How Star Delta Starters Work - Control Circuit Explained

Поделиться
HTML-код
  • Опубликовано: 1 дек 2024

Комментарии • 175

  • @seanakiiki7670
    @seanakiiki7670 8 месяцев назад

    I really appreciate u, u have helped me as an electrician to understand more about automation industrial engineering,long live, god bless you, iwill let my son studying begin to follow ur lectures on line, thxu
    Best regards

  • @berkotropia
    @berkotropia Год назад +8

    You are very nice guy who explains simply and accurately. The problem is this industrial electrics that there are too many arrogant and bully engineers there who purposely confuse you and let you down. If I had more people like you, my studies could have been less painful. Thanks!

    • @electreca1
      @electreca1  Год назад +1

      I appreciate the compliment and thanks for watching.

  • @hagenimanatheogene3217
    @hagenimanatheogene3217 Месяц назад

    Keep it ahead about giving the whole world ,
    advanced electrical knowledge and skills

  • @GoldenKamwendo-ib6si
    @GoldenKamwendo-ib6si Месяц назад

    You are a nice teacher Sir. You have helped me understand this circuit.Keep it up.

  • @VeenchisTechBites
    @VeenchisTechBites Год назад

    I love this channel now,I found it today and am really grateful🎉🎉good work mwalimu,came here after not understanding in class😅

  • @vincentowira6743
    @vincentowira6743 2 года назад +15

    Good job bro, but main and the star contactor comes in at the same time.

  • @umarsharif-g7y
    @umarsharif-g7y 4 месяца назад +1

    you are very nice brother.very easy explain to understand us.thank you so much.

  • @thabisodlamini41
    @thabisodlamini41 2 года назад +1

    Thanks Sir, today you made my day well presented video I did understand every single word you spoken

    • @electreca1
      @electreca1  2 года назад +1

      Glad to hear that and Thanks for watching

  • @elibarickandrew4496
    @elibarickandrew4496 Год назад +2

    Good explanation but you said in this circuit star contactor should energize first before main contactor. Qn why star first while the motor will not start if both main and star are not energized.

    • @johnkapauo2995
      @johnkapauo2995 6 месяцев назад

      He just explain the logic here. If you see it properly, I think you'll see, the main idea here is the ADDRESS. The contact that the main rely on relies on the address of the star coil, so star has to come ON first followed by the main, bear in mind that that happens in short space of time (as he mentioned, by the blink of an eye), so if the motor relies on the main, then the motor won't start if star coil is OFF or not energized. This is the result of main not being energized, hence causes the motor to remain OFF.

  • @OloboChristopher
    @OloboChristopher Месяц назад

    I like your lectures

  • @erick2pac360
    @erick2pac360 Год назад +1

    Uv made me clearer

  • @LameckPhiri-ex9bj
    @LameckPhiri-ex9bj Год назад

    Good job bro continue teaching us

  • @siamankangasam6414
    @siamankangasam6414 2 года назад

    You're a great engineer sir

  • @sohailjanjua123
    @sohailjanjua123 Год назад +1

    Hi , I like your video. Thanks

  • @seanakiiki7670
    @seanakiiki7670 8 месяцев назад

    I love u so much ur videos are good and well scientifically explained,

  • @abednigojustin3508
    @abednigojustin3508 5 месяцев назад +5

    Great job brother....but just a suggestion...why not use the auxiliary contact (NO) of the delta contactor to keep the main contactor energised when the star connection time elapses..... because using the auxiliary contact of the main contactor mean when the start push button is pressed the main contact also start immediately....

  • @siamankangasam6414
    @siamankangasam6414 2 года назад

    Very lovely, you have made me go back to school

  • @samuelmainakamunye571
    @samuelmainakamunye571 Год назад

    good work and educative lesson

  • @Prosper_Electrical.
    @Prosper_Electrical. 3 года назад

    I follow you Everytime

  • @mathewsnyirenda4004
    @mathewsnyirenda4004 Год назад

    Great works indeed. Am learning every day

  • @tinashemuparangi2978
    @tinashemuparangi2978 3 года назад +5

    mr sir there is no reason to interlock the main contactor.
    the main and the star come in together at the same time. lets assume we are using pneumatic timer that means it should be coupled with the main contactor..maybe u can add a hold in for delta and disconnects the timer from the by adding normallt ope interlock for delta on timer circuit.

