How to do Short circuit current calculation|Cable sizing calculation part-3

Поделиться
HTML-код
  • Опубликовано: 23 окт 2024

Комментарии • 27

  • @FaheemNawazwarangalwaale
    @FaheemNawazwarangalwaale 3 года назад +1

    For power DB u considered default system SC current is 10ka,how can we decide, because I have another panel DGLV of 250A main with 3ways of 250A each. Does it depends on load? Please reply. Thanks

  • @Kk-hs4qf
    @Kk-hs4qf 3 года назад +1

    Suppose my office is getting power from a 100kva transformer with sc rating 3kA. Should I select my cable based on 3kA or power DB sc rating of 10kA?

  • @thesilentgamer4210
    @thesilentgamer4210 11 месяцев назад

    Hello sir. Thank you for the great tutorial. Can I use 2 runs of same size smaller cable to compensate the kA rating? Example the system fault kA is 15kA. then 1 run 2 single core cable with 10kA capacity each.. is this okay?

    • @thesilentgamer4210
      @thesilentgamer4210 11 месяцев назад

      I hope to hear from you guys . Thank you for sharing your knowledge

  • @mohanalria8101
    @mohanalria8101 2 года назад

    Very informative video,sir please make video how to calculate short circuit current

  • @satheshdharumu3262
    @satheshdharumu3262 3 года назад +1

    Do you know prospective short circuit current ? If you know pls explain how to calculate for mccb mpcb etc

  • @ushashmi
    @ushashmi 2 года назад +1

    what is the effect on short circuit capacity if we increase number of runs of cables per phase ?

  • @heynid
    @heynid 3 года назад

    Hi, Can you please share, Where I can find the short circuit current of DBs and other equipment? I mean is there any standard/Table for that? Like IEC classification?

  • @openeering
    @openeering 2 года назад

    The best

  • @ranjan1436
    @ranjan1436 3 года назад +1

    Is it necessary to size a cable, if the length of the cable less than 100 Mts?

    • @electricalmastar
      @electricalmastar  3 года назад

      Thanks for your comments and yes it is necessary to consider cable calculation below 100m

  • @stevengerrard286
    @stevengerrard286 3 года назад +1

    Can i use two cable of 70 mm sq to increase the cable short circuit capacity of 20 A.?

    • @electricalmastar
      @electricalmastar  3 года назад

      Yes off course you can use 2 numbers of cable to increase short circuit withstanding capacity

  • @charithaniroshan5663
    @charithaniroshan5663 3 года назад

    Can you please mention the relevant IEC or BS standard for this equation ?

  • @anandababupvn1938
    @anandababupvn1938 3 года назад

    Please provide reference international standard for this formula. Is this mentioned in IEC 60502.

  • @bollinenipavan5830
    @bollinenipavan5830 3 года назад

    sir please make the video for power factor demaand factor efficiency of load

  • @gzoro1
    @gzoro1 3 года назад

    Hello How we now the system short circuit current ? In this example is 10 kA

  • @rebokahawaki6591
    @rebokahawaki6591 2 года назад

    Kind Sir
    How much is the Temperature in this Formula?

  • @ranjan1436
    @ranjan1436 3 года назад +1

    You have not considered the breaker closing time?

  • @umakantkamalapure1459
    @umakantkamalapure1459 4 года назад +1

    What basis short circuit current calculation in selection MCCB income, outgoing feeder

    • @electricalmastar
      @electricalmastar  4 года назад

      Thanks for your comments, for circuit breaker sizing i already posted one video please check the link
      ruclips.net/video/kh3uaPrxMUA/видео.html

  • @baruaanup
    @baruaanup 2 года назад

    5:38 where can I get the chart that, 10kA for power DB and others. Thanks

  • @jabbarfahad687
    @jabbarfahad687 Год назад

    thank

  • @umarchohangujjar233
    @umarchohangujjar233 2 года назад

    Dear Sir,
    I am really thankful to you for this lecture.
    Please make a video on how to find short circuit current of motor.
    Regards

  • @RizwanKhan_99
    @RizwanKhan_99 3 года назад

    Where 143.08 came from