NFPA 13 - ROLLED PAPER STORAGE

Поделиться
HTML-код
  • Опубликовано: 2 дек 2024

Комментарии • 3

  • @O.H91
    @O.H91  2 дня назад

    Control mode specific area CMSA sprinklers are only applicable to palletized & solid-piled storage , not allowed to be used with bin box and shelf storage.

  • @O.H91
    @O.H91  13 дней назад

    Mentioned data is for sprinkler system only, for requirements of FHCs and hose allowance follow,refer to CH 20 & 21

    • @O.H91
      @O.H91  13 дней назад

      Table 20.15.2.6, For roll paper storage hose allowance as following:-
      1- CMDA 500 gpm for 120min.
      2- CMSA 500 gpm for 120min.
      3- ESFR 250 gpm for 60min.