  • @SamuelNdimba
    @SamuelNdimba 10 месяцев назад

    Great job sir❤

  • @mwangijohn538
    @mwangijohn538 3 года назад +4

    Thanks David, during demonstration,u said this goes here , and that goes there, especially energizing the main contactor, there are terminal, there marked 13 ,22 and 14: and 21 so which one do mean inside nor out, please clarify by naming the terminal nos and either no or nc

    • @umakantamirdha9019
      @umakantamirdha9019 2 года назад +1

      Pppppppp hi nhi ho skta ki a hai pyar ki asi thila ok I

  • @morgankpabitey1837
    @morgankpabitey1837 3 года назад +2

    Thank you so much. This is crystal clear.

  • @mohdfauzeerosslie7515
    @mohdfauzeerosslie7515 Год назад

    ty my man. simple explainantion.

  • @konnehzinnah3124
    @konnehzinnah3124 Год назад +1

    Thanks brother for the video. It's good.
    Point of injection:
    Use the main contactor NO across the start pb switch so it serves as the master switch; It will stop entire control network if the Stop Pb switch is pressed. The main contactor should work with both the star and delta contactor. The main contactor should control the timer coil from the action of its NO Auxiliary contact.
    It's the timer's duty to switch between the Star and Delta contactors with its NC and NO contacts respectively with the set time.

  • @bisoborwaseaneilly7080
    @bisoborwaseaneilly7080 2 года назад

    So good sir am learning and enjoying thxu

  • @ClementMwanda
    @ClementMwanda Месяц назад

    Please help me with a manual forward and automatic reverse starting of a 3 phase induction motor

  • @piusngibeyo5161
    @piusngibeyo5161 3 года назад

    We are approaching amillion subscribers, bro thanks for your videos that are educating am from turkana county

    • @electreca1
      @electreca1  3 года назад

      Thanks so much Pius....by the grace of God and hard work we will hit a million

    • @nkailefrance665
      @nkailefrance665 2 года назад

      Please add yu number sir if we need any assistance we will contact you.......or we can great group....

  • @ayodeleelijah3257
    @ayodeleelijah3257 Год назад

    Thanks for the explanation 👍👍👍

  • @denofilms2438
    @denofilms2438 Год назад

    Good job.. Iam requesting you do alarm bell sirens using relay for 8,12,14 pin.
    And using relay in controls more machines

    • @electreca1
      @electreca1  Год назад

      OK will consider, thanks for watching

  • @IzoKey-iy9zq
    @IzoKey-iy9zq 7 месяцев назад

    Thanks your for the teaching

  • @KudzaiisheMusonza
    @KudzaiisheMusonza Год назад

    Good explanation

  • @kumning3331
    @kumning3331 Год назад

    thanks, well presented

  • @erick2pac360
    @erick2pac360 Год назад +1

    Knowing starters and backups means that am done with automation??

  • @abdulhamidmirzaee3097
    @abdulhamidmirzaee3097 Год назад

    Hi. Thanks for the video. One question: Why the NO of the timer is needed before delta contactor. Delta contactor will energize without the timer NO being there.

    • @-1HUMANITY-
      @-1HUMANITY- 11 месяцев назад

      Can it gets energized without no

  • @mbuthianjoroge9434
    @mbuthianjoroge9434 3 года назад

    Kazi nzuri boss

  • @MutenderiYafesi
    @MutenderiYafesi 7 месяцев назад

    Good work papa

  • @jameschitala3753
    @jameschitala3753 8 месяцев назад

    Very educative sir....thanks alot. I have a question: if the main contactor energizes last then, which contactor does the holding role?

