HVAC Service Call: LG MULTI V 4 Error Code CH26 Repair (Inverter Compressor Overcurrent) CH29 Error

Поделиться
HTML-код
  • Опубликовано: 22 окт 2024
  • HVAC Service Call: LG MULTI V 4 Error Code CH26 Repair (Inverter Compressor Overcurrent) LG MULTI V IV Compressor & Inverter Board Replacement (LG MULTI V 5 Repair) HVAC(Heating, Ventilation, Air Conditioning) Service Call: LG Multi V IV Error Code CH29 (Inverter Compressor Over Current) Error Code 291 / LG MULTI V 5 ERROR CODE CH29 - Outdoor Unit Inverter Compressor Over Current ( Outdoor Unit Inverter Compressor Fault Or Drive Fault) LG Troubleshooting / HVAC VRF VRV Training #HVAC #LG #JUMPERMANTECH
    GoPro HERO8 Black (Camera Used In This Video)
    amzn.to/3q4FmEz
    Veto Pro Pac TECH MC
    amzn.to/3gURJyZ
    Fluke 902 FC HVAC True-RMS Clamp Meter
    amzn.to/39wvwiK​​
    Fieldpiece ADK7 Deluxe Silicone Test Lead Kit
    amzn.to/3VNYXDv
    Klein Tools ET600 Megohmmeter Insulation Tester
    amzn.to/409iNvu
    Supco M500 Insulation Tester/Electronic Megohmmeter
    amzn.to/42oy0ua
    Fluke 1AC-A1-II VoltAlert Non-Contact Voltage Tester
    amzn.to/3FcWElQ
    Fieldpiece JL3KR4 HVACR Charge Kit (Digital Gauges/Probes)
    amzn.to/3E4W0Fr
    Fieldpiece SPK2 Folding Pocket In-Duct Thermometer
    amzn.to/3mi8Fih
    Fieldpiece SPK3 Folding ROD Dual Temperature Thermometer
    amzn.to/3FbDufQ
    Milwaukee M12 2-Tool Combo Kit 2598-22
    amzn.to/3CtCRNC
    Milwaukee Cut 1 Dipped GLOVES L
    amzn.to/3s8H18O​
    Milwaukee 2351-20 M12 LED Stick Light
    amzn.to/3rVJKEK
    Milwaukee 48-22-1985 Fastback Hawk Bill Folding Knife
    amzn.to/3e53ygW
    Milwaukee 48-22-1500 Fastback Compact Folding Utility Knife
    amzn.to/3qazJkC
    Milwaukee 48-22-4041 Iron Carbide Core Large-Looped Jobsite Scissors
    amzn.to/32fxC6I
    Milwaukee 4932459097 Billet Torpedo Level
    amzn.to/30Dh6Nw
    Milwaukee Wide Blade Magnetic Tape Measure 16 FT
    amzn.to/3yEN7kL
    Milwaukee Fine Pt. Markers Black
    amzn.to/3e4fH5W
    Streamlight 66604 MicroStream USB 250-Lumen Rechargable Pocket Flashlight
    amzn.to/320XiEF
    Klein Tools 11-in-1 Screwdriver / Nut Driver
    amzn.to/3s3o8ql
    Klein Tools 32561 Multi-Bit Screwdriver / Nut Driver 6-in-1
    amzn.to/3e4ur4x
    Klein Tools 32807MAG 7-in-1 Nut Driver, Magnetic Driver
    amzn.to/321n4bW
    Klein Tools 600-4 1/4-Inch Keystone Cushion-Grip Screwdriver
    amzn.to/3J11hS1
    Klein Tools 32581 4-in-1 Electronics Screwdriver Set
    amzn.to/3yEj3WC
    Klein Tools LLK12 L-Style Hex Key Caddy Set 12-Piece (Metric/Sae)
    amzn.to/3yRUiGJ
    Yellow Jacket 18975 Charge Tool
    amzn.to/3J4pfvJ
    Yellow Jacket 60613 Service ratchet Wrench
    amzn.to/3E8iYeZ
    Yellow Jacket 19173 5/16" Female Quick Couplers x 1/4" Male Flare
    amzn.to/3q0TQ4M
    Cooper Bussmann BP-FP-2 Cartridge Carded Fuse Puller
    amzn.to/3e0USrY
    Crescent 2 Pc. X6 4-in-1 Black Oxide Spline Ratcheting SAE Wrench Set
    amzn.to/3qqKlw7
    Crescent 4" Adjustable Cushion Grip Wrench
    amzn.to/3J4qsmL
    Knipex 09 08 240 SBA 9.5-Inch Insulated Ultra-High Leverage Lineman's Pliers (1000v)
    amzn.to/30EQmw5
    Knipex 09 11 240 9.5-Inch Ultra-High Leverage Lineman's Pliers with Fish Tape Puller and Crimper
    amzn.to/3H9iYAu
    KNIPEX Tools - Long Nose Pliers With Cutter, 1000V Insulated
    amzn.to/3e3IEi7
    KNIPEX Tools - Long Nose Pliers With Cutter
    amzn.to/3gUSE2i
    KNIPEX Tools 98 62 02, Flat Nose Plastic Pliers 1000V Insulated
    amzn.to/3p6lFsZ
    KNIPEX - 74 08 200 - High Leverage Diagonal Cutters, 1000V Insulated
    amzn.to/3mh8K5U
    KNIPEX - 74 01 200 Tools - High Leverage Diagonal Cutters
    amzn.to/3F1VScb
    KNIPEX Tools - Cobra QuickSet Pump Pliers, 1000V Insulated
    amzn.to/3sftr5Q
    KNIPEX Tools 3 Piece Cobra Pliers Set
    amzn.to/3FbRwy7
    KNIPEX Tools Pliers Wrench 3-Piece Set
    amzn.to/3nnRLfW

