Student's Guide - Safe Isolation

Поделиться
HTML-код
  • Опубликовано: 27 авг 2024
  • Steven Devine, author of Student’s Guide to the IET Wiring Regulations, takes us through the essential tools that should be in your toolkit. Buy the book from Amazon: www.amazon.co....
    To view more videos from the Student's Guide series please visit:
    tv.theiet.org/...
    For more updates and videos, please subscribe to our channel.
    / theiet
    Join the conversation now:
    @IETtv
    #IETtv
    More RUclips Video from The IET:
    / theiet
    LET'S CONNECT!
    / theinstituti. .
    / theiet
    www.theiet.org
    www.iet.tv

Комментарии • 10

  • @massey65man
    @massey65man 6 лет назад +2

    Well done Stephen on a comprehensive video. I didn't know such a book existed prior to watching this video. Just two observations from an NVQ L3 Electrotechnical Assessor that may assist anyone undertaking the AM2; I encourage apprentices to use LINE to identify the 3 line conductors instead of LIVE as the neutral is also determined as a "live" conductor. Secondly, I insist that apprentices put the test probe (the one without the indicating lights) onto the zero potential first when proving "DEAD" at the single phase voltage L-N and L-E part of the procedure, in case the unconnected test probe would become "live" due to a back-feed. Apparently these are two failure areas in the AM2 assessment if not correctly observed.

  • @flookoco2008
    @flookoco2008 2 года назад +1

    An excellent and professionally produced video. Good clear content presented in an interesting manner.

    • @theiet
      @theiet  2 года назад

      Glad you enjoyed it!

  • @joegroves446
    @joegroves446 4 года назад

    Good clear video,thanks

  • @samuraj7143
    @samuraj7143 6 лет назад +1

    Very good video! Only one issue. Student have asked about permision to switch the power off on the beginning before he isolated DB(shower circuit). Unfortunetely there is no instruction what to do after he finishes the job on shower circuit. Before he switch power back on he supposed to ask again for permision to do so in case somebody else would be working on that circuit without his knoledge (or on another circuit in case isolating whole DB as this could result in an accident-electric shock).

    • @theiet
      @theiet  6 лет назад +2

      Thank you for your comment and I am glad that you like the
      video. We are always happy to receive comments and suggestions as they help us
      to provide useful guidance. The safe isolation video is intended to help
      students pass assessments set by awarding organisations. If, in the
      workplace, more than one skilled person is working on an installation each
      person should carry out the safe isolation procedure and have their own locking
      devices in place for the circuit they are working on. If a hasp is used then
      additional padlocks can be placed to avoid the installation being re-energised
      until the last padlock is removed. I will look into providing more
      information and guidance on safe isolation in respect of what to do when two or
      more skilled persons are working on an installation or circuit.

  • @siyawashnishat9073
    @siyawashnishat9073 3 года назад

    Thanks

  • @herrklamm1454
    @herrklamm1454 4 года назад

    Guy sounds like Garth Marenghi.

  • @gbelectricks
    @gbelectricks 3 года назад

    Ask, knock, lock, key, sign, prove,test, prove👍

  • @dale2712
    @dale2712 4 года назад +1

    Well rubbish this was just sat in lesson bored and Kev pincher made us watch it