Testing my HVAC fire alarm duct detector and HVAC shut down failure. Home fire alarm system

Поделиться
HTML-код
  • Опубликовано: 22 авг 2024

Комментарии • 53

  • @shadowof1155
    @shadowof1155 10 месяцев назад +9

    Freshman year of high school we had a kind of "prom" style party for freshmen only and they had fog machines that went off every so often for specific songs... well the duct detector threw a fit and set off the fire alarms lol at least we knew they worked but it stopped the party for about an hour while fire crews double checked to make sure it wasn't something else

    • @KanoaDeCastro
      @KanoaDeCastro 10 месяцев назад +1

      Well at least they know it's working correctly.

    • @BotvacProductions469
      @BotvacProductions469 3 дня назад

      LMAOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOOO

  • @Richard-zz2cb
    @Richard-zz2cb 10 месяцев назад +3

    HVAC Tech here.
    Great video and demonstration! What probably happened about the air handler not shutting down was most likely because of the variable speed blower motor, which stays on for 90 seconds after the call for cooling/heating/fan is no longer calling, on most Tranes (American standards) this does occur and on other brands too.

    • @nics-systems-electric
      @nics-systems-electric  10 месяцев назад

      Yeah that would make sense but that kept running after the board had no power at all which I found interesting

    • @Richard-zz2cb
      @Richard-zz2cb 10 месяцев назад

      @@nics-systems-electric Variable speed or ecm/x-13 motors have their own separate board inside the actual motor, if the air handler still has power going to the legs it still will run no matter if the board lost power. They run 90 seconds after 24v power has been disconnected (voltage from the 24 volt thermostat line), unless if the high voltage 240v power is disconnected as well

  • @RossTheGenMan
    @RossTheGenMan 10 месяцев назад +6

    You may need to change to a relay that interrupts the high voltage to the HVAC unit to ensure shutdown. Great content. Fire alarm system looks good. Still anticipating the video on the garage link.

    • @nics-systems-electric
      @nics-systems-electric  10 месяцев назад +7

      Yes that's what I've done so it now kills power to the primary side of the transformer and the power directly to the blower motor that will be the video on Saturday

  • @sheagoff6009
    @sheagoff6009 9 месяцев назад +1

    The dog is so chill. Doesn’t even care about the fire alarms

  • @fatality_x0x0
    @fatality_x0x0 10 месяцев назад +1

    This house system is amazing! I like the L-Series low frequency sounders.

  • @elektrokinesis4150
    @elektrokinesis4150 10 месяцев назад +1

    the reason why they say supply air is to prevent the furnace from spewing smoke into the living space if it catches on fire or the core starts leaking combustion gasses

    • @nics-systems-electric
      @nics-systems-electric  10 месяцев назад +1

      Yeah I understand that if it's a gas furnace this is pure electric though so it doesn't pose as much more of a risk than fan forced heaters for my location duct detection is only required if a AHU supplies multiple levels or zones so is purely just for the spread of smoke

  • @Big_Noob-ROBLOX
    @Big_Noob-ROBLOX 10 месяцев назад

    These tests are THE BEST and I only watch your Fire Alarm video and did forget something in the video?🤔

  • @user-fr5ry2tv2q
    @user-fr5ry2tv2q 10 месяцев назад +3

    I like this fire alarm content very much. Thank you for this content 😊.

  • @stephengreene3134
    @stephengreene3134 10 месяцев назад

    Great video! Doing tests like this helps to see where the system still needs improvement. I work in production and can defiantly verify that fog machines set of fire alarms. Its always a fun time when we have to evacuate the place because someone went to heavy on the fog haha.

  • @topher8634
    @topher8634 10 месяцев назад

    You may have already figured it out but on these blower motors there is a signal wire or wires that come from the board you're interrupting power to; and a 24 volt that is the "G" terminal from the stat or in your case the EIM below your duct detector. I'm guessing if you're taking away board power but not all of the control power the motor will just not change its status or be able to vary the speed. I still recommend interrupting the 24 volt secondary on the trans or using the S/D terminals if they exist and it's practical. But I'm sure you've already whipped it.

  • @hqgirl567
    @hqgirl567 10 месяцев назад

    Very interesting to learn about this especially since I love fire alarms

  • @HJCF0520
    @HJCF0520 10 месяцев назад

    Very nice!!

  • @leafmk
    @leafmk 10 месяцев назад

    Great video! Really cool Nic! Tho Some issues with the HVAC shutdown.

  • @Bbrd-st3zk
    @Bbrd-st3zk 10 месяцев назад

    Thats good that you test your system

  • @bradwilmot5066
    @bradwilmot5066 10 месяцев назад +1

    ECM motor in the furnace may stay in its' last configuration when power to the board is dropped... you might have to break R between the thermostat and the board to eliminate the call for fan (I assume you have FAN on the thermostat to on). EDIT: Simpler to put both of the wires off the right terminal on the 24V transformer on the load side of the fire relay (IIRC, you only interrupted one of them (power to the board),

    • @bradwilmot5066
      @bradwilmot5066 10 месяцев назад

      Never mind on the transformer... just went back and looked, and it was one of the primary side connections that I thought was paired with the red wire... I'd break R between the board and the thermostat.

