NFPA 14 Flow Rate Requirements for Standpipe & Hose System | Firefighting in Urdu

Поделиться
HTML-код
  • Опубликовано: 27 окт 2024

Комментарии • 103

  • @ermohammadaalamraeen6117
    @ermohammadaalamraeen6117 3 года назад +1

    Very useful presentation... Allah aap ko achhi kamyabi or sehat de..

  • @amjedhussaini3823
    @amjedhussaini3823 4 года назад +1

    Thanks a lot, Sir, YOur concepts are very clear & easy to understand. May Allah bless u

  • @incrediblethings11
    @incrediblethings11 4 года назад +1

    Tanveer Bhai
    Bht Zabardst.🙏🙏🙏🙏🙏🙏

  • @sulaimandawood8698
    @sulaimandawood8698 2 года назад +1

    AoA, mashallah very nice presentation...
    One thing confused me that ap ne pehlay kaha tha k 1st and 2nd stand 500 gpm hotay hain but example ap ne 250 rakha hai.. can you please elaborate?thanks

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      These are different conditions. Watch my standpipe systems videos

  • @skrasel6508
    @skrasel6508 4 года назад +2

    Hello Mr Tanweer,
    It seems you did really a good job. If you add one more picture for horizontal hose connection at 3:00 min of your video that will be more clearer for your visitors. In addition you may also classify the requirements for hose real VS hose rack as well.
    RASEL, CFPS, NFPA

    • @TanweerAhmed
      @TanweerAhmed  4 года назад

      Thanks

    • @skrasel6508
      @skrasel6508 4 года назад +1

      You are welcome if you need your content to review I would spare time for you great job, it's free of course. Furthermore, your presentation is smooth.
      I am certified Fire Protection Specialist from NFPA, USA

    • @TanweerAhmed
      @TanweerAhmed  4 года назад +1

      WhatsApp +923332472721
      It is my pleasure

    • @amtechhse167
      @amtechhse167 4 года назад

      nice

  • @lendssadiasa4814
    @lendssadiasa4814 Год назад +1

    please upload a subtittle or english version opf this video. thank you and hoping for you response to my concern. i am really greatefull some of your videos specially subtittle videos.

  • @setyopermadi2654
    @setyopermadi2654 2 месяца назад +1

    Sir, is NFPA require about painting pipe...thickness, layer , RLA

    • @TanweerAhmed
      @TanweerAhmed  2 месяца назад

      NFPA doesn't specify paint thickness or layers for pipes.

  • @M.k45
    @M.k45 2 года назад +1

    Sir can you please arrange all the playlist in a way that a beginner can easily start watching from 1st to last.
    it is still very helpful but sometimes I get confused like from where to start. which thing comes 1st etc.

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      It is difficult, however I will try

  • @M.k45
    @M.k45 Год назад +1

    sir in class 2 what is it mean by most remote hose connection? if im not getting confused there,s difference b/w hose connection and stand pipe. looking forward to your reply. thank you so much

    • @TanweerAhmed
      @TanweerAhmed  Год назад

      Most remote hose connection means, hose connection installed or want to install at away (farthest) location and pump head pressure calculation from this/that point.

  • @abduljabbaransari8462
    @abduljabbaransari8462 4 года назад +1

    Zabardast

  • @ahanahannahgladwin3870
    @ahanahannahgladwin3870 3 года назад +1

    Good

  • @mohammedshahbaz8861
    @mohammedshahbaz8861 4 года назад +2

    Thanks for this video and i would like to suggest something can u plz take any project fire fighting dwgs for example commercial building b+g+7 office building (which can include combined sprinkler and standpipe system) so that this will be very much clear for sure.
    Thanks & Regards.

  • @nizamuddinz4392
    @nizamuddinz4392 10 месяцев назад +1

    Can you pls tell us how to design water tank storage capacity for this stand pipe systems which has 1250gpm. How much minutes water need to supply 45 or 60 minutes

    • @TanweerAhmed
      @TanweerAhmed  10 месяцев назад

      Watch my video on this topic of tank

  • @vinayakjoshi1969
    @vinayakjoshi1969 3 года назад +1

    Sir but discharge of pump comes from 450lpm to 28880lpm where as you suggesting the discharge that too 1250gpm.as per my knowledge one gallon is 3.5ltrs by your calculations it comes 3600ltrs per minute.pl explain.

