ASTM C1064 - ACI Concrete Temperature Test 2019

Поделиться
HTML-код
  • Опубликовано: 22 май 2019
  • Temperature of Freshly Mixed Hydraulic-Cement Concrete
    ACI Technician Workbook CP-1
    ------------------------------------------------------------------
    * Temperature Measuring Device (TMD) Requirements *
    The thermometer in use must adhere to the following requirements:
    - Measure to within +/- 1 degree Fahrenheit
    - Measuring device must read between 30 to 120 degrees
    - Have 3-inches concrete cover in all directions
    - Be inserted a minimum of 3-inches
    - Be left in concrete a minimum of 2 min., maximum of 5 min.
    - Be calibrated annually, or if there’s a question of accuracy
    - Not vary by more than 1 degree Fahrenheit when verified against a reference thermometer
    ------------------------------------------------------------------