I love how effeciently you’re able to diagnose and know what to look for. I can’t wait till I have that much knowledge and experience at calls like these. I don’t get to see roof tops too often
Great Video Ryan! Yes the facilities companies do like to repair. That’s fine with me as it’s hob security. Been dealing with gas and go bandits lately in PM’s. Airflow good, condensor clean( cause I cleaned it) check charge and psi’s are running high. Recover about a pound of refrigerant and voila running like a champ. This has happened on 3 units in the last week. 🤦♀️ SMH
I like the advice when wondering about a shorted compressor to simply remove the wires and isolate them from the compressor. Then reset the breaker. If it doesn't blow you have a bad compressor. Wouldn't help here without the fuses but for residential pretty fast, easy, and decisive.
It’s a good start, but that’s not always the case. I had a tripped breaker on a condenser and did the same thing. But before condemning the compressor I checked the capacitor and it turned out to be the bad. Something told me to check it out even though it looked brand new. I swapped it out and everything ran smoothly. If I had not checked it I would’ve quoted a new compressor along with a new capacitor and never would have known the difference.
I love how effeciently you’re able to diagnose and know what to look for. I can’t wait till I have that much knowledge and experience at calls like these. I don’t get to see roof tops too often
Thanks for watching man
Jersey mikes is my favorite! Stop there atleast once a week on the way home!
#43 and #8 are my go to subs
That rtu needs the works.
The whole shabang!
That unit is gonna get it Mike's Way....The Works! 💪😎👍
😂
Your making me hungry
Great Video Ryan! Yes the facilities companies do like to repair. That’s fine with me as it’s hob security. Been dealing with gas and go bandits lately in PM’s. Airflow good, condensor clean( cause I cleaned it) check charge and psi’s are running high. Recover about a pound of refrigerant and voila running like a champ. This has happened on 3 units in the last week. 🤦♀️ SMH
Thanks brother
Nice troubleshooting Ryan ... Thx 🍺
Thank you Eddy!
Great Video. Good job and Nice work. Thank you for sharing
Great job talking us through the steps. Learned a lot.
Thanks!
It's always a rough day Ryan, always a rough day.
Always! 😂
Best thing you said had to stop at jersery mikes 😂 that’s my place man food is amazing
Love it!
Nice troubleshooting! I appreciate your videos.
Thanks man! That means a lot!
“It’s testing good”… ah shorted to ground 😂 good diagnosis man!
Wow same day you posted this I had a shorted compressor!
No way!
Can you pls do a video on how to wire a smoke detector
I like the advice when wondering about a shorted compressor to simply remove the wires and isolate them from the compressor. Then reset the breaker. If it doesn't blow you have a bad compressor. Wouldn't help here without the fuses but for residential pretty fast, easy, and decisive.
For sure
It’s a good start, but that’s not always the case. I had a tripped breaker on a condenser and did the same thing. But before condemning the compressor I checked the capacitor and it turned out to be the bad. Something told me to check it out even though it looked brand new. I swapped it out and everything ran smoothly. If I had not checked it I would’ve quoted a new compressor along with a new capacitor and never would have known the difference.
Can you please give me the name of your gloves I need some seriously
Harbor freight gloves
Good one Ryan
Thanks Greg!
Where’d you get the music that slowly comes in towards the end? I’d love to have something like that in my vids.
No copyright claims?
Epidemic sound
Kicking ass and taking names huh... HvacRookie
Thanks Scott
A bad day in Black Rock😮
Thanks for watching
Great video Ryan
Thanks Randy
@@HughesManHVAC your welcome
Good videos but lose the music.
Man just replace the whole unit at that point
Right! Wish it was that easy! These facilities companies love to repair! $$$
only wanna know one thing what kind of sub was that????
#8 club
# 5 hold the Juice :)@@HughesManHVAC
103 thumbs up
Appreciate it Steve!
Acid test
Yep
Nice troubleshooting video ! Did you find any tools ? 😂🔧 🪛 🔨
No unfortunately. Definitely would have included that in the video