EEV/EVX leaking by causing low superheat alarms on chiller

Поделиться
HTML-код
  • Опубликовано: 27 авг 2024
  • A look at Sporlan SERI electronic expansion valve

Комментарии • 61

  • @rookierefrigeration4357
    @rookierefrigeration4357 4 года назад +3

    Good video. Funny how the seat was worn enough to bleed by. Nice find 💪🏼💪🏼

  • @philltafolla
    @philltafolla 4 года назад +3

    Welcome back Ulises 😬😁

    • @UlisesPalacios
      @UlisesPalacios  4 года назад +2

      Felipe Tafolla haha this one was interesting and kicked my butt for a bit. Figured I would make a video so hopefully it could help out someone in the future.

    • @philltafolla
      @philltafolla 4 года назад +1

      Ulises Palacios nice . So even with the pin closed , refrigerant would still leaked by ? I’ve seen it on liquid solenoid valves , few times , since I work on smaller stuff . Good shit shout out from SoCal 😎

  • @bradmironik6137
    @bradmironik6137 4 года назад +1

    Thanks for sharing. Interesting how that works.

  • @JuanTodoli
    @JuanTodoli 4 года назад +1

    Good find Ulises 👍

  • @bmillwood6666
    @bmillwood6666 4 года назад +2

    Those exv come a part. When I installed one of those, I took them apart during welding

  • @ismackherbiehind
    @ismackherbiehind 4 года назад

    Those Veto bags are very nice. I own one and I love it.

  • @HVACRVIDEOS
    @HVACRVIDEOS 4 года назад +1

    Really interesting, it seems like it would take some serious effort to damage that seat......

    • @UlisesPalacios
      @UlisesPalacios  4 года назад

      HVACR VIDEOS yeah. I wondered that myself. They are pretty strong motors and I didn’t see any visual damage on the seat surface

    • @19thcenturyfuture
      @19thcenturyfuture 4 года назад +1

      Ulises Palacios the needle is stainless and the seat is soft brass, after time and many hard close off’s.....there ya go

    • @UlisesPalacios
      @UlisesPalacios  4 года назад

      Jake Crockett makes sense.

    • @19thcenturyfuture
      @19thcenturyfuture 4 года назад

      Ulises Palacios thanks for the vids, always enjoy

    • @UlisesPalacios
      @UlisesPalacios  4 года назад

      Jake Crockett thanks 🙏

  • @sterlingarcher46
    @sterlingarcher46 4 года назад +1

    Very interesting, mate 👍
    Hey who's the make of that EEV ?
    I'm only used to Carel and some Sporlan ones ?

    • @UlisesPalacios
      @UlisesPalacios  4 года назад

      Sterling Archer thanks. It’s a sporlan seri-j

    • @sterlingarcher46
      @sterlingarcher46 4 года назад

      @@UlisesPalacios cheers , mate , love your vids , man , fantastic job !👍👍👍

  • @whitesheatingairappliancer7101
    @whitesheatingairappliancer7101 4 года назад +2

    What voltage are you using to control the motor, 200 vdc?
    Great video thanks

  • @yl923
    @yl923 2 года назад

    where can I see the pinout of the valve connector? what pins do colored wires come to on it?

  • @creativetradesman6833
    @creativetradesman6833 4 года назад +1

    I’m having the exact same issue with a 09’ cgam120. I looked on 360 for parts but there is 3 different part numbers for modules and motors. Do you remember the part numbers for the angle valve and the stepper motor?

    • @UlisesPalacios
      @UlisesPalacios  4 года назад

      Creative Tradesman what’s the serial number. I just replaced one on a 70 ton yesterday. You will need to order the part number that starts with Val and it’s a good idea to replace the module as well

    • @creativetradesman6833
      @creativetradesman6833 4 года назад

      Ulises Palacios is the stepper motor a MOT or an MOD?

  • @norikghoorchian5128
    @norikghoorchian5128 3 года назад +1

    I think I have same problem whit carrier 40 ton chiller. Any way thanks a lot for sharing this video.

    • @UlisesPalacios
      @UlisesPalacios  3 года назад

      Thanks for watching. I’ve had this issue on 2 trane chillers.

  • @robertmason4334
    @robertmason4334 Год назад

    What is that tool called to power exv

  • @SombraLocs
    @SombraLocs 4 года назад

    I’m thinking of getting that SM-12.

  • @SombraLocs
    @SombraLocs 2 года назад +1

    What did you use to take the valve apart?

    • @UlisesPalacios
      @UlisesPalacios  2 года назад +1

      I used a Klein skinny jaw adjusted wrench to
      Hold the valve on the flat spots and a dang pipe wrench to loosen the motorized part of the valve. I heard a crows foot works also

    • @SombraLocs
      @SombraLocs 2 года назад

      @@UlisesPalacios Thanks!

    • @UlisesPalacios
      @UlisesPalacios  2 года назад

      For sure. They are one there pretty tight.

    • @UlisesPalacios
      @UlisesPalacios  2 года назад +1

      When you reassemble it. It doesn’t have to be super tight.

  • @marijoprugovecki2205
    @marijoprugovecki2205 3 года назад

    Hay do you work whit sporlan seri .. KS EV

  • @Oz_is_on_fire
    @Oz_is_on_fire 4 года назад

    Cool. Nice share homie!

  • @adnanqamar4398
    @adnanqamar4398 2 года назад

    hi ULises i have the same issue with cgam 70 machine ,chiller loading alarm of loss of charge.even the parameters are ok.
    some time chiller load alarm after 24 hours some time 16 hours.i had replaced suction sensor and transducer.still same issue.

    • @davemaldonado2496
      @davemaldonado2496 2 года назад

      have you come up with a solution? having low super heat issue w/ cgam 30

  • @izharraza7995
    @izharraza7995 2 года назад

    SIR TARN CHILLER MODEL RTAF WHAT THIS PASWAD LLID BINDING SETTING ON DISPLAY

  • @Bluecollarrebel
    @Bluecollarrebel 4 года назад +1

    Nice👍

  • @anthonymastello1573
    @anthonymastello1573 4 года назад

    There were some software issues with those LLIDS/Controller early on. All you have to do is unbind the EXV and then rebind and download new software to LLID.

    • @UlisesPalacios
      @UlisesPalacios  4 года назад +1

      Anthony Mastello yup. . I have the bulletin. This chiller didn’t fall into those years but I went ahead and updated the software. It’s a 2017. Have you come across this issue?

    • @anthonymastello1573
      @anthonymastello1573 4 года назад

      @@UlisesPalacios I haven't. Do you know if someone changed the EXV recalibration time in the feature settings?

    • @UlisesPalacios
      @UlisesPalacios  4 года назад +1

      Anthony Mastello no. It doesn’t look like it. It’s set to every 24 hours.

    • @UlisesPalacios
      @UlisesPalacios  4 года назад

      Anthony Mastello it’s a 2017 CGAM

    • @anthonymastello1573
      @anthonymastello1573 4 года назад

      @@UlisesPalacios okay, yeah default is 24 hours. I'd be worried if someone changed it to a shorter time. Does the chiller short cycle?

  • @SombraLocs
    @SombraLocs 4 года назад +1

    What type of chiller was it?

  • @Randylazz
    @Randylazz 4 года назад

    Good stuff.......