Комментарии • 40

  • @dimaslespier2688
    @dimaslespier2688 Год назад +12

    Hey jumper man. Hope all is well. In my experience of dealing with LG Multi and Mitsubishi or. Daikin. When you lose that many compressors and or vfd compressors boards. We always find that in the original installation. Either there is a trap situation in which how the air handler piping was done has crated a trap not allowing oil to return back to the compressors causing the compressors to over heat. Same with lack of suction super heat via short of refrigerant. Turn the old compressor over see how much oil comes out. That will tell you. But definitely go over every inch of the piping. One to check for traps two to measure proper charge.

  • @huntergx6581
    @huntergx6581 Год назад +2

    Hello, your work is very excellent and professional. I work in this field. Regarding your question regarding this building, the main reason for these problems in the system is poor installation, and the most important reason may be welding without nitrogen and errors in the process of installing copper pipes. Thank you.

  • @Rodj12341
    @Rodj12341 Год назад +3

    Might be beneficial to enable the Forced Oil Return mode in the ODU's by turning on DIP switch 5 -> Go to SVC mode -> Enable SE 5 by setting it to 01 instead of oFF. This forces the unit to perform the oil return operation to the ODU if the oil level sensor ever reads low.

  • @sparkytech8787
    @sparkytech8787 Год назад +2

    Those condensers look extremely close, I wonder when they run at the same time airflow is compromised, this could be something you could consider, I've had the issue before.

  • @scottmaz4063
    @scottmaz4063 Год назад +2

    You are definitely the man, great job.

  • @vinhle7246
    @vinhle7246 Год назад

    Hi I very like your video , and can you let me know : First time you open the liquid side charging refrigerent into the unit , untill when you turn the unit on , and continous charging till the end , can you explains more detail about that ? Thanks

  • @electroshed
    @electroshed Год назад

    I told you in the last video that another one of those LG's was plotting it's failure haha - wonder if you can get some kind of data logger from LG to record all sensor readings during a typical hot and cold day to see if anything comes back as risky to system health?

  • @Superman3638
    @Superman3638 Год назад

    Since you add new refrigerant, what do you do with the old recovered refrigerant?

  • @Nabinmagar-vz6to
    @Nabinmagar-vz6to 13 дней назад

    nice work and where are you from

  • @kennethlobo4420
    @kennethlobo4420 Год назад

    Great video, waiting to hear from tech support, just a point which comes to mind is there a considerable drop in voltage when the unit is running?

    • @electroshed
      @electroshed Год назад

      Wires entering the unit look rather thin compared to the wires within the unit itself, post incoming supply terminal block.

  • @sunny_empire
    @sunny_empire Год назад

    That's an excellent job! You made mention of lgtechsupport, can you just give a link to the material given to you, I want to go through it for better understanding and lg phone number?

