ITM Wet System Riser, Backflow and Connections

Поделиться
HTML-код
  • Опубликовано: 20 авг 2024
  • ITM Information about Wet System Riser, Backflow Preventers and Fire Department Connections for fire sprinkler systems.

Комментарии • 5

  • @TheGardista
    @TheGardista 2 года назад +2

    That 4” backflow device is installed 4-6” above the floor. A plumbing code is minimum 12” from the floor. Also, that FDC line definitely requires two check valves. An air compressor is placed on the floor , what is unacceptable.

  • @ericcorona4466
    @ericcorona4466 4 года назад +3

    Should they be 2 check valves ? One for each FDC and not just one. To prevent flow from one FDC to e other ?

    • @eliopinto1750
      @eliopinto1750 4 года назад +2

      Eric Corona jr that will depend on the type of hose valves. They might be using the flapping valves build in. But good observation

    • @briancook9579
      @briancook9579 3 года назад +1

      Great Point Bro!!

  • @tusarkamble1115
    @tusarkamble1115 2 года назад