  • @bisoborwaseaneilly7080
    @bisoborwaseaneilly7080 2 года назад

    Sir ur very true and perfect thxu

  • @okolceaser6056
    @okolceaser6056 Год назад

    It's good on that circuit to protect the timer

  • @leomichael3433
    @leomichael3433 Год назад

    Good job thanks for this

  • @bonnymazhara1396
    @bonnymazhara1396 Год назад

    Thanks engineer

  • @umakanthbojanapalli3240
    @umakanthbojanapalli3240 3 года назад

    Valuable information sir

    • @electreca1
      @electreca1  3 года назад +1

      Thanks and welcome

    • @umakanthbojanapalli3240
      @umakanthbojanapalli3240 3 года назад

      @@electreca1 plz send you complete panel wiring video's interlock manually auto motor protected and all 11&33&110&220&400&600 kV vcb power really wiring and ct pt box termination and drawing and small trans former design wire selection core selection bobbins selection and formulas releate charts PDF and every panel wiring PDF and substation commission and PLC and every thing electric part send videos

  • @mahamudabdullahi7506
    @mahamudabdullahi7506 3 года назад

    You explained very well come up with practical. and I request you to repeat on forward and reverse especially on the indicators that is my big problem

  • @ebenvanstaden5364
    @ebenvanstaden5364 Год назад

    How long are timer set before the Delta get enrgized which are going to be brought in by the timer coil...because the minute you leave the start button ,the circuit will be de-energized,start wont be retained because the main contactor dont have power yet ....meaning the entire circuit will fall out again...star en timer

  • @ezekiellaini9530
    @ezekiellaini9530 2 года назад

    Well explained to the point 💪

  • @oyenaraymond6520
    @oyenaraymond6520 Год назад

    My question is star Auxiliary is closed or open? that's what am not getting....in the explanation u Said it's closed but in the diagram it's open so.....

  • @oviaudhimbamatuyeeviyiwana2819
    @oviaudhimbamatuyeeviyiwana2819 2 года назад

    Plus is the power being supplied through the main contactor or from where is the power coming from since on the main there is no where it's indicated as to where the power is coming from to the main contactor ?

  • @ssebuumaMusa-z6e
    @ssebuumaMusa-z6e 3 месяца назад

    Thanks sir kindly produce for me ,star delta starter reverse forward wiring diagram

  • @edwardpamedwardpam8843
    @edwardpamedwardpam8843 4 месяца назад

    Nice one

  • @CollinsMpundu
    @CollinsMpundu 11 месяцев назад

    This is very nice

  • @igwekelechifebian781
    @igwekelechifebian781 Год назад

    I was really getting the mode of operation,but got confused about the illustration on main contact connection after the star disengage

  • @lesliemaloba1825
    @lesliemaloba1825 2 года назад

    Great explanation indeed

  • @mahmoudkamal8673
    @mahmoudkamal8673 3 года назад

    great keep going sir

  • @robertmhlanga9028
    @robertmhlanga9028 3 месяца назад

    How much is one contactor and a time? I need them for my practicals

  • @martin6934
    @martin6934 Год назад

    How can someone solarize the induction motor especially the star delta ones?
    Which inverter?

  • @ongomsamuel2896
    @ongomsamuel2896 2 года назад

    Good Engineer

  • @kindmanmundingi8588
    @kindmanmundingi8588 Год назад

    What wil happen if a main contactor energised before the star and the star pulls in after?

  • @JOFREYNgimba-pk5ur
    @JOFREYNgimba-pk5ur Год назад

    You mean maincontactor Will consist Three auxiliary which is normal open?

  • @basilmasvikeni9931
    @basilmasvikeni9931 2 года назад

    Good stuff man

  • @anthonydicksonojih5079
    @anthonydicksonojih5079 2 года назад

    Thanks very much

  • @mwinemissarch9784
    @mwinemissarch9784 2 года назад

    Thank you

    • @electreca1
      @electreca1  2 года назад

      You're welcome

    • @TheAladinaladin
      @TheAladinaladin Год назад

      That s a bit complicated! What s happend if you don t have a star delta time relay? And you use to many NO aux contact from main contactor! I hawe one diagram much simple and wich never fail!

