HVAC Service Call: LG MULTI V 4 Error Code CH26 Repair (Inverter Compressor Overcurrent) CH29 Error
HTML-код
- Опубликовано: 22 окт 2024
- HVAC Service Call: LG MULTI V 4 Error Code CH26 Repair (Inverter Compressor Overcurrent) LG MULTI V IV Compressor & Inverter Board Replacement (LG MULTI V 5 Repair) HVAC(Heating, Ventilation, Air Conditioning) Service Call: LG Multi V IV Error Code CH29 (Inverter Compressor Over Current) Error Code 291 / LG MULTI V 5 ERROR CODE CH29 - Outdoor Unit Inverter Compressor Over Current ( Outdoor Unit Inverter Compressor Fault Or Drive Fault) LG Troubleshooting / HVAC VRF VRV Training #HVAC #LG #JUMPERMANTECH
GoPro HERO8 Black (Camera Used In This Video)
amzn.to/3q4FmEz
Veto Pro Pac TECH MC
amzn.to/3gURJyZ
Fluke 902 FC HVAC True-RMS Clamp Meter
amzn.to/39wvwiK
Fieldpiece ADK7 Deluxe Silicone Test Lead Kit
amzn.to/3VNYXDv
Klein Tools ET600 Megohmmeter Insulation Tester
amzn.to/409iNvu
Supco M500 Insulation Tester/Electronic Megohmmeter
amzn.to/42oy0ua
Fluke 1AC-A1-II VoltAlert Non-Contact Voltage Tester
amzn.to/3FcWElQ
Fieldpiece JL3KR4 HVACR Charge Kit (Digital Gauges/Probes)
amzn.to/3E4W0Fr
Fieldpiece SPK2 Folding Pocket In-Duct Thermometer
amzn.to/3mi8Fih
Fieldpiece SPK3 Folding ROD Dual Temperature Thermometer
amzn.to/3FbDufQ
Milwaukee M12 2-Tool Combo Kit 2598-22
amzn.to/3CtCRNC
Milwaukee Cut 1 Dipped GLOVES L
amzn.to/3s8H18O
Milwaukee 2351-20 M12 LED Stick Light
amzn.to/3rVJKEK
Milwaukee 48-22-1985 Fastback Hawk Bill Folding Knife
amzn.to/3e53ygW
Milwaukee 48-22-1500 Fastback Compact Folding Utility Knife
amzn.to/3qazJkC
Milwaukee 48-22-4041 Iron Carbide Core Large-Looped Jobsite Scissors
amzn.to/32fxC6I
Milwaukee 4932459097 Billet Torpedo Level
amzn.to/30Dh6Nw
Milwaukee Wide Blade Magnetic Tape Measure 16 FT
amzn.to/3yEN7kL
Milwaukee Fine Pt. Markers Black
amzn.to/3e4fH5W
Streamlight 66604 MicroStream USB 250-Lumen Rechargable Pocket Flashlight
amzn.to/320XiEF
Klein Tools 11-in-1 Screwdriver / Nut Driver
amzn.to/3s3o8ql
Klein Tools 32561 Multi-Bit Screwdriver / Nut Driver 6-in-1
amzn.to/3e4ur4x
Klein Tools 32807MAG 7-in-1 Nut Driver, Magnetic Driver
amzn.to/321n4bW
Klein Tools 600-4 1/4-Inch Keystone Cushion-Grip Screwdriver
amzn.to/3J11hS1
Klein Tools 32581 4-in-1 Electronics Screwdriver Set
amzn.to/3yEj3WC
Klein Tools LLK12 L-Style Hex Key Caddy Set 12-Piece (Metric/Sae)
amzn.to/3yRUiGJ
Yellow Jacket 18975 Charge Tool
amzn.to/3J4pfvJ
Yellow Jacket 60613 Service ratchet Wrench
amzn.to/3E8iYeZ
Yellow Jacket 19173 5/16" Female Quick Couplers x 1/4" Male Flare
amzn.to/3q0TQ4M
Cooper Bussmann BP-FP-2 Cartridge Carded Fuse Puller
amzn.to/3e0USrY
Crescent 2 Pc. X6 4-in-1 Black Oxide Spline Ratcheting SAE Wrench Set
amzn.to/3qqKlw7
Crescent 4" Adjustable Cushion Grip Wrench
amzn.to/3J4qsmL
Knipex 09 08 240 SBA 9.5-Inch Insulated Ultra-High Leverage Lineman's Pliers (1000v)
amzn.to/30EQmw5
Knipex 09 11 240 9.5-Inch Ultra-High Leverage Lineman's Pliers with Fish Tape Puller and Crimper
amzn.to/3H9iYAu
KNIPEX Tools - Long Nose Pliers With Cutter, 1000V Insulated
amzn.to/3e3IEi7
KNIPEX Tools - Long Nose Pliers With Cutter
amzn.to/3gUSE2i
KNIPEX Tools 98 62 02, Flat Nose Plastic Pliers 1000V Insulated
amzn.to/3p6lFsZ
KNIPEX - 74 08 200 - High Leverage Diagonal Cutters, 1000V Insulated
amzn.to/3mh8K5U
KNIPEX - 74 01 200 Tools - High Leverage Diagonal Cutters
amzn.to/3F1VScb
KNIPEX Tools - Cobra QuickSet Pump Pliers, 1000V Insulated
amzn.to/3sftr5Q
KNIPEX Tools 3 Piece Cobra Pliers Set
amzn.to/3FbRwy7
KNIPEX Tools Pliers Wrench 3-Piece Set
amzn.to/3nnRLfW
Hey jumper man. Hope all is well. In my experience of dealing with LG Multi and Mitsubishi or. Daikin. When you lose that many compressors and or vfd compressors boards. We always find that in the original installation. Either there is a trap situation in which how the air handler piping was done has crated a trap not allowing oil to return back to the compressors causing the compressors to over heat. Same with lack of suction super heat via short of refrigerant. Turn the old compressor over see how much oil comes out. That will tell you. But definitely go over every inch of the piping. One to check for traps two to measure proper charge.