    • @nics-systems-electric
      @nics-systems-electric  10 месяцев назад

      That might work if I had a conventional thermostat however it's a wireless thermostat where it just is two wires for power but will still communicate if that power is dropped

    • @bradwilmot5066
      @bradwilmot5066 10 месяцев назад

      @@nics-systems-electric So the wireless radio is built into the furnace? (I do commercial HVAC, not residential...) All of the wireless stats I've dealt with had a radio that connected to the furnace like a standard stat.

    • @nics-systems-electric
      @nics-systems-electric  10 месяцев назад

      @@bradwilmot5066 there's a module on the side of the furnace which is I guess what connects to the thermostat wirelessly

    • @bradwilmot5066
      @bradwilmot5066 10 месяцев назад

      @@nics-systems-electric According to American Standard's applications guide, break the R wire between that module and the furnace board, and it should shut down. (youtube won't let me post the link to the applications guide)

  • @HenBasketFireAlarms
    @HenBasketFireAlarms 10 месяцев назад

    Looking forward to the next video on this

  • @KidderVerse
    @KidderVerse 10 месяцев назад

    Hey Nic, I noticed since the last Duct Detector test You installed what appears to be a Honeywell Wireless Thermostat System, I wonder if that's why your experiencing your issues.

  • @keithpierce8458
    @keithpierce8458 10 месяцев назад

    That was a cool test

  • @rodgodx345
    @rodgodx345 4 месяца назад

    You know if u want u should add a duck detector tester switch.

  • @joeshearer1247
    @joeshearer1247 10 месяцев назад

    You will drive the humidity up very high by running fan continuously in cooling mode

    • @nics-systems-electric
      @nics-systems-electric  10 месяцев назад

      Definitely not it's just circulating air through the house and it's not humid anyways maybe it's different in other parts of the world I don't know but I do know it's not a problem here

  • @suchcone
    @suchcone 10 месяцев назад

    It was worth doing the test!

  • @noxious_nights
    @noxious_nights 2 месяца назад

    What's the box below the duct detector?

  • @SodiumInduction-hv
    @SodiumInduction-hv 10 месяцев назад

    cool

  • @user-fr5ry2tv2q
    @user-fr5ry2tv2q 10 месяцев назад

    Hey nic I got a great idea, why don't you connect both fire alarm system's together and when one fire alarm system turns on the other turns on. Your system will be extra safe like middle schools with portables. Do you agree.

    • @nics-systems-electric
      @nics-systems-electric  10 месяцев назад

      Yes I did they are tied together to put each other into a non-latching supervisory but they can't put each other into alarm as an alarm condition is always latching and you would have to reset both systems which is difficult to do without it re-setting off another one so it ends up like a dog chasing its own tail if you get what I'm saying

    • @user-fr5ry2tv2q
      @user-fr5ry2tv2q 10 месяцев назад

      @@nics-systems-electricoh I get it now. But you still have great fire alarm systems.

  • @ChrisTopher284765490
    @ChrisTopher284765490 10 месяцев назад

    Youll figure it out. You learn the most from mistakes.

  • @SDPP992
    @SDPP992 10 месяцев назад

    Is it killing 24v to the red wire on the stat???

    • @nics-systems-electric
      @nics-systems-electric  10 месяцев назад

      No it is a wireless thermostat the wires to thermostat only keep it powered up

    • @SDPP992
      @SDPP992 10 месяцев назад

      @@nics-systems-electric is there anything that resembles r-power w-heat y-cooling c-common g-fan, in the air handler??

    • @nics-systems-electric
      @nics-systems-electric  10 месяцев назад

      @@SDPP992 i'd have to look there's 14 different wires coming out of the wireless control board that communicates wirelessly to the thermostat either way it's not in a convenient place to tie into

  • @ebennett3655
    @ebennett3655 10 месяцев назад

    multi purpose test

  • @marksmith-ew7ir
    @marksmith-ew7ir 10 месяцев назад

    You have a work person who could asked that always with you on testing day's two bain are better than one.

    • @nics-systems-electric
      @nics-systems-electric  10 месяцев назад

      I had a plan of what I was going to do if this didn't work so that is what I did the video on that will be Saturday

  • @billeyjbob5000
    @billeyjbob5000 10 месяцев назад

    🎉😊

  • @TLNRO
    @TLNRO 10 месяцев назад

    Ayeeeee!!

  • @Chaeuraersat
    @Chaeuraersat 10 месяцев назад

    Hi

  • @Honekawasuneo646
    @Honekawasuneo646 3 месяца назад

    Does your home have the duct is the air condition?