    • @TanweerAhmed
      @TanweerAhmed  3 года назад

      Kindly don't convert in liters and give values in GPM then can understand. Moreover, these all points taken from NFPA-14

  • @sameeraryan8327
    @sameeraryan8327 4 года назад +2

    Sir ap plz ek vedio bnaiye jisme mnc compny samil ho jo fire fighting or fire alarm installations krati.Mai fire fighters engineer hu sir plz

    • @amtechhse167
      @amtechhse167 4 года назад +1

      nice

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      Join my Telegram group "HVAC|MEP Engineering" for technical discussion and documents

  • @mrj8012
    @mrj8012 4 года назад +1

    Tanvir Bhi stAnd pipe agar 4 inch dia design hy.
    Jaisa k pipe k length 20 feet hoti hy kya har 20 feet par flanged joint hoo ga.
    Aur flange weld hoo gi.
    Please replay thanks

    • @TanweerAhmed
      @TanweerAhmed  4 года назад

      It will be weld and flange required where valves or other accessories to be joint with pipe.

    • @mrj8012
      @mrj8012 4 года назад +1

      Thanks for replay.
      Fire hydrant should be threaded despite Of flanged you say this In One Of urs video is it true please confirm.

    • @TanweerAhmed
      @TanweerAhmed  4 года назад +1

      Where pipe size is 2" or less then pipe joints to be threaded

    • @mrj8012
      @mrj8012 4 года назад +1

      Thanks
      It means if connection is 2 1/2 inch then It will be flanged hydrant.

  • @reduanhossain4613
    @reduanhossain4613 2 года назад +1

    Hello Sir,
    If The Building Is Stair 2 Nos
    Can i use 500 gpm?
    750 gpm standard.I Know That I will use 500gpm whice time?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      I think can use, further confirm from designer

  • @mepworld3385
    @mepworld3385 4 года назад +1

    Please clarify one thing. If i have 4 hose connection in one floor in 2nd stand pipe so as per this remote stand pipe has 500gpm and second pipe is 750gpm and additional pipes 250gpm.is this correct.

    • @TanweerAhmed
      @TanweerAhmed  4 года назад

      Kindly watch video again and review NFPA-14 reference page or document. I hope each confusion will be cleared.

  • @manjulalakmal8899
    @manjulalakmal8899 11 месяцев назад +1

    Hi sir,
    The flow rate 500gpm we must calculate at the most remote hose station of at pump discharge outlet?
    Pls explain this.

  • @thepurposeofmyexistence2511
    @thepurposeofmyexistence2511 3 года назад +1

    Dear sir , could y explain when do we single standpipe system , and when do we use combined standpipe system , i mean whats is rquiremnt to use sprinklers syayem along with hose cabinet , like is there area rquirement or somthing like that

    • @TanweerAhmed
      @TanweerAhmed  3 года назад +1

      Hose connection, hose reel or landing valve used in entrance, exit, staircase, lobby locations and sprinklers are used in all general areas. If you want to install both sprinklers and hose connections then this system will be combined, otherwise single system

    • @thepurposeofmyexistence2511
      @thepurposeofmyexistence2511 3 года назад +1

      @@TanweerAhmed i got yr point , but is it possible that in high raise building can i use only automated sprinklers system , and for satircase i will not use it may be if the cost increase . Or nfpa state that its compalsery to use combined syatem in high raise building

    • @TanweerAhmed
      @TanweerAhmed  3 года назад +1

      Mostly combined system is used in high rises building as per NFPA requirements.

    • @thepurposeofmyexistence2511
      @thepurposeofmyexistence2511 3 года назад +1

      @@TanweerAhmed ok thank y sir

  • @imrankaderhussainkn5680
    @imrankaderhussainkn5680 2 года назад +1

    Dear Tanweer, What is that horizontal standpipe gpm should be 750 if it is serving with more than one hose connection means, could you explain sir?.....

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      Watch my more videos on standpipe

    • @imrankaderhussainkn5680
      @imrankaderhussainkn5680 2 года назад

      @@TanweerAhmed you mean if the hose connection is more than one, then the wet riser gpm has to be 750 instead of 500 gpm , right?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      There are different conditions and subject conditions decided riser as explained in video

  • @shahhadi635
    @shahhadi635 4 года назад +1

    Thanks alot

  • @nizamuddinz4392
    @nizamuddinz4392 10 месяцев назад +1

    How to calculate numbers of raiser?. One raiser service for how much area.

  • @jimmyjohn4070
    @jimmyjohn4070 4 года назад +2

    👍

  • @mepworld3385
    @mepworld3385 4 года назад +2

    Building area 80000ft2 is considered as 1 floor area or total all floor area

  • @dailydose789
    @dailydose789 4 года назад +2

    👏

  • @passionateengineer04
    @passionateengineer04 2 года назад

    What will be the standpipe size for class 2 only?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад +1

      At least 2.5" for two hose connections for class2 only

  • @ShakeelAhmad-hd3yp
    @ShakeelAhmad-hd3yp Год назад +1

    how could we bring 1750 gpm to 1250, if calculation is for 1750 then how to make it 1250, which method is to use.