Valuable advice
Hello, your work is very excellent and professional. I work in this field. Regarding your question regarding this building, the main reason for these problems in the system is poor installation, and the most important reason may be welding without nitrogen and errors in the process of installing copper pipes. Thank you.
Might be beneficial to enable the Forced Oil Return mode in the ODU's by turning on DIP switch 5 -> Go to SVC mode -> Enable SE 5 by setting it to 01 instead of oFF. This forces the unit to perform the oil return operation to the ODU if the oil level sensor ever reads low.
Those condensers look extremely close, I wonder when they run at the same time airflow is compromised, this could be something you could consider, I've had the issue before.
You are definitely the man, great job.
Hi I very like your video , and can you let me know : First time you open the liquid side charging refrigerent into the unit , untill when you turn the unit on , and continous charging till the end , can you explains more detail about that ? Thanks
I told you in the last video that another one of those LG's was plotting it's failure haha - wonder if you can get some kind of data logger from LG to record all sensor readings during a typical hot and cold day to see if anything comes back as risky to system health?
Since you add new refrigerant, what do you do with the old recovered refrigerant?
nice work and where are you from
Great video, waiting to hear from tech support, just a point which comes to mind is there a considerable drop in voltage when the unit is running?
Wires entering the unit look rather thin compared to the wires within the unit itself, post incoming supply terminal block.
That's an excellent job! You made mention of lgtechsupport, can you just give a link to the material given to you, I want to go through it for better understanding and lg phone number?
I work with a lot of LG. Do they have oil traps on the roof. Take a minute to pull up the installation manual. Read regarding piping. Inspect the piping open up some ceiling access and locate the BCs see if piping is incorrect. Maybe one of the indoor units exceeds the pipe length. Once you get all the info and have some sort of idea how the installation is. Call Lg and explain to them
Thanks for a very interesting video! You did a great job with the thermal transfer compound.; that should work very well transferring heat. From the Service Manual, the board you replaced is the Converter Board not the Inverter Board. The Converter Board converts the incoming AC to DC to be passed on to the compressor and fan Inverter Boards. Is it possible that a bad Inverter Board for the Compressor is causing both the Compressor and Converter Board to fail?
I also have another thought that came from what you discovered with the strainers outside the units with nothing left inside. Having a look through the hydraulic diagrams shows six internal strainers. If the external protection is non-existent then is there some clogging of any strainers internally? This is assuming that the pipework with the strainers in that condition is used by this particular system, or at all.
Thinking about compressor lubrication, are the Strainer and Solenoid Valve in the Oil Return line between the Accumulator Receiver and the Compressor both functioning as they should? Is the Check Valve between the Oil Separator and Compressor working correctly allowing oil to return to the compressor? If it is not then is too much oil entering the main pipework and starving the compressor?
According to the service manual I found, there are two oil return systems:
- A high pressure centrifugal one that returns oil to the compressor through its own injector pipe which prevents mixing of oil and refrigerant on the suction side of the compressor.
- There is also a Smart Oil Control system that monitors the oil level inside the compressor and initiates an oil return cycle to the Compressor when the oil level is too low. Timed cycles are unnecessary and the Compressor is protected from running with too low an oil level.
Is it possible, given there was oil in strainers you found, that there is a fault in the Smart Oil Control system such as the functioning of the return cycle?
I hope my thoughts and ideas may be of some help to you. Best regards and I wish you success in finding a solution.
Where l can find information over this system
Is a good idea to probably get an LGMV Module to see what the system is doing.
What was the total hours you had from start to finish? Nice job👍
Getting pretty good at this 😂 good job man.
Great job JMT. Thanks for sharing w us this interesting and helpful vid. 👏
Good job Jumper.
Jmt love this job site always fun to change compressor and inverter boards 😂 master tech
By the way great Job again 👍👍👍
Check the section of the input wires to the machine, it seems that the section is too small and that is where the problems with that equipment can come from.
Great Video. Thank you for sharing
Good job Superman Teck
Honeyyyy, i'm back!
Depends when the compressor was manufactured. LG compressors has plastic parts inside which collapse when there is no perfect world. They aren't as good as tecumseh
Great job JMT
Love your vids!
👏🏼👏🏼👏🏼
What meggohm readings did you have?
My thoughts as well re Dimas comments.
Great video brother !!!!
Leave the jacket off. It just suppresses the compressor noise which should not be an issue on the roof. May be contributing to compressor overheating.
Compressors are designed to run with the jacket on. The cooling is done by the suction gas. The jacket protects from the cold along with the cch.
Taking the jacket off isn't going to solve or help
This is an oil return issue. It needs a full survey and probably re-piping
Maybe they are very close to each other