  • @learnwithemmy123
    @learnwithemmy123 3 года назад

    Very good content. Keep the good work.

  • @konithierry9475
    @konithierry9475 Год назад

    Good job bro please my question is how can you wire it involving emergency push button

    • @electreca1
      @electreca1  Год назад

      you can wire you Emagency buuton circuit beaker and Overload relay. thanks for watching

  • @nevermajola4402
    @nevermajola4402 2 года назад +2

    Remove normal open on the main that can make your circuit simple main and star can start together you just confused lot of people but pose uncessary normal open on Main

  • @bezibedie4259
    @bezibedie4259 Год назад

    How can you put an isolation switch in this wiring ?

  • @ishackbugum8179
    @ishackbugum8179 9 месяцев назад

    What is the purpose of the star Auxiliary contact on the main contactor sir

  • @prashanthsadam9048
    @prashanthsadam9048 11 месяцев назад

    Hi
    what will be happening if main contact and star contact at a time start

  • @sahiln3d514
    @sahiln3d514 3 года назад

    Good work , congrats.. But sorry we need pratical if possible . God help you

    • @electreca1
      @electreca1  3 года назад

      I did a practical video for this topic, however, some viewers requested more clarification on the circuit diagram.................. here is the practical video ruclips.net/video/we7MxJ0fjDM/видео.html
      Thanks for watching.

  • @adventurendaba9020
    @adventurendaba9020 3 года назад

    thank you broe

  • @geoffreysakala8496
    @geoffreysakala8496 6 месяцев назад

    Hi.... can i find a video on how to install a 3phase submersible pump

  • @MedadCard
    @MedadCard 5 месяцев назад

    Can you tell how it switches from high voltage to low?

  • @prashanthsadam9048
    @prashanthsadam9048 11 месяцев назад

    In this star delta connection after few seconds circuit will change star to delta in this time main contact in on position here any happend?

  • @odonggeorgerackara4885
    @odonggeorgerackara4885 Год назад

    Does it also apply to transformers

  • @fredericokasper7854
    @fredericokasper7854 2 года назад

    Thanks!

  • @bonnylasu7665
    @bonnylasu7665 Год назад

    Sir very interesting but can you change your colour of marker? Your writing not clear for star, delta wiring

  • @binnasser-rj5id
    @binnasser-rj5id Год назад

    Bro! My question is when push button pressed the phase will pass to Timer and start to count as as main contact make the also pass to normal close of timer and pass to Auxiliary contact of delta contact then to A1 of start contact, I'm confused to this Auxiliary contact which will put above the contact start since we use the NC aux when pass phase make and become open while holded to cont start why still make because NO means phase will blocked via to star contact ???

  • @muradzeynal
    @muradzeynal 2 года назад

    sir, why did you use that H switch, i couldn't quite catch that. My point is that if there is main auxiliary, what is the reason for using H switch?

    • @jmajuta2963
      @jmajuta2963 2 года назад

      The H aux is to hold the timer and the m contact is to hold the main contactor

  • @okolceaser6056
    @okolceaser6056 Год назад

    Timer protection these days is recommended coz the timers in market are week ,let the timer be switched from NC delta and on the timer switch NO put a hold cct from no delta

    • @okolceaser6056
      @okolceaser6056 Год назад

      Put NC for delta to switch timer ,then put hold on contact on timer NO to switch delta this will help timer to be always off when motor is running on delta contact

  • @oviaudhimbamatuyeeviyiwana2819
    @oviaudhimbamatuyeeviyiwana2819 2 года назад

    Why do we need the main contactor in our circuit. Is the circuit not gonna work if removed?

    • @electreca1
      @electreca1  2 года назад

      The main contactor help to hold the circuit that's why we use push button to make the circuit more safe to operate and reliable, if you remove main contactor then you have to use a switch(not push button) which will keep the timer permanently on during operation.
      As long as the timer is on, circuit will remain running.

