contactor
It's damping inrush current of capacitor। मतलब जब capicitor स्टार्ट होता है उस समय वह अधिक मात्रा में करंट लेता है जिससे capicitor और normal कॉन्टैक्टर जल्द ही खराब हो जाता है। cdc में damping resistor होता है जो inrush करंट को रोकता है जिससे capicitor और कॉन्टैक्टर कि लाइफ ज्यादा दिन तक रहती है।
1. Jo humne input liya he MCB me , wo khaan se liya he
aur
Main supply se kaise connect krte he?
Please sir
clear this doubt .
1 ans : apfc panel ka jo main incomer hai uske mccb ke output ke kisi bhi ek phase se MCB ka input. Le sakte ho.
Ans 2 : main electric panel ke output se apfc panel ko supply jata hai
@@JigyasaElectricals iska matlab
ki
Capacitor directly main line se attached hoote he
( Via MCB and contactor )
Main panel ke common busbar se ek feeder banao aur waha se cable ke through apfc panel ko le jaya jata hai
@@JigyasaElectricals
Thanku very much sir
U r the 1st one who replied
Mene " selec apfc 346 " relay use ki he
ON krne prr fault aa rha he
' capacitor bank is not connected '
Iska kya meaning he ?
Please
Reply
Ek baar wiring check kar ke dekho. Kahi per bhul connection hoga. .Full load ka kam se kam 20% load rahne per hi capacitor bank automatically start hota hai
@@JigyasaElectricals
Sir
Syd yahi problem he .
Mera apfc panel 15 kw ka he
aur me testing kr rha hu total
3 motor ( total 3 kw ) at no load ,
Meri apfc relay sahi work kr rhi he
But thodi der baad
"CURR: Phase current error " likha aa jata he
@@JigyasaElectricals
Sir ,
Mene 30 kw ke apfc panel ko
5 kw ke load prr test kiya
Power factor " 0.6 " se upar nhi jaa rha he
aur all capacitor ON hoo gae
What is the problem ?
Please
Reply
Manual Contecotar connection wrong
Menula me wiring rong hai
ek he phase wire se 2 supply pass out karwa rahe ho bhai ye nhi samjha aya 😂
Video time mention Karo please
Veri veri good sir aise hi sir sapot karte rahe thanks sir