Heat Pump 06 Fixed orifice metering device

Поделиться
HTML-код
  • Опубликовано: 28 мар 2023
  • Heat pumps have 2 metering devices but only 1 is used at a time.
    First lets discuss the Fixed orifice metering device.

Комментарии • 20

  • @jtopp86
    @jtopp86 Год назад +7

    everyone should pay very close attention, Ty is an unselfish resource that doesn't come along often.

  • @markblevins1521
    @markblevins1521 3 месяца назад +2

    I learn so much from your videos it's the way you explain makes. It user friendly

    • @love2hvac
      @love2hvac  3 месяца назад

      Thank you mark! That's the motivation I needed today!

  • @mark.r8900
    @mark.r8900 Год назад +5

    You Sir are one of the best hvac instructors. You make everything simple to understand and to the point. Thanks

    • @love2hvac
      @love2hvac  Год назад

      Wow, thanks!
      I appreciate that!

  • @johncarr123
    @johncarr123 9 месяцев назад +1

    Wow great lesson. It sucks that we have companies that do improper installations. I had a new compressor installed and evap coil. They forgot to install the metering orifice device and the compressor ran for 3 months with out the metering orifice. The old evap coil had a TXV valve. They should have installed a TXV valve not a fixed orifice. My new system is so screwed up now. The tech installed the missing orifice by opening the line and he did not evac the system and just added freon. I am going to demand they replace everything.

  • @Keith_Mikell
    @Keith_Mikell 11 месяцев назад +1

    Youre awesome at what you do Ty. I bet you could teach this 42 year old autistic person to do hvac youre that good. (i can be tough to teach). But i do learn well. all love. Youre a pure soul.

    • @love2hvac
      @love2hvac  11 месяцев назад +1

      Thanks!
      Autistic people do really well because of their general attention to detail. HVAC has a lot of details and career paths.
      I can be tough to teach myself. Many times its easier for me to learn on my own with resources. It takes me a while sometimes but once I understand it, I have it forever. ADHD is my superpower.
      I appreciate the kind words!

    • @Keith_Mikell
      @Keith_Mikell 11 месяцев назад

      @@love2hvac yes sir. Thank you for staying true to the trade. To wanting to help others learn and not just pile cash and try to be famous in the hvac space. That means a lot.

  • @920HVAC
    @920HVAC Год назад +2

    Another great informative video Ty! Thank you.🤝

  • @arealmaintenanceandrepairl1103
    @arealmaintenanceandrepairl1103 10 месяцев назад +1

    I wonder if u could use the king valve as a listing ?

  • @WallaceRoseVincent
    @WallaceRoseVincent 29 дней назад +1

    Are there upgrade kits to replace the piston for a direct txv replacement?

    • @love2hvac
      @love2hvac  29 дней назад +1

      Yes, almost every manufacture makes a TXV upgrade kit. There are also universal kits too!

  • @mikeperez4490
    @mikeperez4490 4 месяца назад +1

    Hello TY, need your input on a issue. I have my home AC pumping down when in heat mode. What is causing this ? Im not sure and don’t want ro start changing parts i dont need too. Thanks in advance.. AC model Payne PH3ANA036-C

    • @love2hvac
      @love2hvac  4 месяца назад +1

      Sounds like the indoor check valve is stuck closed

    • @mikeperez4490
      @mikeperez4490 4 месяца назад

      Sounds good, i will try getting this replaced and see how it goes. I didn’t think of that. Thanks for your quick response.. 🙏🏼🙏🏼

  • @fsotomayor96
    @fsotomayor96 Год назад +1

    Are still teaching at ATI?

    • @love2hvac
      @love2hvac  Год назад

      No.
      ATI in in Miami got shut down,
      ATI in las Vegas I left about 6 years ago.