  • @MohamedSavage-d7o
    @MohamedSavage-d7o Год назад

    Can you pls show me how do star delta foward reverse with four magnetic Contactor and one timmer

  • @CollinsMpundu
    @CollinsMpundu 11 месяцев назад

    Kindly am asking if you can assist me with the traffic light circuit diagram

  • @ericmassamaki2498
    @ericmassamaki2498 6 месяцев назад

    it's better you could write the tarminal number of those devices so that some of us could be easy to know after what goes to number what thank you.

  • @denofilms2438
    @denofilms2438 3 месяца назад

    That star oxilary is it 13-14 on Star

  • @AbaahoRobert
    @AbaahoRobert 7 дней назад

    KEEP IT ACHARD ABACK

  • @FowziaMohamud-pi5fh
    @FowziaMohamud-pi5fh Год назад

    Eng.what is the diffrence between delta connection and dol

  • @josephnthungu
    @josephnthungu 3 года назад

    Brother thank you for your video.But i have a qsn about the second Main auxilliary you have introduced down there.Can you just make a loop wire from Main auxilliary and bring down and bypass it,and connect at the second terminal of STAR AUXILLIARY BLOCK?

    • @electreca1
      @electreca1  3 года назад

      If you do that the Main contactor will engage before the Star, yet our primary goal is the Star to engage First

    • @josephnthungu
      @josephnthungu 3 года назад

      Bro.now it's clear now after i followed your video and demonstration

  • @zakariaabdi2316
    @zakariaabdi2316 3 года назад

    Teacher thanks for video 🙏....but sir if possible I need circuit connection please

    • @electreca1
      @electreca1  3 года назад

      That circuit i drew on the board is CONTROL CIRCUIT for star delta stater, unless you need a power circuit. you can find it here electrecasolutions.com/understanding-star-delta-starter/

    • @zakariaabdi2316
      @zakariaabdi2316 3 года назад

      Thanks Teacher

    • @ongomsamuel2896
      @ongomsamuel2896 2 года назад

      They gave us please but he can do it again

  • @Ngobisamuel-rh9sw
    @Ngobisamuel-rh9sw 7 месяцев назад

    Bro , I request u to take us through motor winding

  • @leonardchinonso7067
    @leonardchinonso7067 Год назад

    Pls. Can you do a video on electric motor rewinding

  • @nkosinathimnisi5990
    @nkosinathimnisi5990 3 года назад

    We have circuits that put in the main and star at the same time is it wrong ? If yes tell me why?

    • @ongomsamuel2896
      @ongomsamuel2896 2 года назад

      Do you deal with only 33kv or even the single phase

  • @solomonwanjala7182
    @solomonwanjala7182 2 месяца назад

    Main and star closes at the same time

  • @cyprianmakokha368
    @cyprianmakokha368 25 дней назад

    please do me that of float switch+ bladder tank switch+contactor+selector switch

  • @bobojanespaner9761
    @bobojanespaner9761 3 года назад

    please add temperature sensors on your circuits as well as use of vfds

  • @chidiemelobe1044
    @chidiemelobe1044 2 года назад +1

    Good. But I think it will be nice if the timer coil can be de-energize after switching to delta

    • @electreca1
      @electreca1  2 года назад +2

      The timer I used it Normally closed, so it has to be and remain energised to hold the Delta contactor on. If the timer coil de-energise then delta will lose power.
      What do you think?

  • @johntamrang9139
    @johntamrang9139 11 месяцев назад

    hello David. can you pls do a video on how to connect a 3phase ats signal cable to amf25 pls

    • @electreca1
      @electreca1  10 месяцев назад +1

      Will plan, thanks for watching

  • @viavictoreletrica3527
    @viavictoreletrica3527 2 года назад +1

    Excelente profissional

  • @LawrenceAnderson-c6w
    @LawrenceAnderson-c6w Год назад

    which of the connection is that'

    • @electreca1
      @electreca1  Год назад

      Kindly ask your question again.

  • @praisepola3886
    @praisepola3886 Год назад

    so a star and a mean work like a duble mcb