For power DB u considered default system SC current is 10ka,how can we decide, because I have another panel DGLV of 250A main with 3ways of 250A each. Does it depends on load? Please reply. Thanks
Hello sir. Thank you for the great tutorial. Can I use 2 runs of same size smaller cable to compensate the kA rating? Example the system fault kA is 15kA. then 1 run 2 single core cable with 10kA capacity each.. is this okay?
Hi, Can you please share, Where I can find the short circuit current of DBs and other equipment? I mean is there any standard/Table for that? Like IEC classification?
For power DB u considered default system SC current is 10ka,how can we decide, because I have another panel DGLV of 250A main with 3ways of 250A each. Does it depends on load? Please reply. Thanks
Suppose my office is getting power from a 100kva transformer with sc rating 3kA. Should I select my cable based on 3kA or power DB sc rating of 10kA?
Hello sir. Thank you for the great tutorial. Can I use 2 runs of same size smaller cable to compensate the kA rating? Example the system fault kA is 15kA. then 1 run 2 single core cable with 10kA capacity each.. is this okay?
I hope to hear from you guys . Thank you for sharing your knowledge
Very informative video,sir please make video how to calculate short circuit current
Do you know prospective short circuit current ? If you know pls explain how to calculate for mccb mpcb etc
what is the effect on short circuit capacity if we increase number of runs of cables per phase ?
Hi, Can you please share, Where I can find the short circuit current of DBs and other equipment? I mean is there any standard/Table for that? Like IEC classification?
The best
Is it necessary to size a cable, if the length of the cable less than 100 Mts?
Thanks for your comments and yes it is necessary to consider cable calculation below 100m
Can i use two cable of 70 mm sq to increase the cable short circuit capacity of 20 A.?
Yes off course you can use 2 numbers of cable to increase short circuit withstanding capacity
Can you please mention the relevant IEC or BS standard for this equation ?
Please provide reference international standard for this formula. Is this mentioned in IEC 60502.
sir please make the video for power factor demaand factor efficiency of load
Hello How we now the system short circuit current ? In this example is 10 kA
Kind Sir
How much is the Temperature in this Formula?
You have not considered the breaker closing time?
I have considered as per standard time 1sec
What basis short circuit current calculation in selection MCCB income, outgoing feeder
Thanks for your comments, for circuit breaker sizing i already posted one video please check the link
ruclips.net/video/kh3uaPrxMUA/видео.html
5:38 where can I get the chart that, 10kA for power DB and others. Thanks
thank
Dear Sir,
I am really thankful to you for this lecture.
Please make a video on how to find short circuit current of motor.
Regards
Where 143.08 came from