Chiller Plant Equipment and Piping Design

Поделиться
HTML-код
  • Опубликовано: 21 ноя 2024

Комментарии • 2

  • @hvacdesignsolutions
    @hvacdesignsolutions Год назад

    You're missing a minimum flow bypass valve, on the VPF schematic.

    • @TacoHVACtv
      @TacoHVACtv  Год назад

      Hello Damian,
      Thank you for attending the Taco Tuesday webinar series and we spoke with Rich and Brett and here is their response:
      "The diagrams indicated are for instructional purposes only and are not intended to show all system possibilities.
      Although many systems may require a minimum flow bypass on a Variable Primary Flow (VPF) system, not all systems will require a minimum flow bypass. The engineer of record should make that decision based upon the specific characteristics of the system. "