ClimateMaster Code 8 How to Reset

Поделиться
HTML-код
  • Опубликовано: 7 сен 2024
  • Reset Water Source ClimateMaster

Комментарии • 20

  • @jaimegonzalez6926
    @jaimegonzalez6926 11 месяцев назад

    Good job..

  • @renecuevas4128
    @renecuevas4128  4 года назад +3

    Code 8 can be caused by unit LT 2 sensing 125 ° F for about 30 seconds or more, Due to Low Water Flow. Adjust-Check Water issue and Reset ok.

  • @renecuevas4128
    @renecuevas4128  4 года назад +2

    Code 8 is a Test Mode UPS in Memory.To Reset need take power off to board or to Heat Pump itself.

  • @renecuevas4128
    @renecuevas4128  2 года назад +1

    U P S mean Heat pump run inefficient Need better water pressure and Water Flow .if water is shut down unit will develop or deliver this Code 8

    • @downsouthrapvault
      @downsouthrapvault 2 года назад

      Do you have a phone number I can reach you on please sir? I have same unit and it’s giving me a ton of issues

    • @renecuevas4128
      @renecuevas4128  2 года назад

      ​@@downsouthrapvault I m in Florida idk where are you but yeah if I can help you is 786 390 9911 send me a text first to tell me is yours so I answered......normally I do not answer calls idk. ttul

  • @renecuevas4128
    @renecuevas4128  4 года назад +1

    This is a Water Source Heat Pump made by Climate Master Technologies.

  • @renecuevas4128
    @renecuevas4128  3 года назад +2

    Test Pins will tell you that is Reset and also no addittional Codes unless problem still exists....

  • @renecuevas4128
    @renecuevas4128  3 года назад +2

    A water temperature of 85 degrees Fahrenheit or low is ideal for Water source heat pump Operation.....anything higher most likely will create this condition Adjust water Temp by Adjusting Main Variable Speed Tower Fan.at Roof Location. If too fast or too slow will determine Cooling Tower efficiency or DE fficiency

    • @jessevega4484
      @jessevega4484 3 месяца назад

      awesome information, I just got my 20-year cooling tower to work correctly to many hands touching it before and now my 20-year-old units are shutting off at night. will check Thermistor and temp then look into water temp from cooling tower thanks to your information.

  • @TheHoppala007
    @TheHoppala007 3 года назад +1

    Hi Rene , greeting from Turkey. can I replace the ( Model is TCH036. ) CXM board with DXM2 board by only unplug approprate cable from CMX and move it to appropriate location in DMX2 ? or do we need to program it as well ? I have almost no exprience with heat pump but I can move the cable from CXM to DXM2 ! :-D I find a THC036 for 500 USD but this TCH 036 is Water to Air unit. My plan is modify it water to water unit. ( by just changing Air coil with Coax one and run it without too much problem. Not sure if I am a dreamer with my limited knowedge but I am willing to do :- ))) I want to have simple, easy to repair and cheap heat pump :-D

    • @renecuevas4128
      @renecuevas4128  3 года назад

      To be honest here in America we bypass the board after is not under warranty anymore,,,we use simple relays 24 volts to 240 v. And we just add a Lock out relay that s how we get rid of this 300 doll board....it takes about 10 to 15 min All u need is a relay or two and a lock out relay....use a 3 amp fuse so u save the board just in case😀

    • @renecuevas4128
      @renecuevas4128  3 года назад

      TCH here in Florida is not used as much as Up north Usa

    • @renecuevas4128
      @renecuevas4128  3 года назад

      Before going to water to water conversion you must have enough water flow between 6 to 10 gal per min some bldg s here in America have 8 to 12 or better water flow. The more water u run the better it cools

  • @renecuevas4128
    @renecuevas4128  3 года назад +2

    Si necesitas ayuda en Espanol ,Ruso, Italiano, Estoy disponible en Los comentarios. Если у вас есть вопросы. Мена вам поможет. Давай. Пока пока большое спасибо тебе

    • @milcitrex
      @milcitrex 3 года назад +1

      Cuando te refieres a bajo flujo de agua te refieres al condensador?

    • @renecuevas4128
      @renecuevas4128  3 года назад +1

      @@milcitrex Hola Luis so no hay suficiente flujo de Agua de Galones por minuto la maquina se apaga y numerous 2 si el Agua de condensacion no sale para afuera. O sea sino desagua bien La unidad con su sensor corta la corriente y se Apaga

    • @milcitrex
      @milcitrex 3 года назад

      @@renecuevas4128 I get it!

  • @juanc9645
    @juanc9645 Год назад

    Rene. Como estas? Oye como resetear slow flash fualt relay en un climate master