  • AR FUNCTION TEST FOR LINE PROT. RELAY GE L90

Комментарии • 7

  • @mohamedhassan9657
    @mohamedhassan9657 7 лет назад +1

    thanks alot eng abdou .🙂😉

  • @muhannadabusaleh9981
    @muhannadabusaleh9981 4 года назад

    How I can configure Fault locater ?!

  • @mohamedhassan9657
    @mohamedhassan9657 7 лет назад

    eng abdou i have problem during testing AR , after relay give ar command and trip come again ar must be lock out because i have 1shot but actually relay give another command . do u have solution fir this problem??

    • @abdouamin5779
      @abdouamin5779  7 лет назад +1

      Mohamed Hassan check the reclaim time as it should long enough to prevent another shot up to your setting put it 60sec and check again

    • @mohamedhassan9657
      @mohamedhassan9657 7 лет назад

      Do u mean with reclam time (inc seq time) right??

    • @abdouamin5779
      @abdouamin5779  7 лет назад

      Mohamed Hassan yes

    • @mohamedhassan9657
      @mohamedhassan9657 7 лет назад

      I think when we put status of cb close to make reset , function of auto recloser start from the beginning