    • @TanweerAhmed
      @TanweerAhmed  Год назад

      Watch videos and understand. If you have any confusion then learn from designer

  • @sahijadqureshi2648
    @sahijadqureshi2648 4 года назад

    Nice

  • @robertbangalore1628
    @robertbangalore1628 4 года назад +2

    I mean ,Pump GPM

    • @TanweerAhmed
      @TanweerAhmed  4 года назад

      Yes, total flow is pump flow including all loses & pipe length as per NFPA-14

    • @amtechhse167
      @amtechhse167 4 года назад

      nice

  • @yusufahmed7819
    @yusufahmed7819 4 года назад +1

    Hello Mr. Tanweer,
    I have a project where there are 22 standpipe risers. There is 1 electric pump, 1 diesel pump each of 1250 gpm. My local code states that , "All standpipes in standpipe system shall be sized so that they will provide a minimum flow 500 gpm. In standpipe system with more than one standpipe, the supply piping shall be sized for the minimum flow 500 gpm for the first standpipe plus 1000 litre per minute for each additional standpipe. The total number of such additional standpipes shall not be more than 8."
    Does this mean I need to get another set of pumps if the total standpipe riser exceeds more than 9?

    • @TanweerAhmed
      @TanweerAhmed  4 года назад

      Can you share local code ? on my WhatsApp +923332472721

    • @yusufahmed7819
      @yusufahmed7819 4 года назад

      @@TanweerAhmed BNBC 2006 (Bangladesh National Building Code) code no 4.2.3.2

    • @TanweerAhmed
      @TanweerAhmed  4 года назад

      I am not familiar with this code but all codes follows NFPA, I think so... How much area is for 22 nos. standpipes ?

    • @TanweerAhmed
      @TanweerAhmed  4 года назад

      NFPA say that non sprinkler standpipes shall be max flow 1250 GPM.

  • @robertbangalore1628
    @robertbangalore1628 4 года назад +1

    Sir ,if total GPM above 1250 for non-sprinkler riser wat we have to do?

    • @TanweerAhmed
      @TanweerAhmed  4 года назад

      Follow NFPA-14

    • @TanweerAhmed
      @TanweerAhmed  4 года назад

      These are for light & ordinary hazard. For extra hazard follow hydraulic calculations in the light of NFPA-14

    • @nayeemsaleem7466
      @nayeemsaleem7466 4 года назад +1

      Consider your pump selection to be 1250 gpm as shown in this video. Max 1250gpm irrespective to how many riser you have. I hope it is clear for you now.

  • @dyphan7522
    @dyphan7522 3 года назад +1

    English version please 🙏🏻

  • @singhrana479
    @singhrana479 4 года назад +1

    Sir Kahan se ho aap muje bhi Hydrants system ki knowledge chahiye aap charge kroge wo bhi dene k liye teyar hu aap apna contact share kr di jiye jis se aapse baat kr sku

  • @salmanakhtar8382
    @salmanakhtar8382 2 года назад

    In this whole presentation one thing I didn't understand,how the class is define?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      What didn't understand about Class?

    • @salmanakhtar8382
      @salmanakhtar8382 2 года назад

      Class 1 2 3 , sir kaise identify kre?

    • @TanweerAhmed
      @TanweerAhmed  2 года назад +2

      1. Class-I means 2.5" hose valve connection with standpipe
      2. Class-II means 1.5" or less diameter with Hose Rack or Hose Connection with standpipe
      3. Class-III is combination of Class-I and Class-II means 2.5" connection along with 1.5" or less Dian hose rack or hose reel

    • @salmanakhtar8382
      @salmanakhtar8382 2 года назад

      Thank u sir
      Jazakallah

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      Welcome

  • @abduljabbaransari8462
    @abduljabbaransari8462 4 года назад +1

    Plz mor upload videos

    • @TanweerAhmed
      @TanweerAhmed  4 года назад

      مھرباني.... انشاءالله

  • @sameeraryan8327
    @sameeraryan8327 4 года назад +2

    Sir ap plz ek vedio bnaiye jisme mnc compny samil ho jo fire fighting or fire alarm installations krati.Mai fire fighters engineer hu sir plz

    • @amtechhse167
      @amtechhse167 4 года назад +1

      nice

    • @TanweerAhmed
      @TanweerAhmed  2 года назад

      Join my Telegram group "HVAC|MEP Engineering" for technical discussion and documents

  • @sameeraryan8327
    @sameeraryan8327 4 года назад +1

    Sir ap plz ek vedio bnaiye jisme mnc compny samil ho jo fire fighting or fire alarm installations krati.Mai fire fighters engineer hu sir plz