  • @anthonyc826
    @anthonyc826 Год назад

    I work with a lot of LG. Do they have oil traps on the roof. Take a minute to pull up the installation manual. Read regarding piping. Inspect the piping open up some ceiling access and locate the BCs see if piping is incorrect. Maybe one of the indoor units exceeds the pipe length. Once you get all the info and have some sort of idea how the installation is. Call Lg and explain to them

  • @DelticEngine
    @DelticEngine Год назад +1

    Thanks for a very interesting video! You did a great job with the thermal transfer compound.; that should work very well transferring heat. From the Service Manual, the board you replaced is the Converter Board not the Inverter Board. The Converter Board converts the incoming AC to DC to be passed on to the compressor and fan Inverter Boards. Is it possible that a bad Inverter Board for the Compressor is causing both the Compressor and Converter Board to fail?
    I also have another thought that came from what you discovered with the strainers outside the units with nothing left inside. Having a look through the hydraulic diagrams shows six internal strainers. If the external protection is non-existent then is there some clogging of any strainers internally? This is assuming that the pipework with the strainers in that condition is used by this particular system, or at all.
    Thinking about compressor lubrication, are the Strainer and Solenoid Valve in the Oil Return line between the Accumulator Receiver and the Compressor both functioning as they should? Is the Check Valve between the Oil Separator and Compressor working correctly allowing oil to return to the compressor? If it is not then is too much oil entering the main pipework and starving the compressor?
    According to the service manual I found, there are two oil return systems:
    - A high pressure centrifugal one that returns oil to the compressor through its own injector pipe which prevents mixing of oil and refrigerant on the suction side of the compressor.
    - There is also a Smart Oil Control system that monitors the oil level inside the compressor and initiates an oil return cycle to the Compressor when the oil level is too low. Timed cycles are unnecessary and the Compressor is protected from running with too low an oil level.
    Is it possible, given there was oil in strainers you found, that there is a fault in the Smart Oil Control system such as the functioning of the return cycle?
    I hope my thoughts and ideas may be of some help to you. Best regards and I wish you success in finding a solution.

    • @AdolfoAscanio-f7i
      @AdolfoAscanio-f7i 7 месяцев назад

      Where l can find information over this system

  • @carloscetz8314
    @carloscetz8314 Год назад +1

    Is a good idea to probably get an LGMV Module to see what the system is doing.

  • @scottk0623
    @scottk0623 Год назад

    What was the total hours you had from start to finish? Nice job👍

  • @aquaticspecialities5382
    @aquaticspecialities5382 Год назад +2

    Getting pretty good at this 😂 good job man.

  • @izzybell11
    @izzybell11 Год назад

    Great job JMT. Thanks for sharing w us this interesting and helpful vid. 👏

  • @johnwalker890
    @johnwalker890 Год назад

    Good job Jumper.

  • @thesilentonevictor
    @thesilentonevictor Год назад

    Jmt love this job site always fun to change compressor and inverter boards 😂 master tech

  • @jrh86
    @jrh86 Год назад +2

    By the way great Job again 👍👍👍

  • @UnaiExtremo
    @UnaiExtremo Год назад

    Check the section of the input wires to the machine, it seems that the section is too small and that is where the problems with that equipment can come from.

  • @zekenzy6486
    @zekenzy6486 Год назад

    Great Video. Thank you for sharing

  • @davefeely2101
    @davefeely2101 Год назад

    Good job Superman Teck

  • @svdleer
    @svdleer Год назад

    Honeyyyy, i'm back!

  • @carlpoole1686
    @carlpoole1686 Год назад

    Depends when the compressor was manufactured. LG compressors has plastic parts inside which collapse when there is no perfect world. They aren't as good as tecumseh

  • @JohnDoe-ej1lw
    @JohnDoe-ej1lw Год назад

    Great job JMT
    Love your vids!

  • @nicolerennie
    @nicolerennie Год назад +1

    👏🏼👏🏼👏🏼

  • @Practicing_HVACR
    @Practicing_HVACR Год назад

    What meggohm readings did you have?

  • @jrh86
    @jrh86 Год назад

    My thoughts as well re Dimas comments.

  • @kamechanicalhvac2891
    @kamechanicalhvac2891 Год назад

    Great video brother !!!!

  • @briancarlisi2224
    @briancarlisi2224 Год назад +2

    Leave the jacket off. It just suppresses the compressor noise which should not be an issue on the roof. May be contributing to compressor overheating.

    • @richardbartlett6932
      @richardbartlett6932 Год назад +1

      Compressors are designed to run with the jacket on. The cooling is done by the suction gas. The jacket protects from the cold along with the cch.
      Taking the jacket off isn't going to solve or help
      This is an oil return issue. It needs a full survey and probably re-piping

  • @m_abbas1991
    @m_abbas1991 Год назад

    Maybe they are very close to each other

  • @67tr876
    @67tr876 Год назад

    Nicee!!!

  • @prowesstv
    @prowesstv Год назад +1

    At this point this Model seems like it's problematic 😅

  • @abdullah_q8171
    @abdullah_q8171 Год назад

    Vrf always compresses damage..